Panduit VeriSafe VS-CKP14-6, VeriSafe VS-CKP4-000 Installation Instructions Manual

Page 1
VeriSafe Insulation-Piercing
Connection Kits
Insulation-Piercing Connectors for
VeriSafe AVT Sensor Lead Tapping on Copper Conductors
Rev. 02 [10-2018]
INSTALLATION INSTRUCTIONS
Models: VS-CKP14-6, VS-CKP4-000
© Panduit Corp. 2018
PANDUIT VSC Series Insulation-Piercing Connectors are intended for use in simplifying installation and connection of PANDUIT VeriSafe AVT Absence of Voltage Testers to phase (run) conductors, per electrical code requirements, within the rated environmental and operational limitations according to regulatory / safety standard certifications or listings.
TO REDUCE THE RISK OF INJURY, USER MUST READ INSTALLATION INSTRUCTIONS BEFORE ATTEMPTING TO INSTALL
NOTE: In the interest of higher quality and value, Panduit products are continually being improved and updated. Consequently, pictures may vary from the enclosed product.
NOTE: Updates to this Installation Instructions may be available. Check www.panduit.com for the latest version of this manual.
Email:
techsupport@panduit.com
EU Website:
www.panduit.com/emea
EU Email:
emeatoolservicecenter
@panduit.com
www.panduit.com
Panduit Corp.
USA Technical Support
Tel: 800-777-3300
Panduit Europe • EMEA Service Center
Tel: +31 546 580 452 • Fax: +31 546 580 441
Page 2
© Panduit Corp. 2018
INSTALLATION INSTRUCTIONS
Models: VS-CKP14-6, VS-CKP4-000
Rev. 02 [10-2018]
DOC#: T-PMPI-322EN Page 2 of 4 Rev 02 [10-2018]
Safety Information
This installation instructions contains information and warnings which must be followed to ensure safe termination and operation of the Insulation-piercing Connectors and an AVT Device.
Always de-energize panel and verify absence of voltage in the panel before attempting to install
connector. Do not install connector on an energized conductor.
Installer must also follow all safety, installation, commissioning and operating steps from the
AVT Device Manual.
Connector is intended for one-time installation and use. Do not reuse nor re-install connector.
Connection Kit Contents
Connection Kits contain connectors and ferrules for installing an AVT Device, per below;
CONNECTION
KIT CATALOG
PART NUMBER
“RUN” Wire
(CODE WIRE)
“TAP” Wire AWG
(Terminated w/ Ferrule)
CONNECTOR
FERRULE
MIN. AWG
[METRIC, mm2]
MAX. AWG
[METRIC, mm2]
Catalog
P/N
Quantity
Catalog
P/N
Quantity
VS-CKP14-6
14 AWG
[2.1, r]
6 AWG
[13.3, r]
14 AWG STR
Class K
(Terminated w/ Ferrule)
VSC6
3
F80-12-M
12
VS-CKP4-000
4 AWG
[21.2, r]
3/0 AWG STR
[85, r]
VSC3/0
3
F80-12-M
12
Step-by-Step Installation Procedure
1. See FIGURE 1: Prepare (strip) AVT device sensor leads.
2. See FIGURE 1: Crimp ferrules F80-12-M onto sensor leads.
3. See FIGURE 1: Make locating mark on sensor leads.
4. See FIGURE 2: Review connector features.
5. See FIGURE 2: Loosen factory-tightened MAIN FASTENER at least 6 full turns before proceeding to the next step.
AFTER PROPER TERMINATION OF FERRULE, MARK LINE ON CONDUCTOR INSULATION FROM END OF CRIMPED FERRULE
STRIP SENSOR LEAD INSULATION
FERRULE F80-12-M
0.875”
FIGURE 1: PREPARATION OF FERRULES ONTO SENSOR LEADS
INSERTION PORTS FOR FULLY-INSERTED AND PROPERLY CRIMPED TAP WIRES (AVT SENSOR LEADS) INTO TERMINALS INSIDE THE CONNECTOR
T10 TORX TERMINAL SCREWS ARE ACCESSIBLE FROM THE TWO PORTS AND ARE USED TO ADJUST TERMINALS INSIDE THE CONNECTOR. TERMINALS ARE USED TO SECURE A PAIR OF COLOR-CODED, FULLY-INSERTED AND PROPERLY-CRIMPED TAP WIRES (AVT SENSOR LEADS) WITHIN TERMINALS
FIGURE 2: CONNECTOR FEATURES
MAIN FASTENER
Page 3
© Panduit Corp. 2018
INSTALLATION INSTRUCTIONS
Models: VS-CKP14-6, VS-CKP4-000
Rev. 02 [10-2018]
DOC#: T-PMPI-322EN Page 3 of 4 Rev 02 [10-2018]
Step-by-Step Installation Procedure (continued from page 2 of 4)
6. See FIGURE 3 and FIGURE 4: Inspect location of factory-tightened TERMINAL in each TAP WIRE port in connector.
Connector was shipped with each TERMINAL SCREW and TERMINAL in a factory-tightened state.
In a factory-tightened state, the TERMINAL blocks access to and restricts insertion of TAP WIRE.
Installer must loosen TERMINAL SCREW and push down on SCREW to ensure TERMINAL position
permits insertion of TAP WIRE.
REMOVE TAP TORQUE reminder label before proceeding to STEP 7.
7. See FIGURE 5: Loosen TERMINAL SCREW two turns and push down on SCREW to move TERMINAL.
Verify position of TERMINAL and repeat loosening two turns and repeat push down on the SCREW.
Repeat until TERMINAL is in the position shown in FIGURE 6. DO NOT completely loosen screw.
8. See FIGURE 6: Verify that TERMINAL is positioned at the bottom of port for TAP WIRE insertion.
TERMINAL must be positioned at bottom of port, permitting full-insertion of TAP WIRE.
COMPLETELY REMOVE TAP TORQUE LABEL FROM CONNECTOR BEFORE STEP 7
TERMINAL POSITION RESTRICTS INSERTION OF TAP WIRE
FIGURE 3: TERMINAL POSITION
FIGURE 4: DETAIL VIEW
TERMINAL OPENING IS VISIBLE WHEN POSITIONED AT THE BOTTOM OF THE WIRE PORT AND PERMITS FULL-INSERTION OF THE TAP WIRE
Top Housing outline shown for clarity of the Terminal position within the Connector
LOOSEN SCREW WITH T10 TORX TORQUE-DRIVER AND PUSH DOWN ON SCREW HEAD
FIGURE 5: LOOSEN TERMINAL SCREWS AND PUSH TERMINAL INTO PROPER POSITION
FIGURE 6: VERIFY TERMINALS ARE IN PROPER POSITION AND THAT TAP WIRE CAN BE FULLY-INSERTED
Page 4
© Panduit Corp. 2018
INSTALLATION INSTRUCTIONS
Models: VS-CKP14-6, VS-CKP4-000
Rev. 02 [10-2018]
DOC#: T-PMPI-322EN Page 4 of 4 Rev 02 [10-2018]
Step-by-Step Installation Procedure (continued from page 3 of 4)
9. See FIGURE 7: Insert a crimped, color-coded pair of AVT sensor leads into TAP WIRE terminals.
10. See FIGURE 7: Verify fully-inserted AVT sensor leads by verifying that “location mark” (STEP 3) is flush with the connector body at wire insertion port.
11. See FIGURE 7: Use torque-driver (T10 Torx drive) to tighten terminal screws to specified Torque, as listed on Connector packaging (also shown below in Connector Rating Information).
12. See FIGURE 8: Properly position connector onto phase conductor (RUN WIRE) and keep RUN WIRE centered with the circular recess during next step.
13. See FIGURE 8: Use torque-driver (SAE Hex) to tighten MAIN FASTENER, while keeping RUN WIRE centered with the circular recess of opening. Tighten until the specified TORQUE value is achieved and maintained for 5 seconds. Torque value is listed on Connector packaging (also shown below in Connector Rating Information).
CONNECTOR RATING INFORMATION
PANDUIT CATALOG P/N
VSC6
VSC3/0
MAX. Operating Temperature (°C)
90°C
MAX. Operating Voltage (Volts)
600V
RUN
WIRE
Torque-driver SAE Hex Size
(Main Fastener)
5/16”
3/8”
Installation Torque (Required)
40 in-lb
[4.52 Nm]
80 in-lb
[9.04 Nm]
Minimum Rated Wire Size, AWG
[Metric, mm2, rigid]
14 SOL 14 STR
[2.1, r]
4 SOL 4 STR
[21.2, r]
Maximum Rated Wire Size, AWG
[Metric, mm2, rigid]
6 SOL 6 STR
[13.3, r]
3/0 STR
[85, r]
TAP
WIRE
Torque-driver Installation Bit Size
T10 Torx
Torque-driver Installation Tool*
Wiha P/N 28502 (*recommended)
Installation Torque (Required)
7 in-lb
[0.79 Nm]
Minimum Rated Wire Size, AWG
14 STR Class K
Required Ferrule (Panduit P/N)
F80-12-M
Recommended Crimp Tool
(Panduit P/N)
CT-1160
USE TORQUE-DRIVER (T10 TORX) FOR TIGHTENING TERMINAL SCREWS TO SPECIFIED TORQUE. TORQUE VALUE IS LISTED ON CONNECTOR PACKAGING AND SHOWN BELOW IN
CONNECTOR RATING INFORMATION
INSERT WIRE FULLY UNTIL “LOCATING MARK” IS FLUSH WITH CONNECTOR
BODY AT THE WIRE INSERTION PORTS
MAIN FASTENER HEX SIZE
VSC6: 5/16” SAE HEX
VSC3/0: 3/8” SAE HEX
KEEP RUN WIRE CENTERED WITH THE CIRCULAR RECESS OF OPENING
FIGURE 8: INSERT AND CENTER THE
RUN WIRE, IN THE CENTER OF THE CIRCULAR RECESS. TIGHTEN HEX BOLT UNTIL THE SPECIFIED TORQUE IS ACHIEVED AND MAINTAINED FOR 5 SECONDS
FIGURE 7: FULLY-INSERT SENSOR LEADS AND SECURE BY TIGHTENING TERMINAL SCREWS TO SPECIFIED TORQUE
WIRE
CONNECTOR
587H