Panduit SN5RC Installation Manual

Page 1
NET-A
© Panduit Corp. 2013, 2014
CCESS
INSTRUCTIONS CM667A
N-Type and S-Type Cabinets
)
Equipment Rail Installation
Install [4] Equipment Rail Mounting Brackets to Equipment Rails with [3] Counter-sunk Torx screws per bracket (use T25 Torx bit)
Ensure that counter-sinks of brackets are oriented to match heads of counter-sunk screws
Equipment Rail Mounting Bracket
Ensure that counter-sinks of bracket match screw
FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
Page 1 of 2
[3] Counter-sunk Torx Screws (use T25 Torx bit)
Page 2
INSTRUCTIONS CM667A
Equipment Rail Installation
Locate desired Equipment Rail position
Insert [2] Equipment Rail Mount Nuts through slots of Front-to-Back Beam (top and bottom locations)
Fasten [2] M10 Hex Screws to E-Rail Mount Nuts at top and bottom of Equipment Rail
Tighten M10 Hex Head Screw to 30.0 +/- 5.0 N-m [22.1 +/- 3.7 Ft-lbs]
M10 Hex Head Screw (use 15mm socket wrench)
Equipment Rail Mount Nut (Finger Grip Area)
Barbed Surface (face to outside of cabinet)
INSTALL EQUIPMENT RAILS
Equipment Rail Mount Nut
Slot of Front-to-Back Beam
M10 Hex Head Screw (use 15mm socket wrench)
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
Page 2 of 2
M10 Hex Head Screw (use 15mm socket wrench)
E-mail:
techsupport@panduit.com
Phone:
866-405-6654