NOTE - Some views in this document may vary
slightly from your actual cabinet configuration.
FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
Page 2 of 22
Page 3
INSTRUCTIONS V00029AC Rev. 02
…
…
…
…
…
…
…
…
…
…
Table of Contents - Net-Access S-Type Network Cabinets
General Cabinet OperationPage
Packaging Material Removal……………………………………………...…………… 4
Leveling…………………………..……………………………………………………
Floor Mounting…………………………………………………………………………
Ganging………………………………………………………………………………… 7-8
Grounding………………………………………………………………………………
Equipment Rail Adjustment……………………………………………………………
Overhead Cable Openings……………………………………………………………… 11
Cable Management Fingers Installation (SN15F, SN25F)……………………………
Single Hinge Door (Removal and Installation) ………………………………………
Rear Split Doors (Removal and Installation) …………………………………………
Side Panels (Distinguishing Features) …………………………………………………
Side Panels (Removal/Installation and Adjustment - optional) ………………………
Vertical Blanking Panels (Floor Sealing) ………………………………………………
Rear Floor Seal Installation (Vertical Exhaust Duct ONLY) …………………………
Top of Cabinet Cable Manager Installation …………………………………………… 20
Top of Cabinet Cable Manager Installation (for Vertical Exhaust Ducts) ……………
5
6
9
10
12
13-14
15
16
17
18
19
21
Note: The maximum static weight load of the cabinet is 3000 lbs. [1361 kg]. The maximum
weight load when the cabinet is rolling on casters is 2500 lbs. [1134 kg]. The weight load should
be evenly distributed across the height of the cabinet, with the heaviest components mounted at
the bottom of the cabinet.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 22
Page 4
INSTRUCTIONS V00029AC Rev. 02
Packaging Material Removal
Before removal of packaging material:
Check tip indicator on the outside of cabinet to ensure cabinet was shipped in the upright position. If tip indicator shows improper handling,
inspect cabinet for damage before accepting cabinet.
Before handling cabinet:
Small glide strips are installed at various locations around the cabinet to protect the cabinet’s finish during shipping. These strips are to be
removed prior to handling of cabinet.
“Shipping Hold Down Bracket” Doubles as Floor Mounting Bracket. Retain bracket if floor mounting is desired. (see Page 6)
•Remove all stretchwrap and protective cardboard from outside of cabinet
•Remove all Shipping Brackets (if necessary)
•Remove [2] Hold Down Brackets at front and rear of cabinet
•Use
IMPORTANT:
Leveling Legs must be fully retracted before the cabinet is moved into place. Sliding cabinet on leveling legs may
result in damage to the leveling legs. (Leveling Legs ship in retracted position)
[2] people to carefully lift and remove cabinet from pallet
[2] M14 Hex Nuts
(use 22mm socket wrench)
[2] Shipping
Hold Down
Brackets
Front Door
Shipping Bracket
[8] M10 Hex Head Screws
(use 15mm socket wrench)
[4] Lag Screws and Washers
(use 13mm socket wrench)
Pallet
Note: Doors, Side panels, and other components are removed for clarity.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 22
Page 5
INSTRUCTIONS V00029AC Rev. 02
Leveling
•Ensure that [4] Leveling Legs are fully retracted
•Slide Cabinet into final position
•Lower the [4] Leveling Legs until the cabinet weight is fully supported
•Adjust the [4] Leveling Legs so that the cabinet is level front-to-back and side-to-side
Front-to-Back Cabinet Leveling
[4] Leveling Legs
(use 6mm Allen Key)
Side-to-Side Cabinet Leveling
Note: When ganging multiple cabinets together, ensure that adjacent cabinets are adjusted to the same height.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 5 of 22
Page 6
INSTRUCTIONS V00029AC Rev. 02
Floor Mounting
•Ensure that [4] Leveling Legs are fully retracted
•If Necessary, secure [2] “Shipping Hold Down Brackets” at front and rear of cabinet
•See Floor Mounting View below for floor mounting dimensions
•Attach the anchors to the floor with appropriate hardware for your type of floor
[2] Shipping
Hold Down
Brackets
[4] M10 Hex Head Screws
(use 15mm socket wrench)
Floor Mounting View
4X 14mm DIA
[0.55”]
173mm
[6.79”]
DIM A
DIM A:
-1070mm deep cabinets: 699mm [27.52”]
-1200mm deep cabinets: 581mm [33.51”]
DIM B:
-600mm wide cabinets: 191mm [7.52”]
-700mm wide cabinets: 241mm [9.48”]
-800mm wide cabinets: 291mm [11.46”]
DIM B
2X 216mm
[8.50”]
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 6 of 22
Page 7
INSTRUCTIONS V00029AC Rev. 02
Ganging (front of cabinet)
•Ensure cabinets are level
•Secure Ganging Brackets to cabinets at [2] front locations shown below
•Do not use Ganging Brackets to cinch cabinets together
IMPORTANT:
Ensure cabinets are level by following the guidelines on page 5. Leveling the cabinet prior to
ganging is important to ensure proper door operation.
[2] Front Ganging
Brackets
[4] M6 Torx Screws
(use T25 Torx bit)
FRONT OF CABINETS
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 7 of 22
Page 8
INSTRUCTIONS V00029AC Rev. 02
Ganging (rear of cabinet)
•Ensure cabinets are level
•Secure Ganging Brackets to cabinets at [2] rear locations shown below
•Do not use Ganging Brackets to cinch cabinets together
IMPORTANT:
Ensure cabinets are level by following the guidelines on page 5. Leveling the cabinet prior to
ganging is important to ensure proper door operation.
[2] Rear Ganging
Brackets
[4] M6 Torx Screws
(use T25 Torx bit)
REAR OF CABINETS
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 8 of 22
Page 9
INSTRUCTIONS V00029AC Rev. 02
Grounding
•Attach Grounding Lug or Grounding Bar at any of the [6] location(s) shown below
•Grounding location is indicated by universal ground symbol
•Use M5 bonding screw
[8] Grounding Lug Locations
(Front and Rear of Beams)
Note: top cap removed for clarity.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 9 of 22
Page 10
INSTRUCTIONS V00029AC Rev. 02
Equipment Rail Adjustment
•Loosen M10 Hex Head Screw at top and bottom of equipment rail
•Adjust equipment rail to desired position
•Tighten M10 Hex Head Screw to 30.0 +/- 5.0 N-m [22.1 +/- 3.7 Ft-lbs]
Uninstall/Re-install and Move Equipment Rails (Top and Bottom Locations)
•Remove [2] M10 Hex Screws at top and bottom of Equipment Rail
•Remove [2] Equipment Rail Mount Nuts through slots of Front-to-Back Beam
•REVERSE STEPS to re-install Equipment Rails (insert Equipment Rail Mount Nuts through slots of Front-to-Back beam while holding
finger grip of mount nut; ensure that barbed surface of Equipment Rail Mount Nut faces outside of cabinet)
M10 Hex Head Screw
(use 15mm socket wrench)
Equipment Rail
Mount Nut
(Finger Grip Area)
Barbed Surface
(face to outside
of cabinet)
UNINSTALL/RE-INSTALL AND MOVE EQUIPMENT RAILS
Equipment Rail
Mount Nut
Slot of Front-to-Back Beam
M10 Hex Head Screw
(use 15mm socket wrench)
M10 Hex Head Screw
(use 15mm socket wrench)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 10 of 22
Page 11
INSTRUCTIONS V00029AC Rev. 02
Overhead Cable Openings
•Remove Bezel Insert to allow for overhead cable entry
•Cut [8] tabs with wire cutter to open large cable openings - OPTIONAL
•Install M10 threaded rod into [6] tapped holes, if desired
•[2] 152.4mm x 152.4mm [6” x 6”] openings can be used to route power overhead
•PANDUIT
C
OOL BOOT
Overhead Cable
Opening Bezel
TM
products can be used to seal around cables/fiber to prevent hot air recirculation
Removable Insert
Bezel
[6] M10 Threaded Holes
[2] 152.4mm x 152.4mm Openings
[6” x 6”]
OPTIONAL
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 11 of 22
Page 12
INSTRUCTIONS V00029AC Rev. 02
Cable Management Fingers (SN15F, SN25F)
•Insert tabs of Cable Management Finger into mounting slots of equipment rails
•Slide Cable Management Finger inward to lock into place
Cable Managment Finger
-Insert tabs into cabinet post
-Slide inward to lock in place
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 12 of 22
Page 13
INSTRUCTIONS V00029AC Rev. 02
Single Hinge Door (Removal and Installation)
•VIEW 1 Pull down Compression Sleeve at top door hinge
•VIEW 1 Pull Single Hinge Door away from cabinet so that Top Hinge Screw fits through cutout of door
•VIEW 2 Lift bottom of door off Bottom Hinge Pin
•REVERSE STEPS to install Single Hinge Door
Top Hinge Screw
Compression Sleeve (Pull down)
VIEW 1
VIEW 2
VIEW 3
Bottom Hinge Pin
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 13 of 22
Page 14
INSTRUCTIONS V00029AC Rev. 02
Single Hinge Door (Door Handle Direction Reversal)
•VIEW 1, 2 Remove Top and Bottom Hinge Brackets from current location (remove top hinge screw, if necessary)
•VIEW 1, 2 Install Top and Bottom Hinge Brackets on opposite side of cabinet (re-install top hinge screw, if necessary)
•VIEW 3 Move Door catch to opposite side of cabinet frame
Door Handle Reversal (Lay door on a flat surface) - VIEW 4, 5
•Remove Door Handle Backing Plate and rotate position of Door Handle 180º
•Loosen Cam Screw to reposition Door Cam and Cam Stop to outside of door. Tighten Cam Screw
•With Door Handle repositioned, secure Door Handle Backing Plate to Door Handle
•Remove PANDUIT label and re-attach in correct orientation near top of door
•Reinstall Single Hinge Door per instructions on Page 12
VIEW 3
VIEW 1
VIEW 2
[2] M4 Screws
(use 2.5mm Allen Key)
[2] Hex Nuts
(use 8mm socket wrench)
Top Hinge Bracket
M6 Torx Screw
(use T30 Torx bit)
Bottom Hinge Bracket
Door Cam
(reposition to
outside edge
of door)
Door Handle
(rotate 180º)
Door
Handle
Backing
Plate
Door Catch
VIEW 5
PANDUIT Label
VIEW 4
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 14 of 22
Page 15
INSTRUCTIONS V00029AC Rev. 02
Rear Split Doors (Removal and Installation)
•Open Rear Split Doors to approximately 90º
•Lift Rear Split Doors up pull doors away from cabinet frame
•REVERSE STEPS to install Rear Split Doors
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 15 of 22
Page 16
INSTRUCTIONS V00029AC Rev. 02
Side Panel - (Distinguishing Features -- also reference instructions V00029CM)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 16 of 22
CURRENT VERSION
Backstop feature
on bottom beam
CURRENT VERSION
[2] Adjustable
bushings
Page 17
INSTRUCTIONS V00029AC Rev. 02
Side Panels (Removal/Installation and Adjustment - optional)
•Pull [2] Spring Loaded Hinge Pins to release Rear Side Panel from cabinet frame
•Pull [4] Spring Loaded Hinge Pins to release Front Side Panel from cabinet frame
•REVERSE STEPS to install In-Row Side Panels
IMPORTANT: Install Front Side Panel First
Spring Loaded Hinge Pins
[2] Locations
Spring Loaded Hinge Pin
(Top and Bottom)
Spring Loaded Hinge Pins
[2] Locations
Move Finger Pull into
Slot to Lock Hinge Pin
in
OPEN position
Front Side Panel
Adjust Fit of Side Panels
Use included wrench to raise
or lower adjustment bushings
Rear Side Panel
Side panels removed
from view to add clarity
Adjustment
Bushing
Adjustment
Wrench
(included)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 17 of 22
Page 18
INSTRUCTIONS V00029AC Rev. 02
Vertical Blanking Panels (Floor Sealing)
•Install [2] Flap Seal sections onto edges of Bottom Horizontal Blanking Panel
•Insert [3] M5 Torx Screws into Bottom Horizontal Blanking Panel
•Install Horizontal Blanking Panel so that front face aligns with equipment rails
•Install [2] Bottom Seal Brackets (Left Bracket is noted by diamond cutout)
•Attach D-shaped Rubber Seal to Horizontal Blanking Panels (top and bottom)
•Attach 25mm x 50mm Foam Seals to bottoms of Horizontal Blanking Panel and [2] Bottom Seal Brackets
Flap Seal
Bottom Horizontal
Blanking Panel
[3] M5 Torx Screws
(use T25 Torx bit)
D-Shaped Rubber Seal
[2] M5 Torx Screws
(use T25 Torx bit)
Horizontal Blanking Panel
(align with equipment rails)
Flap Seal
LEFT Bottom
Seal Bracket
[2] M5 Torx Screws
(use T25 Torx bit)
25mm x 50mm Foam Seals
RIGHT Bottom
Seal Bracket
(note diamond
cutout)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 18 of 22
Page 19
INSTRUCTIONS V00029AC Rev. 02
Rear Floor Seal Installation (Vertical Exhaust Duct ONLY)
•Install Floor Seal to rear of cabinet frame using (2) M10x20mm Bolts. (Flange on floor seal will face outward away from the cabinet.)
[2] M10x20mm Bolts
(use 15mm socket wrench)
Floor Seal
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 19 of 22
Page 20
INSTRUCTIONS V00029AC Rev. 02
Top of Cabinet Cable Manager Installation
•Disassemble front fascia assemblies (packaged in cabinet) by removing (2) M5x0.8 button head screws (use T25 Torx bit).
•Remove (2) M5x0.8 button head screws (use T25 Torx bit) from front and rear of Cable Manager base.
•Install vertical walls on front and back of Cable Manager base using (5) M5x0.8 button head Torx screws (use T25 Torx bit). Reinstall screws from previous step to secure to the frame.
•Attach front fascia to the front vertical wall by sliding fascia over studs in vertical wall.(see detail view). Tighten with (4) M5x0.8 button head screws (use T25 Torx bit).
•Attach rear fascia to the rear vertical wall by sliding fascia over studs in vertical wall (see detail view). Tighten with (4) M5x0.8 button head screws (use T25 Torx bit).
- Remove [4] M5 Torx Screws
(use T25 Torx bit)
[2] Vertical Walls
[2] Vertical Walls
Front Fascia
Rear Fascia
[4] M5 Torx Screws
(use T25 Torx bit)
[5] M5 Torx Screws
(use T25 Torx bit)
Studs
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 20 of 22
Page 21
INSTRUCTIONS V00029AC Rev. 02
Top of Cabinet Cable Manager Installation (for vertical exhaust ducts)
IMPORTANT - INSTALL VERTICAL EXHAUST DUCT PRIOR TO INSTALLING REAR VERTICAL WALL
•Disassemble front fascia assemblies (packaged in cabinet) by removing (2) M5x0.8 button head screws (use T25 Torx bit).
•Remove (2) M5x0.8 button head screws (use T25 Torx bit) from front of Cable Manager base.
•Install vertical wall on front of Cable Manager base using (5) M5x0.8 button head Torx screws (use T25 Torx bit). Re-install screws
from previous step to secure to the frame.
•Attach front fascia to the front vertical wall by sliding fascia over studs in vertical wall.(see detail view). Tighten with (4) M5x0.8 button head screws
•Attach rear vertical wall to the Cable Manger with (4) M5x0.8 button head screws (use T25 Torx bit) from underneath Top of Cabinet Cable Manager.
Front Vertical Wall
- Remove [2] M5 Torx Screws
(use T25 Torx bit)
Rear Vertical Wall
[5] M5 Torx Screws
(use T25 Torx bit)
Front Vertical Wall
[4] M5 Torx Screws
(use T25 Torx bit)
Studs
IMPORTANT
VERTICAL EXHAUST
DUCT MUST BE
INSTALLED PRIOR TO
INSTALLATION OF
REAR VERTICAL WALL
[4] M5 Torx Screws
(use T25 Torx bit)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 21 of 22
Page 22
INSTRUCTIONS V00029AC Rev. 02
This page is left intentionally blank
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
Page 22 of 22
E-mail:
techsupport@panduit.com
Phone:
866-405-6654