Base to Base
35 RU Min. Spacing
39 RU Max. Spacing
POU Bracket for 2 Post Racks
Part Number(s): R2PPDUB
© Panduit Corp. 2011
R2PPDUB
Installation Instructions-Outer Mounting Brackets
Attach (2) #12-24 X 1/2" screws to rack (per bracket) at appropriate locations.
Fasten outer mounting brackets to rack using the screws. The large flat surface with slotted holes may face outside or inside.
For mounting long (66.25") POU’s, the brackets may be spaced vertically between 35 and 39 RUs apart, in 1 RU increments, measured from
bracket base to bracket base.
For mounting short (39") POU’s, the brackets may be spaced vertically between 19 and 23 RUs apart, in 1 RU increments, measured from
bracket base to bracket base.
INSTALLATION INSTRUCTIONS
The R2PPDUB part contains the following components referred to in this
instruction sheet:
• (2) Outer Mounting Brackets
• (2) Inner Mounting Brackets
• (12) #12-24 X 1/2" Screws
#12-24 X 1/2" Screws
(first)
CM521
Base to Base
Outer Mounting
Brackets (slide in
19 RU Min. Spacing
23 RU Max. Spacing
under screws)
Bracket Installation for Long POU’s
#12-24 X 1/2" Screws
(first)
Bracket Installation for Short POU’s
Installation Instructions-Inner Mounting Brackets
Slide inner mounting brackets into outer mounting brackets with the POU mounting keyway surface facing opposite the outer bracket slotted
hole surface. Fasten brackets together using (4) #12-24 X 1/2" screws for each bracket set. (2) screws will be fastened on the top flange and
(2) screws will be fastened on the bottom flange.
Important: (2) screws must be fastened in the most outward hole on each outer mounting bracket (1 top, 1 bottom). (2) screws must be fastened in the position where the hole in the inner mounting bracket is closest to the face of the rack, regardless of extended position.
Note: Multiple holes on the top and bottom of the brackets allow the distance from the rack a POU can be mounted to be adjustable. This
means that the side facing POU can be mounted ranging from 3.7"-18.7" horizontally from the face of the rack. The rear facing POU can be
mounted ranging from 12.3"-20.3" horizontally from the face of the rack.
See illustrations on Page 2
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 2

© Panduit Corp. 2011
18.7” Maximum
POU Side
Mounting Distance
INSTALLATION INSTRUCTIONS
Installation Instructions-Inner Mounting Brackets (continued)
#12-24 X 1/2" Screws
Mounting Brackets Fully Retracted
Inner Mounting Brackets
CM521
#12-24 X 1/2" Screws
3.7” Minimum
POU Side Mounting
Distance
#12-24 X 1/2" Screws
Note: No other rack equipment can be mounted in the same RU
spaces that the POU Mounting Brackets occupy.
Mounting Brackets Fully Extended
Installation Instructions-Installing Power Outlet Units (POU)
Install POU to the R2PPDUB by lining up the mounting buttons provided with the POU with the centers of 1 mounting keyhole on each of the
bracket assemblies.
Note: POU’s may be rear facing or side facing on the R2PPDUB assembly, but in no case should there be more than two (2) POU’s mounted
at the same time. The maximum load for POU’s and cabling is 50 lbs.
POU Rear Facing on the R2PPDUB assembly
For Instructions in Local Languages
www.panduit.com/resources/install_maintain.asp
and Technical Support:
www.panduit.com
Page 2 of 2
POU Side Facing on the R2PPDUB assembly
E-mail:
cs@panduit.com
Fax:
(708) 444-6448