Cable Management Numbers-Up Style Racks
Part Numbers:R2P48, R2P, R2PS, R2PW,R2P96
INSTRUCTIONS CM458
Mounting Configuration
3/8” Nut 3-8X1” Bolt
3/8” Paint Piercing Washer
RACK ASSEMBLY
Apply Antioxidant Paste to painted surfaces that the 3/8 paint piercing washers will come in contact with. Install top angles to upright channels using (2) 3/8x1” bolts (2) 3/8” nuts and (4) 3/8” paint piercing washer (see figure below) per angle. Finger tighten only.
Apply Antioxidant Paste to painted surfaces that the 3/8 paint piercing washers will come in contact with.Install the base angles to the vertical upright channels using (4) 3/8x1” bolts (4) 3/8” nuts and (8) 3-16 paint piercing washers (see figure below) per angle. Finger tighten only.
Stand rack upright. Square the upright channels with the base using a carpenter square. Completely tighten
all bolts to at least 14 ft.-lbs(19.0 N-m).
Top Angle
Antioxidant Paste
3/8X1” Bolt
MOUNT RACK TO FLOOR
Securely mount the rack to the floor using the appropriate hardware based on the floor construction (concrete, raised floor, or wood). Note: Mounting using the holes closest to the rack will minimize deflection.
For Instructions in Local Languages
www.panduit.com/resources/install_maintain.asp
and Technical Support:
3/8 Paint Piercing Washer
15.0
3/8 Nut
6.0
16.0” = 19” RACK
20.0” = 23” RACK
20.3” = 19” RACK
24.3” = 23” RACK
Rack Channel
6.5
9.5
1.25” TYP
12.5
Note: The maximum weight load of the rack is 1,000 pounds with the exception of the R2P48, which is 300 lbs. The weight should be evenly distributed across the height of the rack, with the heaviest components mounted at the bottom of the rack. The top angles are not intended to support a significant load.