Panduit PZWMC1230W Installation Manual

Page 1
0.8"
B
Mounting
Holes
C
4.5"
Mounting Holes
A
Footprint with Cabinet Open
Cabinet Width
PANZONE Wall Mount Cabinet
Part Numbers: PZWMC
© Panduit Corp. 2019
INSTRUCTIONS CM315E
Parts Included: (1) - Extra Door Spacer (8) - Keys (1) - Roll of Tak-Ty (12) - #12-24 Screws (1) - Removable Top Vent Cover Panel
PZWMC12W
Cabinet with Windowed Door

Location Footprint

CABINET
DEPTH
25.0 45.1
30.0 50.1
RU DIM “B”DIM “C”
12 20.7” 23.8” 18 31.2” 34.3” 26 45.2” 48.3”
DIM “A”
FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
Page 1 of 11
Page 2
INSTRUCTIONS CM315E
PANZONE Wall Mount Cabinets can be installed in a hinged right or hinged left application. For your installation, determine which side of the cabinet will hinge. The cabinet is shown hinged left. Mounting surface must have sufficient strength to support the cabinet with payload. The mounting surface must also be flat and extend beyond the overall cabinet footprint.
To open cabinet, push latch release button to dis-engage latch.
2” or 2 1/2” Conduit Knockout
Front Door with Lock
Plastic
Step 2:
To reverse rear hinge direction.
Open cabinet, and remove the latch from the rear lock. Remove the rear lock and the lock hole grommet on the opposite side. Close the cabinet and remove decorative covers on hinges. Remove the thread forming screws & lockwashers from the hinges (M5), and latches (M4), and re-install the components on the opposite sides of the cabinet. Open the cabinet and re-install the lock and grommet on the opposite sides. Re-assemble the lock latch, ensuring it locks in the downward rotation (see below).
1/2” or 3/4” Conduit Knockout
Step 1:
Remove door and side panels for ease of handling. Ensure rear latches are closed. Install (4) 3/8” mounting hardware (not provided) as shown in Location Footprint. Hardware should protrude 3/8” from wall. Mount the cabinet to the wall by hooking the keyholes over the protruding 3/8” mounting hardware. Once the cabinet is in place, carefully swing cabinet from wall and tighten the hardware securely. Re-install door and side panels. Door swing direction can be changed by rotating the door 180°. Ensure the plastic spacer is placed at
the bottom of the door hinge.
M5 Thread forming screws & lock­washers
Hinge
Lock Hole Grommet
Lock
Lock in downward
rotation
M4 Thread forming
screwsLatch
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 11
Page 3
INSTRUCTIONS CM315E
PZWMC18RR Rear Rails
1
2
3
4
5
1 For PZMWCGK Cabinet Jumper Grounding Kit Only
2 Recommended for direct 1:1 switch patching only
3 Recommended for direct 1:1 switch patching only
4 Default Rail Location: Recommended for traditional patching with
small gauge patch cord, Use PZBR3 or PZBR3.5 Bend Radius Posts
5 Recommended for traditional patching with standard patch cords. Use
PZBR4 Bend Radius Posts.
Step 3: To adjust the depth of the mounting rail for specific applications, remove the M6 thread forming screws and lockwashers, move the rail to the desired position and re-install mounting hardware.
Mounting Rail Installation (PZWMC12RR)
To install mounting rail use (2) M6 thread forming screws & lockwashers at desired location as shown below
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 11
Mounting Rail
Mounting Hardware
Page 4
INSTRUCTIONS CM315E
Cable Routing
Cable must be routed with an adequate slack loop to prevent cable damage. Route cable to point 1 secure to tie down with a TAK-TY. Next route cable across the bottom of the enclosure to point 2 secure to tie down with a TAK-TY. Route to the desired patch panel after securing the cables with a T
AK-TY at point 3 or 4.
Point 4
Cables Extend to Patch Panel
Point 2
Point 3
Point 1
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 11
Page 5
INSTRUCTIONS CM315E

Optional Accessories

PZWMC12W (Shown)
Cabinet with Window Door
PZWMC-CL
Combination
Lock Kit
PZCHSM2
ANZONE Horizontal
P
Slack Manager
PZWMC12RR PZWMC18RR PZWMC26RR
ANZONE Rear Equipment
PZBR4
ANZONE 4” Bend
P
P
Rail Kits
Radius Post Kit
PZBR3
PANZONE 3” Bend
Radius Post Kit
PZWMCFKHF
PANZONE
Fan Kit
High Flow
PZBR3.5
PANZONE 3.5” Bend
Radius Post Kit
For Technical Support: www.panduit.com/resources/install_maintain.asp
PZCFK
P
ANZONE Fan Kit
PZCFR
ANZONE Fan Media
P
Replacement Kit
Page 5 of 11
Page 6
INSTRUCTIONS CM315E

PANZONE Fan Kits (PZCFK, PZCFK-E, PZWMCFKHF, PZWMCFKHF-E)

Fan kits are installed using (4) #10-32 screws and lockwashers provided with kit as shown below. If only one fan kit is used, install the provided blank on the opposite wall using (4) #10-32 screws and lockwashers provided. For European Schuko (240V) plugs, use fan kits with ‘-E’ part numbers
Scenario 1: Switches not exceeding 120 watts of total heat output use fan kit as shown.
Scenario 2: POE (Power over Ethernet) or switches totaling over 120 watts of total heat, use two PZCFK fan kits or one PZWMCFKHF. Mount second fan
where blank is shown.
Optional: Remove Top Panel Blank for additional venting. A fan kit can be installed on top vent, but will occupy the top RU space. NOTE: Fan kits draw air into the cabinet.
M5 Thread forming screws
Top Panel Blank
Fan Kit Blank
Note: When using switches with side air intake and opposite side exhaust use one fan without fan blank
Fan Kit
#10-32 Screws and Lockwashers (8 Places)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 6 of 11
Page 7
INSTRUCTIONS CM315E
PANZONE Horizontal Slack Manager
Install tray using (4) #12-24 x 1/2 screws provided at desired RU as shown in figure 3. Refer to recommended layout section for optimal mounting location(s).
Screw Mounting Locations
Bend Radius Post Installation
Bend radius posts can be installed at any rack location using (1) #12-24 x 2.5" [(1) #12-24 x 1.5” for PZBR3] screw provided as shown in Figure 1. Post can be customized by removing tabs as show in Figure 2. Note: Post may be installed over active equipment mounting locations.
Figure 3
Figure 1
Figure 2
Bend Radius Post
Score Line
#12-24 x 2.5" Screw
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 7 of 11
Page 8
Cam Lock Spacer Rings
Combination locks including Cylinder Nut, Retaining Screw, Lock Washer, Flat Washer and Direction Setting Washer
Figure 1
Cam Lock Spacer Rings
Combination locks including Cylinder Nut, Retaining Screw, Lock Washer, Flat Washer and Direction Setting Washer
Figure 1
.640 .650
.755 .765
DIA.
Figure 2
Cam from lock
Figure 3
Cylinder Nut
Spacer Ring
Combination Lock Head
PZWMC* Cabinet Surface
Lock Cylinder
Cylinder Nut Installed on Back of Cabinet
Figure 4
Figure 5
Spacer RIng
Lock Head
Figure 6

PANZONE Lock Kits (PZWMC-CL)

Kit Contents
Combination locks (2)
Spacer rings (2)
Cylinder nuts (2)
Retaining screw (2)
Lock washers (2)
Flat washers (2)
Direction setting washers (2)
INSTRUCTIONS CM315E
Mounting Cutout
Installation
Remove the existing locks from the cabinet and save cams for later use. (Figure 2)
Remove the Cylinder Nut from the Combination Lock and insert the Spacer Ring over the Lock Cylinder. (Figure 3)
Install the Combination Lock onto the Cabinet and tighten the Cylinder Nut. The Lock Head should be spaced away from the Cabinet Surface. (Figures 3 &
4)
Remove the Retaining Screw, Lock Washer, Flat Washer, and Direction Setting Washer.
Pull the Lock Head from the cylinder and rotate until oriented in the desired direction. (Figures 5-7)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Cam will rotate right
Page 8 of 11
Cam will rotate left
Direction Setting Washer
Figure 7
Page 9
INSTRUCTIONS CM315E
Figure 11
Figure 10
Spacer Ring
Lock Head
Reset Button
Push reset button with pin
Scroll numbers to desired combination
Figure 9
Installation (continued)
Install the remaining parts in the following order: Direction Setting Washer, Cam (saved from previ­ous lock), Flat Washer, Lock Washer, and Retain­ing Screw. (Figure 7)
Set the lock to the factory combination 0-0-0.
Test lock rotation direction. Adjust cam angle if
necessary
To Change Combination:
Set the lock to the previous combination or factory combination (0-0-0).
Push reset button with pin. (Figure 9)
While reset button is pushed, scroll numbers to the desired combination. (Figure 9)
Release the reset button to set the combination.
Cam (saved) from pre­vious lock)
Lock Washer
Retaining Screw
Flat Washer
Direction Setting Washer
Figure 8
To Hide the Reset Button:
Set the lock to the desired combination.
Remove the direction setting washer, cam. flat washer. lock washer, and retaining screw. (Figure
12)
Pull out the lock head and rotate 180º. (Figures 10-11)
Reinstall the direction setting washer, cam, flat washer, lock washer, and retaining screw. (Figure
12)
Cam (saved) from pre­vious lock)
Lock Washer
Retaining Screw
Flat Washer
Direction Setting Washer
Figure 12
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 9 of 11
Page 10
INSTRUCTIONS CM315E
Recommended Layout (18 RU)
Recommended Layout (26 RU)
2 RU of Blanking Panel
2 RU of 24 Port Patch Panels
PZCHSM2
1 RU of Active Equipment
2 RU of 24 Port Patch Panels
2 RU of 24 Port Patch Panels
PZCHSM2
PZCHSM2
2 RU of Active Equipment
2 RU of Active Equipment
2 RU of Active Equipment
PZCHSM2
PZCHSM2
PZCHSM2
2 RU of 24 Port Patch Panels
2 RU of 24 Port Patch Panels
2 RU of 24 Port Patch Panels
2 RU of 24 Port Patch Panels
2 RU of Blanking Panel
2 RU of Blanking Panel
PZCHSM2
Recommended Layout (12 RU)
24 Port Patch Panel
24 Port Patch Panel
PZCHSM2
24 Port Patch Panel
24 Port Patch Panel
PZCHSM2
Active Equipment
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 10 of 11
Page 11
INSTRUCTIONS CM315E
c
L
c
L
Recommended Cable Routing Guide
Place patch cord slack around furthest spool as feasible to provide best possible cable management
Never cross over center line of horizontal slack manager with cable slack
Top View of PZCHSM2
Typical patch cord length is 4 feet minimum Route patch cords as shown to avoid crossover
Recommended Mounting Locations for Bend Radius Posts
Typical patch cord length is 5 feet minimum Route patch cords as shown to avoid crossover
Routed to top Horizontal Slack Manager
For instuctions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
Lower Horizontal Manager
www.panduit.com
Page 11 of 11
Recommended Mounting Locations for Bend Radius Posts
Route patch cords going to top horizontal slack towards the outside of the cabinet to avoid cross overs with patch cords going to lower slack manager.
E-mail:
techsupport@panduit.com
Phone:
866-405-6654
Loading...