Parts Included:
(1) - Extra Door Spacer
(8) - Keys
(1) - Roll of Tak-Ty
(12) - #12-24 Screws
(1) - Removable Top Vent Cover Panel
PZWMC12W
Cabinet with Windowed Door
Location Footprint
CABINET
DEPTH
25.045.1
30.050.1
RUDIM “B”DIM “C”
1220.7”23.8”
1831.2”34.3”
2645.2”48.3”
DIM “A”
FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
Page 1 of 11
Page 2
INSTRUCTIONS CM315E
PANZONE Wall Mount Cabinets can be installed in a hinged right or hinged left
application. For your installation, determine which side of the cabinet will hinge.
The cabinet is shown hinged left. Mounting surface must have sufficient strength to support the cabinet with payload. The mounting surface must also
be flat and extend beyond the overall cabinet footprint.
To open cabinet,
push latch release
button to dis-engage
latch.
2” or 2 1/2” Conduit Knockout
Front Door
with Lock
Plastic
Step 2:
To reverse rear hinge direction.
Open cabinet, and remove the latch from the rear lock. Remove the rear lock and the
lock hole grommet on the opposite side. Close the cabinet and remove decorative covers
on hinges. Remove the thread forming screws & lockwashers from the hinges (M5), and
latches (M4), and re-install the components on the opposite sides of the cabinet. Open
the cabinet and re-install the lock and grommet on the opposite sides. Re-assemble the
lock latch, ensuring it locks in the downward rotation (see below).
1/2” or 3/4” Conduit Knockout
Step 1:
Remove door and side panels for ease of handling. Ensure rear latches are
closed. Install (4) 3/8” mounting hardware (not provided) as shown in Location
Footprint. Hardware should protrude 3/8” from wall. Mount the cabinet to the
wall by hooking the keyholes over the protruding 3/8” mounting hardware.
Once the cabinet is in place, carefully swing cabinet from wall and tighten the
hardware securely. Re-install door and side panels. Door swing direction can
be changed by rotating the door 180°. Ensure the plastic spacer is placed at
the bottom of the door hinge.
M5 Thread forming
screws & lockwashers
Hinge
Lock Hole
Grommet
Lock
Lock in downward
rotation
M4 Thread forming
screwsLatch
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 11
Page 3
INSTRUCTIONS CM315E
PZWMC18RR
Rear Rails
1
2
3
4
5
1For PZMWCGK Cabinet Jumper Grounding Kit Only
2Recommended for direct 1:1 switch patching only
3Recommended for direct 1:1 switch patching only
4Default Rail Location: Recommended for traditional patching with
small gauge patch cord, Use PZBR3 or PZBR3.5 Bend Radius Posts
5Recommended for traditional patching with standard patch cords. Use
PZBR4 Bend Radius Posts.
Step 3: To adjust the depth of the mounting rail for specific applications, remove the M6 thread forming screws and lockwashers, move the rail
to the desired position and re-install mounting hardware.
Mounting Rail Installation (PZWMC12RR)
To install mounting rail use (2) M6 thread forming
screws & lockwashers at desired location as shown
below
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 11
Mounting Rail
Mounting Hardware
Page 4
INSTRUCTIONS CM315E
Cable Routing
Cable must be routed with an adequate slack loop to prevent cable damage. Route cable to point 1 secure to tie down with a TAK-TY. Next
route cable across the bottom of the enclosure to point 2 secure to tie down with a TAK-TY. Route to the desired patch panel after securing
the cables with a T
AK-TY at point 3 or 4.
Point 4
Cables Extend
to Patch Panel
Point 2
Point 3
Point 1
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 11
Page 5
INSTRUCTIONS CM315E
Optional Accessories
PZWMC12W (Shown)
Cabinet with Window Door
PZWMC-CL
Combination
Lock Kit
PZCHSM2
ANZONE Horizontal
P
Slack Manager
PZWMC12RR
PZWMC18RR
PZWMC26RR
ANZONE Rear Equipment
PZBR4
ANZONE 4” Bend
P
P
Rail Kits
Radius Post Kit
PZBR3
PANZONE 3” Bend
Radius Post Kit
PZWMCFKHF
PANZONE
Fan Kit
High Flow
PZBR3.5
PANZONE 3.5” Bend
Radius Post Kit
For Technical Support: www.panduit.com/resources/install_maintain.asp
PZCFK
P
ANZONE Fan Kit
PZCFR
ANZONE Fan Media
P
Replacement Kit
Page 5 of 11
Page 6
INSTRUCTIONS CM315E
PANZONE Fan Kits (PZCFK, PZCFK-E, PZWMCFKHF, PZWMCFKHF-E)
Fan kits are installed using (4) #10-32 screws and lockwashers provided with kit as shown below. If only one fan kit is used, install the provided blank on the
opposite wall using (4) #10-32 screws and lockwashers provided. For European Schuko (240V) plugs, use fan kits with ‘-E’ part numbers
Scenario 1: Switches not exceeding 120 watts of total heat output use fan kit as shown.
Scenario 2: POE (Power over Ethernet) or switches totaling over 120 watts of total heat, use two PZCFK fan kits or one PZWMCFKHF. Mount second fan
where blank is shown.
Optional: Remove Top Panel Blank for additional venting. A fan kit can be installed on top vent, but will occupy the top RU space. NOTE: Fan kits draw air into
the cabinet.
M5 Thread forming screws
Top Panel Blank
Fan Kit Blank
Note: When using switches with side air intake and opposite side exhaust use one fan without fan blank
Fan Kit
#10-32 Screws and
Lockwashers
(8 Places)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 6 of 11
Page 7
INSTRUCTIONS CM315E
PANZONE Horizontal Slack Manager
Install tray using (4) #12-24 x 1/2 screws provided at desired
RU as shown in figure 3. Refer to recommended layout
section for optimal mounting location(s).
Screw Mounting Locations
Bend Radius Post Installation
Bend radius posts can be installed at any rack location using (1) #12-24 x 2.5" [(1) #12-24 x 1.5” for PZBR3] screw provided as shown in
Figure 1. Post can be customized by removing tabs as show in Figure 2.
Note: Post may be installed over active equipment mounting locations.
Figure 3
Figure 1
Figure 2
Bend
Radius
Post
Score Line
#12-24 x 2.5" Screw
For Technical Support: www.panduit.com/resources/install_maintain.asp
Combination locks
including Cylinder Nut,
Retaining Screw, Lock
Washer, Flat Washer and
Direction Setting Washer
Figure 1
.640
.650
.755
.765
DIA.
Figure 2
Cam
from
lock
Figure 3
Cylinder Nut
Spacer Ring
Combination Lock Head
PZWMC* Cabinet
Surface
Lock
Cylinder
Cylinder Nut
Installed on
Back of Cabinet
Figure 4
Figure 5
Spacer RIng
Lock
Head
Figure 6
PANZONE Lock Kits (PZWMC-CL)
Kit Contents
•Combination locks (2)
•Spacer rings (2)
•Cylinder nuts (2)
•Retaining screw (2)
•Lock washers (2)
•Flat washers (2)
•Direction setting washers (2)
INSTRUCTIONS CM315E
Mounting Cutout
Installation
•Remove the existing locks from the cabinet and save
cams for later use. (Figure 2)
•Remove the Cylinder Nut from the Combination Lock
and insert the Spacer Ring over the Lock Cylinder.
(Figure 3)
•Install the Combination Lock onto the Cabinet and
tighten the Cylinder Nut. The Lock Head should be
spaced away from the Cabinet Surface. (Figures 3 &
4)
•Remove the Retaining Screw, Lock Washer, Flat
Washer, and Direction Setting Washer.
•Pull the Lock Head from the cylinder and rotate until
oriented in the desired direction. (Figures 5-7)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Cam will
rotate
right
Page 8 of 11
Cam will
rotate left
Direction Setting Washer
Figure 7
Page 9
INSTRUCTIONS CM315E
Figure 11
Figure 10
Spacer Ring
Lock
Head
Reset
Button
Push reset button with pin
Scroll numbers to
desired combination
Figure 9
Installation (continued)
•Install the remaining parts in the following order:
Direction Setting Washer, Cam (saved from previous lock), Flat Washer, Lock Washer, and Retaining Screw. (Figure 7)
•Set the lock to the factory combination 0-0-0.
•Test lock rotation direction. Adjust cam angle if
necessary
To Change Combination:
•Set the lock to the previous combination or factory
combination (0-0-0).
•Push reset button with pin. (Figure 9)
•While reset button is pushed, scroll numbers to
the desired combination. (Figure 9)
•Release the reset button to set the combination.
Cam
(saved)
from previous lock)
Lock
Washer
Retaining
Screw
Flat
Washer
Direction
Setting
Washer
Figure 8
To Hide the Reset Button:
•Set the lock to the desired combination.
•Remove the direction setting washer, cam. flat
washer. lock washer, and retaining screw. (Figure
12)
•Pull out the lock head and rotate 180º. (Figures
10-11)
•Reinstall the direction setting washer, cam, flat
washer, lock washer, and retaining screw. (Figure
12)
Cam
(saved)
from previous lock)
Lock
Washer
Retaining
Screw
Flat
Washer
Direction
Setting
Washer
Figure 12
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 9 of 11
Page 10
INSTRUCTIONS CM315E
Recommended Layout (18 RU)
Recommended Layout (26 RU)
2 RU of Blanking Panel
2 RU of 24 Port Patch Panels
PZCHSM2
1 RU of Active Equipment
2 RU of 24 Port Patch Panels
2 RU of 24 Port Patch Panels
PZCHSM2
PZCHSM2
2 RU of Active Equipment
2 RU of Active Equipment
2 RU of Active Equipment
PZCHSM2
PZCHSM2
PZCHSM2
2 RU of 24 Port Patch Panels
2 RU of 24 Port Patch Panels
2 RU of 24 Port Patch Panels
2 RU of 24 Port Patch Panels
2 RU of Blanking Panel
2 RU of Blanking Panel
PZCHSM2
Recommended Layout (12 RU)
24 Port Patch Panel
24 Port Patch Panel
PZCHSM2
24 Port Patch Panel
24 Port Patch Panel
PZCHSM2
Active Equipment
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 10 of 11
Page 11
INSTRUCTIONS CM315E
c
L
c
L
Recommended Cable Routing Guide
Place patch cord slack around furthest spool as feasible to
provide best possible cable management
Never cross over center line of horizontal slack manager
with cable slack
Top View of PZCHSM2
Typical patch cord length is 4 feet minimum
Route patch cords as shown to avoid crossover
Recommended Mounting Locations
for Bend Radius Posts
Typical patch cord length is 5 feet minimum
Route patch cords as shown to avoid crossover
Routed to top Horizontal
Slack Manager
For instuctions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
Lower
Horizontal
Manager
www.panduit.com
Page 11 of 11
Recommended Mounting Locations
for Bend Radius Posts
Route patch cords going to top horizontal
slack towards the outside of the cabinet to
avoid cross overs with patch cords going
to lower slack manager.
E-mail:
techsupport@panduit.com
Phone:
866-405-6654
Loading...
+ hidden pages