Part Numbers: PZRFE4U, PZRFE8U, PZRFE12U & PZRFC
INSTRUCTIONS CM469D
© Panduit Corp. 2014
The following items are included with PZRFE4/8/12
PANZONE Raised Floor Enclosures
Optional Components: PZRFC
(1) Set of Keys
(1) Magnetic Ruler
(4) Bonding Bolts
(1) Enclosure with
(4) Grommet Sleeves
(4) Support Brackets, with
Washers and Nuts
Required Tools
*10mm Socket
*7/16” Socket
(1) Lockable Enclosure Cover
Mounting Depth Table
PZRFE4U PZRFE8U
PZRFE12U
Distance from bottom of pedestal head plate to top of mounting brackets.
Part Number
Mounting Bracket Depth Below Floor 5” 8.5” 12”
With Optional Cover
Enclosure Load Rating
(+ .25” Tolerance)
PZRFE4U
18 lb 36 lb
PZRFE8U
7”
10.5” 14”
Installation:
1. Select the installation location ensuring there are no obstacles to interfere with the installation.
2. Mount the four support brackets under the enclosure by placing one on each pedestal mount bracket by attaching the U-bolt and nut
around the pedestal (See Figure 2.1). Refer to Figures 4.1 through 4.3 for adjustment to various pedestal sizes. Use the magnetic ruler to
measure the correct mounting location for each support bracket. Point them towards the center making a cross from the corners (See
Figure 2.2). Ensure that the plate is allowed to pivot from side-to-side. Note: If Grid Runner is placed above pedestal plate, then the
mounting assembly must be removed from plate and reconnected with the mounting assembly under the pedestal plate (See Figure 2.3).
3. Push CoolBoot Assemblies inside enclosure (See Figure 3.1) and then insert the enclosure in the desired floor tile.
PZRFE12U
54 lb
Figure 2.1
Figure 2.2
Figure 3.1
Figure 2.3
Mounting assembly connected
under pedestal mount plate.
FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
Page 1 of 5

INSTRUCTIONS CM469D
Installation of Pedestal Mount Assembly to Various Pedestal Sizes:
4. The PZRFE*U may be mounted to 7/8” square or up to 2” diameter round pedestals by adjusting the engagement of the U-Bolt.
7/8” square pedestal
Figure 4.1
1 1/2” diameter pedestal
2” diameter pedestal
Figure 4.2
Figure 4.3
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 5

INSTRUCTIONS CM469D
Installation continued:
5. Angle one side of the enclosure lower than the other to engage two pedestal mounting brackets. Then rock the enclosure clockwise and
counter clockwise while lowering the opposite side on the pedestal mounting brackets to manually align the four corners and mounting hole
locations (See Figure 5.1 & 5.2).
6. Once all four corners and mounting holes are aligned in the correct orientation (See Figure 6.1), fasten the enclosure to the pedestal mounting brackets using the supplied M6 X 12mm bonding bolts (See Figure 6.2).
Figure 5.1
Figure 6.1
Top View
Figure 5.2
Figure 6.2
M6 X 12mm Bonding Bolts
(4) Places
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 5

INSTRUCTIONS CM469D
Installation continued:
7. Each enclosure can accommodate both field terminated or pre-terminated connectivity. If using field terminated connectivity leave TIA/
EIA 19” mounting brackets as factory installed or remove center mounting bracket (See Figure 7.1 and 7.2). If using pre-terminated connectivity (example: cassettes, enclosures) remove TIA/EIA 19” mounting brackets and relocate to the center of the enclosure (See Figure 7.3).
Figure 7.1
Note: Install all cabling in accordance with NEC article 300.22 and Article 800.
Figure 7.2
Cool Boot Application
Parts List:
(A) - Fabric & (B) - Hook and loop cinch tie
B
Figure 7.3
a.)
A
b.)
Cinch material in center to separate wire bundles.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 5

INSTRUCTIONS CM469D
Optional: PanZone Raised Floor Enclosure Cover (PZRFC)
Enclosure’s Cover Installation:
Remove the two knockout tabs located at the top of the enclosure to allow access for the cover’s locking mechanism.
8
Attach Adhesive Foam Seal to the top of the enclosure as shown in Figure 8.
Foam Seal
Knockouts (2) Places
Once the knockouts have been successfully removed, drop the cover
9
The cover’s locking mechanism tabs should be aligned in the knockout geometry as shown in Figure 10.
10