Panduit PZCFK Installation Manual

Page 1
© Panduit Corp. 2015
PANZONE Wall Mount Cabinet Accessories
Part Number(s): PZCHSM2, PZCRR, PZBR4, PZBR3, PZBR3.5, PZCFK
INSTRUCTIONS V00030AF
PZBR4
P
ANZONE 4” Bend Radius Post Kit
P
ANZONE Horizontal Slack Manager
PZCRR
P
ANZONE Rear Equipment Rail Kit
P
ANZONE 3” Bend Radius Post Kit
P
ANZONE 3.5” Bend Radius Post Kit
PZBR3
PZCFK
PANZONE Fan Kit
PZBR3.5

PANZONE Fan Kit (PZCFK)

Fan kits are installed using (4)#10-32 screws and lockwashers provided with kit as shown below. If only one fan kit is used, install the provided blank on the opposite wall using (4) #10-32 screws and lockwashers provided.
Scenario 1: Switches not exceeding 120 watts of total heat output use fan kit as shown.
Scenario 2: POE (Power over Ethernet) or switches totaling over 120 watts of total heat, use two fan kits mount second fan where blank is shown.
Blank
Note: When using switches with side air intake and opposite side exhaust use one fan without fan blank
FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
Page 1 of 4
Fan Kit
#10-32 Screws and Lockwashers (8 Places)
Page 2
Mounting Rail Installation (PZCRR)
To install mounting rail use (4)#12-24 screws at desired location as shown below
INSTRUCTIONS V00030AF
Mounting Rail
Mounting Hardware
PANZONE Horizontal Slack Manager
Install tray using (4) #12-24 x 1/2 screws provided at desired RU as shown in figure 3. Refer to recommended layout section for optimal mounting location(s).
Screw Mounting Locations
Bend Radius Post Installation
Bend radius posts can be installed at any rack location using (1)#12-24 x 2.5" [(1) #12-24 x 1.5” for PZBR3]screw provided as shown in Figure 1. Post can be customized by removing tabs as show in Figure 2.
Note: Post may be installed over active equipment mounting locations
Figure 3
Figure 1
Bend Radius Post
Score Line
#12-24 x 2.5" Screw
Figure 2
FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
Page 2 of 4
Page 3
INSTRUCTIONS V00030AF

Recommended Layout

Recommended Cable Routing Guide

Place patch cord slack around furthest spool as feasible to provide best possible cable management
24 Port Patch Panel
24 Port Patch Panel
24 Port Patch Panel
24 Port Patch Panel
Active Equipment
Typical patch cord length is 4 feet Route patch cords as shown to avoid crossover
Top View of PZCHSM2
c
L
Never cross over center line of horizontal slack manager with cable slack
c
L
*Front door removed for clarity
FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
Recommended Mounting Locations for Bend Radius Posts
Page 3 of 4
Page 4
Typical patch cord length is 5 feet Route patch cords as shown to avoid crossover
INSTRUCTIONS V00030AF
Recommended Mounting Locations for Bend Radius Posts
Route patch cords going to top horizontal slack manager towards the outside of the cabinet to avoid cross overs with patch cords going to lower slack manager
*Front door removed for clarity
For instuctions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
Lower Horizontal Manager
www.panduit.com
Page 4 of 4
Routed to top horizontal slack manager