Panduit TX6A™ and TX6A-SD™ 10Gig™ UTP COPPER CABLING SYSTEM
INSTALLATION GUIDELINES
The TX6A™ and TX6A-SD™ 10Gig™ UTP Copper Cabling System is to be installed in
accordance to the cable management requirements set forth in ANSI/TIA/EIA-568-C
(Commercial Building Telecommunications Cabling Standard) and in ANSI/TIA/EIA-569-C
(Commercial Building Standard for Telecommunications Pathways and Spaces). To aid
compliant installation, guidelines for the TX6A™ and TX6A-SD™ 10Gig™ UTP Copper Cabling
System are provided below.
Pathways and Spacing Management
Pathways should be located to minimize occupant disruption and allow for easy
moves, adds, and changes.
For initial installation, the maximum fill capacity for pathways (i.e. conduit, raceways,
trays, baskets) is 40 percent.
Number cables = Pathway Internal Area X 40%
Cable Area
For the TX6A™
area is 0.0707 inches2 (46 mm2).
For the TX6A™
is 0.0707 inches2 (46mm2).
For the TX6A™
cable, the cable area is 0.0707 inches2 (46 mm2).
For the TX6A™
area is 0.0707 inches2 (46 mm2).
For the TX6A-SD™
cable area is 0.0452 inches2 (29 mm2).
For the TX6A-SD™
cable area is 0.0452 inches2 (29mm2).
For the TX6A-SD™
PUL6ASD04**) cable, the cable area is 0.0452 inches2 (29 mm2).
For the TX6A-SD™
cable area is 0.0452 inches2 (29 mm2).
Refer to the TX6A™ and TX6A-SD™
conduit fill capacity guideline table in Appendix A of this document to
determine the maximum number of cables per conduit trade size.
The maximum fill capacity of 60 percent is allowed to accommodate future additions
after initial installation.
10Gig™ Plenum (i.e. P/N PUP6A04**) cable, the cable
10Gig™ Riser (i.e. P/N PUR6A04**) cable, the cable area
10Gig™ Low Smoke Zero Halogen (i.e. P/N PUL6A04**)
10Gig™ CM/PVC (i.e. P/N PUC6A04**) cable, the cable
10Gig™ Plenum (i.e. P/N PUP6ASD04**) cable, the
10Gig™ Riser (i.e. P/N PUR6ASD04**) cable, the
10Gig™ Low Smoke Zero Halogen (i.e. P/N
10Gig™ CM/PVC (i.e. P/N PUC6ASD04**) cable, the
10Gig™ UTP Copper Cabling
For Technical Support: www.panduit.com/resources/install_maintain.asp
Proper cable bend radius control must be maintained throughout the pathways. The
bend radius needs to be four (4) times the cable diameter.
For the TX6A™
minimum bend radius is 1.20 inches (30 mm)
For the TX6A™
bend radius is 1.20 inches (30 mm)
For the TX6A™
cable, the minimum bend radius is 1.20 inches (30 mm)
For the TX6A™
minimum bend radius is 1.20 inches (30 mm)
For the TX6A-SD™
minimum bend radius is 0.96 inches (24 mm)
For the TX6A-SD™
minimum bend radius is 0.96 inches (24 mm)
For the TX6A-SD™
PUL6ASD04**) cable, the minimum bend radius is 0.96 inches (24 mm)
For the TX6A-SD™
minimum bend radius is 0.96 inches (24 mm)
Pathways and Spacing Management
For data center applications, it is recommended to use Panduit
GridRunner™Underfloor Cable Routing Systems for cable raceway management.
The fittings provide minimum 1.5-inch bend radius to protect against signal loss due
to excessive cable bends.
Pathways should be designed to allow for future expansion (minimum two cables per
work area, with pathways supporting three cables per work area). Therefore when
designing a pathway, the pathway needs to accommodate 150% of the initial cable
installation. For example, if the initial design requires 2 cables each for ten work
areas, the pathway shall be designed to accommodate 30 cables.
Conduit should be run in the most direct route possible with no more than two 90
degree bends between pull boxes and serve no more than three outlet boxes.
Conduit bends should be at least six times the conduit diameter.
Cable trays are to be installed per manufacturing guidelines and loading capacities
must be considered during cabling installation.
Cable trays used in the ceiling should allow for at least 12 inches (305 mm) of
clearance above the tray. Cable trays used in the floor should allow for at least 2
inches (51 mm) of clearance between the top part of the tray and the bottom of the
floor tile.
J-Mod or J-Pro Cable Support System should be located at 5 foot intervals
maximum and have at least 3 inches (76 mm) of clearance above suspended
ceilings.
Please reference Panduit website for J-Mod or J-Pro Cabling Support System fill
capacity information for various sizes available.
10Gig™ Plenum (i.e. P/N PUP6A04**) cable, the
10Gig™ Riser (i.e. P/N PUR6A04**) cable, the minimum
10Gig™ Low Smoke Zero Halogen (i.e. P/N PUL6A04**)
10Gig™ CM/PVC (i.e. P/N PUC6A04**) cable, the
10Gig™ Plenum (i.e. P/N PUP6ASD04**) cable, the
10Gig™ Riser (i.e. P/N PUR6ASD04**) cable, the
10Gig™ Low Smoke Zero Halogen (i.e. P/N
10Gig™ CM/PVC (i.e. P/N PUC6ASD04**) cable, the
®
FiberRunner™ or
For Technical Support: www.panduit.com/resources/install_maintain.asp
limitations with sharing pathways with other category copper cables throughout the
whole cable run.
Separation and physical barriers between TX6A™ or TX6A-SD™
Copper Cable and power cables must be maintained within raceways. If TX6A™ or
TX6A-SD™ 10Gig™ UTP Copper Cable and power cables need to cross install
perpendicular to each other. Please reference the National Electric Code for local
installation guidelines.
The maximum channel distance for the TX6A™
System in the backbone and/or horizontal is 328 feet (100 meters). The total length
of equipment cords, patch cords and work area cords shall not exceed 33 feet (10
meters)
The maximum permanent link distance for the TX6A™
System in the backbone and/or horizontal is 295 feet (90 meters)
The maximum channel distance for the TX6A-SD™
System in the backbone and/or horizontal is 230 feet (70 meters). The total length of
equipment cords, patch cords and work area cords shall not exceed 33 feet (10
meters)
The maximum permanent link distance for the TX6A-SD™
Cabling System in the backbone and/or horizontal is 197 feet (60 meters)
Cable Pulling & Installation Management
The maximum pulling tension is not to exceed 25 lbf. Cable installation should not in
any way deform the cable jacket.
The cable should not come in contact with any water or chemicals (ex. paint,
lubricants), or be exposed to any high humidity during or after installation.
Avoid any cable kinks and maintain proper bend radius control during cabling pulling.
If any kinks should occur, kinked cable should be removed and replaced.
Organize and manage cables for quick and easy moves, adds and changes Use the rack vertical manager fill cable capacity table in Appendix B of this document
to determine the maximum number of cables per telecommunication rack.
Termination procedures at the patch panel include:
Feed cables from both sides of the panel
Maintain acceptable bend radius levels
Do not kink cables
Do not cinch cable ties so tightly as to deform the cable in any way
To enhance wire management in the back of the panel, it is
recommended that a strain relief bar (i.e. P/N SRBM19BLY) be mounted
to the rack. The strain relief bar includes Tak-Ty® Hook & Loop Cable
Ties for additional cable management.
Termination procedures for the DP6A™ 10Gig™ Punchdown Patch Panel include:
Follow installation instruction sheet PN379.
Outer cable jacket should be as close as possible to point of termination
Last twist should be no further than 0.5 inches from the point of
termination.
Cable Management in the Work Area
For surface raceway applications, the Pan-Way
optimal solution in the work area for routing TX6A™ or TX6A-SD™ 10Gig™ Copper
Cables. The TG Raceway system provides adequate space to maintain proper cable
bend radius control.
Allow for at least one outlet per work area with a minimum of two cable terminations. Pathways should be designed to allow for future expansion. For example, work
areas with two cables must be served by pathways that can accommodate a
minimum of three cables.
Allow for at least 12 inches (305 mm) of slack at the work area. Pull slack up into the
ceiling or back into the raceway and store it there, where it can later be pulled into
the box if re-termination is necessary.
Terminate Mini-Com
®
TX6A™ 10GigTM UTP Jack Modules per installation instruction
sheet PN511.
To improve bend radius control of TX6A™ or TX6A-SD™ 10Gig™ Copper Cable in
junction boxes, it is recommended that Panduit sloped faceplates (i.e. P/N
UICFPSE2**) be used in the work area.
With Panduit sloped faceplates, the following junction boxes can be used with
ANSI/TIA/EIA-568-C (Commercial Building Telecommunications Cabling Standard)
ANSI/TIA/EIA-569-C (Commercial Building Standard for Telecommunications Pathways
Practical Fill: Estimate assumes a 40% fill factor (i.e. Sum of the cable cross sectional
areas equals 40% of the vertical channel.) The 40% factor is intended to account for
cable routing.
Note: All content subject to change without notice.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 8 of 8
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.