Panduit PSM7004IG-KED Installation Manual

Page 1
Field test
instrument
C
Work
Area
Outlet
Optional
Consolidation
point
Horizontal Cross-connect
or Interconnect
D E B
A
Maximum length
B + C = 90 m (295 ft)
A + D + E = 10 m (32.8 ft)
Field test instrument
TX6A™ 10Gig™ SHIELDED COPPER CABLING SYSTEM with TX7000™
SHIELDED MARINE COPPER CABLE TESTING PROCEDURE PN546
Copper cabling transmission performance depends on cable characteristics, connecting hardware, patch cords and cross-connect wiring, the total number of connections, and the care with which they are installed and maintained. To qualify for a Panduit System Warranty, post­installation performance testing must be completed using Panduit approved field test instruments to verify that the installed cabling will meet or exceed the performance requirements of the designated classification defined in the Commercial Building Telecommunication Standards. These standards based test results should then be submitted to the Panduit Warranty Department for review.
Panduit offers warranty on the TX6A™ 10Gig™ Copper Cabling System for the current standards, or ANSI/TIA-568-C.2 to channel performance Category 6A, or ISO 11801 Amendment 1 Class EA Ch AMD1.
Channel Test Configuration
The channel test configuration is to be used by system designers and users of data communications systems to verify the performance of the overall channel. Channel performance is the most critical to the end user, as this is how their network will perform. The channel includes up to 90 m (295 ft) of horizontal cable, a work area equipment cord, a telecommunications outlet/connector, an optional transition/consolidation connector, and two connections in the telecommunications room. TIA/EIA recommends and ISO requires that the consolidation point be located at least 5 m (16.4 ft) from the telecommunications room to reduce the effect of multiple connections in close proximity on NEXT loss and return loss. Per the TIA standard, the total length of equipment cords, patch cords or jumpers and work area cords shall not be more than 10 m (32.8 ft). If total patch cords are longer than 10 meters, the entire channel length must be de­rated by the length exceeding 10 meters depending either by 20% or 50% depending on the patch cord cable type used. The connections to the equipment at each end of the channel are not included in the channel definition. The channel definition does not apply to those cases where the horizontal cabling is cross-connected to the backbone cabling. A schematic representation of a channel can be found below.
ANSI/TIA-568-C.2
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 8
Page 2
© Panduit Corp. 2010 TESTING PROCEDURES PN546
Panduit System Warranty
Panduit has different types of warranties. These include the Certification Plus™ System Warranty and the Pan-Net™ Performance Guarantee. Each warranty is standards based. Panduit will typically provide a system warranty in the following way:
Channel Warranty is based on passing channel test results. (It is recommended to keep the patch cords installed after testing as there may be variations between patch cords)
As stated previously, passing test results must be obtained using an approved field test instrument. Panduit places each handheld test instrument thru an evaluation before approving it for use in the field. This ensures the integrity of the test data submitted for warranty.
Current field testers approved for Category 6A:
Fluke DTX-1800 Agilent Wirescope Pro N2640A
Testing Required for TIA/EIA Category 6A Channel Operation Warranty
Panduit requires that internal channel performance be verified for each link to obtain the warranty. Panduit does not require that field alien crosstalk testing be performed, as the TX6A™ 10Gig Copper Cabling System has been thoroughly lab tested and verified to meet alien crosstalk requirements under worse case conditions of 6-around-1 tightly bundled configuration. The customer may wish to perform optional alien testing and this procedure is included for reference.
Fluke DTX-1800 Series Digital Cable Analyzer
Panduit has evaluated the Fluke DTX-1800 Series Digital Cable Analyzer and approves the use of this tester for the certification of installed Category 6A cabling channels. In order to verify that the installed cabling will meet or exceed the performance requirements of the designated classification defined in the ANSI/TIA/EIA Category 6A standard, it is important that the following steps are followed.
Channel Testing
1) Verify that your DTX-1800 Series tester has the most up-to-date software (software version
2.24 or better is required). The latest software updates can be found on the Fluke website at:
http://www.flukenetworks.com/fnet/en­us/supportAndDownloads/downloadsAndUpdates/?pid=50004
Turn on the unit and wait for initialization to complete.
2) Perform a Set Reference procedure in the special functions prior to testing. Fluke Networks recommends that a Set Reference procedure be performed every 30 days to ensure the maximum accuracy of the test results.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 8
Page 3
© Panduit Corp. 2010 TESTING PROCEDURES PN546
For detailed instructions on Set Reference procedure, refer to Fluke Network‟s DTX-1800 Series Users Manual page 20, on “Setting the Reference for Twisted Pair Cabling”. The link
for the User‟s Manual is:
http://www.flukenetworks.com/fnet/en-us/techdocs/Manuals.htm?pid=50004
Note: Fluke Networks also recommends factory calibration once a year to ensure that the
test tool meets or exceeds the published accuracy specifications.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 8
Page 4
© Panduit Corp. 2010 TESTING PROCEDURES PN546
Note – this is the only step that has to be carried out differently for S/FTP cabling from the steps that would be required for testing of a UTP solution
3) Select the Fluke Channel Adapter (# DTX-CHA002) and attach them to the DTX-1800 Series Main and Remote unit.
4) Turn the main function dial from „Autotest‟ one step clockwise to the setting entitled „Setup‟.
5) Under Twisted Pair, set the appropriate Standard Limit to apply different standards,
Select from the following Fluke Test Limits, for which warranty is desired:
TIA Cat 6A Channel ISO11801 Channel Class EA
6) In the scroll down menu, click onto „Cable Type‟, select and click Cat 6A. Scroll down to, Cat 6A FTP and click, and then Shield Test – Enable. This option will ensure that the continuity of the shielding is verified end to end for the complete channel.
Scroll to manufacturer and select accordingly, Scroll to outlet configuration (T568A or B) for your test. Under tab 2 enable HDTDX/HDTDR for all tests.
Under Instrument Settings tab 1, set Store Plot Data to Extended. Under tab 2, enter operator site and company info. Under tab 3 make sure Date and time are set correctly.
Set the main function dial back to Autotest
7) For channel testing, install all patch cords prior to testing. Note: Panduit recommends for installers to install and test a few channels before completing
the entire system.
8) Begin testing your installed channels with the Fluke DTX-1800 Series Digital Cable Analyzer and save all test results.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 8
Page 5
© Panduit Corp. 2010 TESTING PROCEDURES PN546
Approved Test Leads For Panduit ® Mini-Com® TX6A 10Gig Jack Modules and DP6A
10Gig Patch Panels
Channel
Firmware
Version
Software
Version
Calibration
Equipment
Autotest
Test Leads
Personality
Module
Comments
Fluke: Networks DTX-1800
Series Cable
Analyzer
Fluke
Networks
Website
Software:
V2.24 or
later
Linkware
Software V6.0
or later
-
TIA
Cat6A
Channel
Part # DTX-
CHA002 Cat6A / Class E Channel
Adapter
N/A
1. Consult Fluke Networks' website for the latest Firmware and Software Version.
2. It is STRONGLY RECOMMENDED that the tester is calibrated prior to testing
Agilent:
WireScope
Pro N2640A
Agilent
Technologies
Website
WireScope
Pro
Software
3.0.53 or later
WireScope
Pro
(ScopeData
Pro II)
Software
3.0.53 or later
-
Cat6A
Channel
Part # N2644A-100
Universal Cat6A
Channel
SmartProbe
N/A
1. Consult Agilent's website for the latest Software Version.
2. Calibration with the Precision Calibration is STRONGLY RECOMMENDED.
3. Tester holds last calibration. Tester must be recalibrated if using a different DualRemote, upgrading the software, when transitioning from Cat7/Class F copper cable test to Cat6A/Class E or lower performance categories, or after 30 days.
4. Universal Cat6A Channel SmartProbes should be in optimal condition. See owner's manual.
9) Troubleshoot and repair any failing channels. Channels resulting in a PASS* are considered a PASS and will be acceptable for warranty.
Note: The Fluke HDTDX analyzer and HDTDR test are very helpful when troubleshooting failing channels. Both can be found on the SINGLE TEST menu and will also run automatically when a failure occurs. Also make sure that Store Plot Data is set to Extended under Setup/Instrument settings.
10) Submit electronic channel test reports to the Panduit Warranty Department with all required warranty paperwork. A channel warranty will then be given based on passing test results.
Note: Panduit recommends for installers to install and test a few channels before completing the entire system.
Alien crosstalk testing is not needed for shielded cable systems.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 5 of 8
Page 6
© Panduit Corp. 2010 TESTING PROCEDURES PN546
Appendix A
Typical Installation and Testing Equipment Required
Fluke DTX1800 Test Set
4 corresponding Category and short length Patch cords to be used e.g. Category 6A 3 meter
Walkie Talkies?
Typical tool kit for Network Technician. As well as commonly available tools, ensure the kit
contains:
110 type punchdown tools for pairs (PDT110) and for blocks (PDT110M),
GP6™ Punchdown tools for pairs (GPST), for blocks (GPDTM), and base for jacks
(AVPDB),
Panduit wire strippers (CJAST),
Flush cutters (CWST),
Terminating tools (EGJT + CGJT)
Flashlight – smallest (5 to 6-inch) narrow body maglight
Digital Camera (memory card and batteries)
Laptop with Excel and Visio, and latest Fluke test set software
Spare Batteries / power supply / adapters for all the equipment
Drawing Materials (graph paper), markers and Clip Board
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 6 of 8
Page 7
© Panduit Corp. 2010 TESTING PROCEDURES PN546
Freq. (MHz)
Insertion Loss (db)
NEXT (dB)
PSNEXT (dB)
Return Loss (dB)
ACR-F (dB)
PS ACR-F (dB)
ACR-N (dB)
PSACR-N (dB)
1 3 65.0
62.0
19.0
63.3
60.3
4
4.2
63.0
60.5
19.0
51.2
48.2 8 5.8
58.2
55.6
19.0
45.2
42.2
10
6.5
56.6
54.0
19.0
43.3
40.3
16
8.2
53.2
50.6
18.0
39.2
36.2
20
9.2
51.6
49.0
17.5
37.2
34.2
25
10.2
50.0
47.3
17.0
35.3
32.3
31.25
11.5
48.4
45.7
16.5
33.4
30.4
62.5
16.4
43.4
40.6
14.0
27.3
24.3
100
20.9
39.9
37.1
12.0
23.3
20.3
200
30.1
34.8
31.9
9.0
17.2
14.2
250
33.9
33.1
30.2
8.0
15.3
12.3
350
40.6
30.3
27.3
6.6
12.4
9.4
500
49.3
26.1
23.2
6.0
9.3
6.3
Freq. (MHz)
Insertion Loss (db)
NEXT (dB)
PSNEXT (dB)
Return Loss (dB)
ACR-F (dB)
PS ACR-F (dB)
ACR-N (dB)
PSACR-N (dB)
1 4 65.0
62.0
19.0
63.3
60.3
61
58.0 4 4.2
63.0
60.5
19.0
51.2
48.2
58.9
56.4
8
5.8
58.2
55.6
19.0
45.2
42.2
52.4
49.8
10
6.5
56.6
54.0
19.0
43.3
40.3
50.1
47.5
16
8.2
53.2
50.6
18.0
39.2
36.2
45.0
42.4
20
9.2
51.6
49.0
17.5
37.2
34.2
42.5
39.8
25
10.2
50.0
47.3
17.0
35.3
32.3
39.8
37.1
31.25
11.5
48.4
45.7
16.5
33.4
30.4
36.9
34.2
62.5
16.4
43.4
40.6
14.0
27.3
24.3
28.0
24.2
100
20.9
39.9
37.1
12.0
23.3
20.3
19.0
16.2
200
30.1
34.8
31.9
9.0
17.2
14.2
4.7
1.8
250
33.9
33.1
30.2
8.0
15.3
12.3
-0.8
-3.7
350
40.6
30.6
27.6
6.6
12.4
9.4
-10.0
-13.0
500
49.3
27.9
24.8
6.0
9.3
6.3
-21.4
-24.5
Appendix B
Standards Limits
ANSI/TIA-568-C.2 Category 6A Channel
ISO Class EA Ch AMD1
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 7 of 8
Page 8
© Panduit Corp. 2010 TESTING PROCEDURES PN546
Part Number
Description
Jack Modules
CJS6X88TGY
Mini-Com® TX6A™ 10Gig™ Shielded Jack Module
Cable
PSM7004IG-KED
TX7000™ Marine Rated S/FTP Category 7 Shielded Copper Cable
Patch Cords
STP6X**
TX6A™ 10Gig™ STP Patch Cords
Modular Panels
Mini-Com® All Metal Shielded Modular Patch Panels
CP16BLY
16 port, 1 RU
CP24BLY
24 port, 1 RU
CP48BLY
48 port, 1 RU
CP72BLY
72 port, 1 RU
CP16WSBLY
16 port, 1 RU, with strain relief bar
CP24WSBLY
24 port, 1 RU, with strain relief bar
CP48WSBLY
48 port, 1 RU, with strain relief bar
Panduit TX6A™ 10Gig™ Copper Cabling System Product List
** - denotes additional characters required for complete part number
For Technical Support: www.panduit.com/resources/install_maintain.asp