Panduit PE2VFD10 Installation Manual

Page 1
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 13
© Panduit Corp. 2018
V00029RB
PATCHRUNNERTM 2 Enhanced Vertical Managers
Table of Contents
Description Page
Part Configurations and Contents ...................................................................................................2
Door Support Installation …………..................................................................................................3
Orientation of Vertical Manager to Rack .......................................................................................4
Installation of Vertical Manager to Rack .......................................................................................5
End of Row Bracket Condition (Optional) ……………………...........................................................6
Finger Installation..............................................................................................................................7
Door Installation ...…………………...................................................................................................8
EIA 19” Equipment Vertical Mounting ……………………………………………………….……………9
End Panel Installation......................................................................................................................11
Other Compatible Accessories........................................................................................................12
Part Numbers
Style
Front/Rear Two doors
Front Only
Single Door
Front/Rear
Single door
7ft
Tall
PE2VD06
PE2VFD06
PE2VSD06
PE2VD08
PE2VFD08
PE2VSD08
PE2VD10
PE2VFD10
PE2VSD10
PE2VD12
PE2VFD12
PE2VSD12
8ft
Tall
PE2VD0696
PE2VFD0696
PE2VSD0696
PE2VD0896
PE2VFD0896
PE2VSD0896
PE2VD1096
PE2VFD1096
PE2VSD1096
PE2VD1296
PE2VFD1296
PE2VSD1296
Add "WH" as a suffix to the part numbers listed above to identify a white part, such as PE2VD06WH
Tools required:
3mm Allen Wrench (Door Support installation) 17mm Wrench (Rack installation) 18mm Wrench (Rack installation) 5mm Allen Wrench (Optional End of Row Bracket installation)
Page 2
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 13
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
V00029RB
Front / Rear Assembly Contents
(1) PATCHRUNNER
TM
2 Enhanced Vertical Cable
Manager (2) Door Support assemblies – Qty 2 (3) PATCHRUNNER
TM
2 door – Qty 2
(4) Molded cable management left finger kits
7ft – Qty 6 8ft – Qty 8 (5) Molded cable management right finger kits
7ft – Qty 6 8ft – Qty 8 (6) Hardware Kit (not shown)
Includes:
M12 Serrated Flange Bolts and Hex Nuts – Qty 6
End of Row Bracket with (2) M6 Socket Head Cap
Screws
M5 Flat Head hex drive screws – Qty 12
Front Only Assembly Contents
(1) PATCHRUNNER
TM
2 Enhanced Vertical Cable
Manager
(2) Door Support assemblies – Qty 2 (3) PATCHRUNNER
TM
2 door – Qty 1
(4) Molded cable management left finger kits
7ft – Qty 3 8ft – Qty 4
(5) Molded cable management right finger kits
7ft – Qty 3 8ft – Qty 4
(6) Hardware Kit (not shown)
Includes:
M12 Serrated Flange Bolts and Hex Nuts – Qty 6
M5 Flat Head hex drive screws – Qty 12
Page 3
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 13
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
V00029RB
Door Support Installation
Cable manager frame assembly
Door Support assembly (2 per cable manager)
M5 flat head screws, use a 3mm hex allen wrench to secure in place at the top and bottom of the manager frame.
Bottom of the assembly is indicated by the diamond shaped cutouts on the cable manager side panels.
NOTE:
The Door Support assembly slides vertically into place in the cable manager. Orientate so that the 40/60 open areas match as shown on the next page and align mount holes. The bottom of the vertical cable manager assembly is identified by the diamond shaped cutouts at the lower edge of the side panels.
Page 4
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 13
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
V00029RB
LARGER SIDE FACING FORWARD
APPROX. 40% OF CAPACITY
APPROX. 60% OF CAPACITY
APPROX. 60% OF CAPACITY
SMALLER SIDE FACING FORWARD
Determine Cable Manager Mount Orientation to the Rack
APPROX. 40% OF CAPACITY
PATCHRUNNER
TM
2 Enhanced Vertical Cable Managers may be installed with either side facing forward.
Page 5
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 5 of 13
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
V00029RB
Installation of Vertical Cable Managers to Racks
The Vertical Cable Manager will mount to the rack in 3 locations using (3) M12 Serrated Flange Bolts and (3) M12 Serrated Flange Nuts on 2 Post and 4 Post racks regardless of size.
The racks have pairs of mounting holes where the vertical cable manager can be mounted, but the vertical cable manager is designed to use only one mounting hole per pair. Align the mount holes as shown. The mount holes used on the rack will be the forward holes on the top and bottom mount locations and the rear rack hole in the center mount location regardless of which side of the vertical cable manager is facing forward.
Installed view with 40% capacity side of the vertical cable manager facing forward
Installed view with 60% capacity side of the vertical cable manager facing
-Top ­Forward mount hole
-Bottom­Forward mount hole
-Middle­Rear mount hole
Page 6
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 6 of 13
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
V00029RB
End of row bracket condition (Optional)
Place end of row bracket around inside face of the rack vertical post and inside face of Vertical Cable Manager as shown.
Tighten the end of row bracket using (2) M6 x 30mm Socket Head Cap screws.
M6 x 30mm Socket Head Cap screws
End of row bracket
Inside face of rack vertical post
Inside face of vertical cable manager
Page 7
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 7 of 13
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
V00029RB
Finger Installation to PATCHRUNNERTM 2 Enhanced Vertical Managers
Finger Removal and Replacement
Step 1: Using a flat head screwdriver, gently pry up plastic latches in (4) places indicated while at the same time applying forward pressure to the finger section. Step 2: Push out the finger section toward the inside of the manager.
Align finger mount tabs with mounting slots on the manager side panels. Finger sections installed pointed up with the rounded side facing inward. Push toward the outside of the manager until you her an audible “click”.
7 ft Managers: 3 Fingers per side
8 ft Managers: 4 Fingers per side With the shorter section Installed at the top position
Latch tab location
Page 8
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 8 of 13
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
V00029RB
Door Installation
Hinge pins
Door knobs in locked position
Align Door hinge pins on 4 sides to slots on door supports and simply push closed. The door knobs will be in locked position as shown.
Hinge pins
slots
slots
Page 9
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 9 of 13
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
V00029RB
EIA 19” Equipment Vertical Mounting Instructions
Detail View
Cable Manager Horizontal Panel
1. Mount the appropriate cage nuts to the square cutouts provided in the cable manager horizontal panels to allow mounting of EIA 19” equipment.
2. Secure equipment using appropriate screws.
Cage nut cutouts
Optional Slack Spool mount keyhole slots
Rack unit I.D. marks
Tak-Ty Hook & Loop cable tie slots
Page 10
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 10 of 13
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
V00029RB
To open the door to the right, turn the left knob counterclockwise until engaged. To open door to the left, turn the right knob clockwise until engaged.
Page 11
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 11 of 13
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
V00029RB
End Panel Installation to PATCHRUNNERTM 2 Enhanced Vertical Managers
Part Numbers: PE2VEP, PE2VEPWH, PE2VEP96, PE2VEP96WH Installing Bottom Panel:
Bottom panel with integral hooks
M10 x 16 Serrated hex head bolt and nut (4x)
Diamond cutout indicates bottom of panel
Use integrated hooks on the bottom panel to clip in place in the square cutouts on the cable manager side panels
Top panel
M10 x 16 Serrated hex head bolt and nut (2x)
Use integrated hooks on the top panel to hang in place in the front to back door support brackets and align mount holes
M6 x 16 Serrated hex head bolt and nut (2x)
Page 12
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 12 of 13
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
V00029RB
Other Compatible Accessories (sold separately)
PRSP5 and PRSP7 Slack Spools
Mount face
Angled flange for removal
Mount keyhole slots
Mount buttons
Step 1: Align spool mount buttons with keyhole slots in the cable manager horizontal panel, with the angled flange facing upwards. Step 2: Push spool mount buttons though the keyholes and apply downward pressure until the spool clicks into place. Step 3: To remove the spool, pull back on the mount flange while applying pressure upward.
Note: Spools will hold up to 14 lbs.
WR5E-X Cable Retainer Clip
To install cable retainer clips, place the open end of the clip around the leg of the molded finger on the vertical cable manager and position as required.
Cable retainer clips
Page 13
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 13 of 13
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
V00029RB
SRB19BLY, SRB19MDBL, SRB19D5BL, SRB19D7BL Strain Relief Bars
Strain relief bars can be mounted vertically in the cable manager patching area using #12-24 screws and cage nuts. Multi-Layer Strain Relief Bars can be used to create vertical channels within the manager and additional cable support and management.
Other Compatible Accessories (sold separately)
Strain Relief Bar
#12-24 screws and cage nuts supplied with the Strain Relief Bar
Top view
Strain Relief Bar
BR1B, BR2B Brush Seal Blank Panel 19” Panels
1RU or 2RU Brush Seal Blank Panels can be mounted vertically in the cable manager patching area using screws and cage nuts. Brush Seal Blank Panels allow front to back cable management while maintaining a thermal seal pass through.
Brush Seal