Parts Included:
(1) - Extra Door Spacer
(8) - Keys
(1) - Roll of Tak-Ty
(3) - Packages of 4 - #12-24 Screws
(1) - Removable top vent cover panel
PZWMC12W
Cabinet with Windowed Door
Location Footprint
Cabinet depth is 25.0” in
closed position
FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
Page 1 of 7
Page 2
INSTRUCTIONS CM315B
PANZONE Wall Mount Cabinets can be installed in a hinged right or hinged left
application. For your installation, determine which side of the cabinet will hinge.
The cabinet is shown hinged left. Mounting surface must have sufficient strength to support the cabinet with payload. The mounting surface must also
be flat and extend beyond the overall cabinet footprint.
To open cabinet,
push latch release
button to dis-engage
latch.
2” or 2 1/2” Conduit Knockout
Front Door
with Lock
Plastic Spacer
Step 2:
To reverse rear hinge direction.
Open cabinet, and remove the latch from the rear lock. Remove the rear lock and the
lock hole grommet on the opposite side. Close the cabinet and remove decorative covers
on hinges. Remove the thread forming screws & lockwashers from the hinges (M5), and
latches (M4), and re-install the components on the opposite sides of the cabinet. Open
the cabinet and re-install the lock and grommet on the opposite sides. Re-assemble the
lock latch, ensuring it locks in the downward rotation (see below).
1/2” or 3/4” Conduit Knockout
Step 1:
Remove door and side panels for ease of handling. Ensure rear latches are
closed. Install (4) 3/8” mounting hardware (not provided) as shown in Location
Footprint. Hardware should protrude 3/8” from wall. Mount the cabinet to the
wall by hooking the keyholes over the protruding 3/8” mounting hardware.
Once the cabinet is in place, carefully swing cabinet from wall and tighten the
hardware securely. Re-install door and side panels. Door swing direction can
be changed by rotating the door 180°. Ensure the plastic spacer is placed at
the bottom of the door hinge.
Step 3:To adjust the depth of the mount-
ing rail for specific applications, remove
the M6 thread forming screws and lockwashers, move the rail to the desired
position and re-install mounting hardware.
M5 Thread forming
screws & lockwashers
Hinge
Lock Hole
Grommet
Lock
Lock in downward
rotation
M4 Thread forming
screwsLatch
Mounting Rails are adjustable in
0.9” increments.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Mounting Rail
Mounting Hardware
Page 2 of 7
Page 3
INSTRUCTIONS CM315B
Cable Routing
Cable must be routed with an adequate slack loop to prevent cable damage. Route cable to point 1 secure to tie down with a TAK-TY. Next
route cable across the bottom of the enclosure to point 2 secure to tie down with a TAK-TY. Route to the desired patch panel after securing
the cables with a T
AK-TY at point 3 or 4.
Point 4
Cables Extend
to Patch Panel
Point 2
Point 3
Point 1
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 7
Page 4
Optional Accessories
INSTRUCTIONS CM315B
PZWMC12P
Cabinet with Perforated Door
PZWMC12W (Shown)
Cabinet with Window Door
PZCHSM2
ANZONE Horizontal
P
Slack Manager
For Technical Support: www.panduit.com/resources/install_maintain.asp
PZBR4
ANZONE 4” Bend
P
Radius Post Kit
PZBR3
ANZONE 3” Bend
P
Radius Post Kit
PZBR3.5
P
ANZONE 3.5” Bend
Radius Post Kit
Page 4 of 7
PZWMC12RR
ANZONE Rear Equipment
P
Rail Kit
PZCFK
P
ANZONE Fan Kit
PZCFR
ANZONE Fan Media
P
replacement Kit
Page 5
INSTRUCTIONS CM315B
PANZONE Fan Kit (PZCFK)
Fan kits are installed using (4)#10-32 screws and lockwashers provided with kit as shown below. If only one fan kit is used, install the provided blank on the
opposite wall using (4) #10-32 screws and lockwashers provided.
Scenario 1: Switches not exceeding 120 watts of total heat output use fan kit as shown.
Scenario 2: POE (Power over Ethernet) or switches totaling over 120 watts of total heat, use two fan kits mount second fan where blank is shown.
Optional: Remove Top Panel Blank for additional venting. A Fan Kit can be installed on top vent, but will occupy the top RU space.
M5 Thread forming screws
Top Panel Blank
Fan Kit Blank
Note: When using switches with side air intake and opposite side exhaust use one fan without fan blank
Fan Kit
#10-32 Screws and
Lockwashers
(8 Places)
Mounting Rail Installation (PZWMC12RR)
To install mounting rail use (2) M6 thread forming
screws & lockwashers at desired location as shown
below
For Technical Support: www.panduit.com/resources/install_maintain.asp
Mounting Rail
Mounting Hardware
Page 5 of 7
Page 6
INSTRUCTIONS CM315B
PANZONE Horizontal Slack Manager
Install tray using (4) #12-24 x 1/2 screws provided at desired
RU as shown in figure 3. Refer to recommended layout
section for optimal mounting location(s).
Screw Mounting Locations
Bend Radius Post Installation
Bend radius posts can be installed at any rack location using (1)#12-24 x 2.5" [(1) #12-24 x 1.5” for PZBR3]screw provided as shown in
Figure 1. Post can be customized by removing tabs as show in Figure 2.
Note: Post may be installed over active equipment mounting locations
Figure 3
Figure 1
Figure 2
Bend
Radius
Post
Score Line
#12-24 x 2.5" Screw
Recommended Layout
24 Port Patch Panel
24 Port Patch Panel
PZCHSM2
24 Port Patch Panel
For Technical Support: www.panduit.com/resources/install_maintain.asp
24 Port Patch Panel
PZCHSM2
Active Equipment
Page 6 of 7
Page 7
INSTRUCTIONS CM315B
c
L
c
L
Recommended Cable Routing Guide
Place patch cord slack around furthest spool as feasible to
provide best possible cable management
Never cross over center line of horizontal slack manager
with cable slack
Top View of PZCHSM2
Typical patch cord length is 4 feet
Route patch cords as shown to avoid crossover
Recommended Mounting Locations
for Bend Radius Posts
Typical patch cord length is 5 feet
Route patch cords as shown to avoid crossover
Routed to top Horizontal
Slack Manager
For instuctions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
Lower
Horizontal
Manager
www.panduit.com
Page 7 of 7
Recommended Mounting Locations
for Bend Radius Posts
Route patch cords going to top horizontal
slack towards the outside of the cabinet to
avoid cross overs with patch cords going
to lower slack manager.