Keyed Knockout
Slots for Wall
Mount Application
(6 places)
INSTALLATION INSTRUCTIONS CM310
List of Components:
(4) #10-32 Hex Nuts
(4) #10 Split Lock Washers
(4) #8-32 Hex Nuts
(4) #8 Split Lock Washers
(1) Grounding Cable
(4) Pieces of Fire Resistant Foam
(1) 26" length Grommet Edging
(1) 2 Position Surface Mount Box
(PANDUIT Part No. CBXJ2WH-A)
(1) 2' long Cat5e Patch Cord
(PANDUIT Part No. UTPCH2)
(1) Cat5e Jack Module
(PANDUIT Part No. CJ5E88TWH)
(1) Foam Retention Plate
(1) Key
PZWIFIEW
Brackets for Fire
Resistant Foam
(2 places)
#10-32 threaded
Grounding Studs
Knockouts
for Surface
Raceway
(2 places)
Double Knockout
for 1/2” or 3/4”
Conduit (3 places)
(door removed from view for clarity)
TABLE OF CONTENTSPage (s)
External Wall Mount Installation........................................................................................ 2-4
In-Ceiling Mount Installation.............................................................................................. 5-7
For Technical Support: www.panduit .com/resources/install_maintain.asp
Page 1 of 8
Page 2
INSTALLATION INSTRUCTIONS CM310
EXTERNAL WALL MOUNT INSTALLATION
Refer to the installation and configuration guidelines provided by the manufacturer of the wireless
access point to determine the optimum enclosure installation location and antenna configuration.
Please read these instructions in their entirety prior to installing the enclosure.
Step 1: Knockout Removal
1.1 Determine whether the network cable will be routed into
the enclosure through conduit or surface raceway.
Remove the appropriate knockouts.
For Conduit - Remove knockout “A”, “B” or “C”. This
double knockout accommodates either 1/2” or 3/4”
conduit.
For Surface Raceway - Remove knockout “D” or “E”. This
opening accommodates PANDUIT LD10 surface raceway.
1.2 Locate the wall studs. Position the enclosure on the wall
and identify which keyed knockouts should be removed. It
is recommended that two of the mounting holes be aligned
with the wall stud. Wall anchors (not included) should be
used for each additional mounting hole chosen by the
installer. Remove desired knockouts.
Optional: Flexible grommet edging can be used to cover
knockout edges if desired.
11
D
A
E
B
C
Step 2: Mount Enclosure to Wall
2.1 Locate the wall studs.
2.2 Hold the enclosure against the wall to mark the
location of the mounting holes.
2.3 Mount the enclosure to the wall using mounting screws
and wall anchors (not included). Enclosure designed
for use with #14 screws.
Step 3: Install Wireless Access Point Bracket
3.1 Place the Wireless Access Point Mounting Bracket
(supplied with the enclosure) inside the enclosure
Install the bracket in the orientation as shown in the
view.
3.2 Secure the mounting bracket with the supplied #8 Split
Lock Washers and #8-32 Hex Nuts.
2
3
3
MountingBracket
2 x 4 Stud
Panduit
Supplied
Mounting
Bracket
For Technical Support: www.panduit .com/resources/install_maintain.asp
Page 2 of 8
Page 3
INSTALLATION INSTRUCTIONS CM310
Step 4: Grounding
4.1 Run cable from the Telecommunications Grounding
Busbar (TGB) to the enclosure and attach to the
grounding stud on the base.
4.2 Using the supplied Grounding Cable, attach one end to
the grounding stud on the base (on top of TGB cable)
and the other end to the grounding stud on the door.
4.3 Secure with the #10 Split Lock Washers and #10-32 Hex
Nuts.
Step 5: Install Wireless Access Point
5.1 Attach mounting plate supplied with Cisco 1130 access
point to the enclosure base with the Cisco supplied #632 x 1/4” flat head screws (note orientation)
5.2 Prepare the Cisco AP1130 access point for installation
by gently pushing the access point to the open position.
5.3 Line up the access point keyholes with the two keyhole
pads on the Cisco Supplied mounting plate.
5.4 Slide the WAP downward over the keyhole pads until
an audible “snap” is heard. Lightly pull the WAP in the
opposite direction to verify that it is properly locked into
place.
4
4
5a
Grounding
Studs
GroundingStuds
Cisco Supplied
Mounting Plate
Step 6: Install Surface Mount Box
6.1 Run the network cable to and into the enclosure.
6.2 Terminate the Cat5e Jack Module to the network cable.
Refer to the PANDUIT website for jack termination
instructions if needed.
6.3 Mount the base of the 2 Position Surface Mount Box to
the back wall of the enclosure using provided double
sided tape.
6.4 Snap the terminated jack into position “1” of the box.
Place the network cable between the two cable
retention tabs on the back of the base.
6.5 Remove the breakout tab on the back of the cover.
6.6 Snap the cover onto the base.
Note: A second Cat5e Jack Module can be installed in
position “2” of the surface mount box to provide
access to the serial port on the WAP.
Step 7: Install Patch Cord
7.1 Insert one end of the 2' long Cat5e Patch Cord into the
RJ45 port located on the WAP.
7.2 Insert the other end of the patch cord into the Cat5e
jack located in the surface mount box.
#6-32x1/4” Flat Head
Screws
WAP
5b
6 / 7
Surface
Mount
Box
For Technical Support: www.panduit .com/resources/install_maintain.asp
Page 3 of 8
Page 4
INSTALLATION INSTRUCTIONS CM310
IN-CEILING MOUNT INSTALLATION
Refer to the installation and configuration guidelines provided by the manufacturer of the wireless
access point to det e rmine the optimum enclosure installation location and ante nna configuration.
Please read these instructions in their entirety prior to installing the enclosure.
Note: PANDUIT Part Number PZWIFIDCB is required
for the in-ceiling mount application.
1
Step 1: Knockout Removal
1.1Remove knockouts in desired cable entry location:
For Conduit - Remove knockout “A”, “B” or “C”. This
double knockout accommodates either 1/2” or 3/4”
conduit.
Without Conduit - Remove knockout “A” or “B”.
Remove the 1/2” diameter opening.
C
A
B
Step 2: Install Wireless Access Point Bracket
2.1 Place the Wireless Access Point Mounting Bracket
(supplied with the enclosure) inside the enclosure
Install the bracket in the orientation as shown in the
view.
2.2 Secure the mounting bracket with the supplied #8
Split Lock Washers and #8-32 Hex Nuts.
For Technical Support: www.panduit .com/resources/install_maintain.asp
2
Panduit
Supplied
Mounting
Bracket
Page 4 of 8
Page 5
INSTALLATION INSTRUCTIONS CM310
Step 3: Install Ceiling Mount Brackets
PANDUIT Part #: PZWIFICB - PanZone Wireless Access Point
Ceiling Bracket Kit (sold separately)
3.1 Install Ceiling Mount Brackets against side wall of the
enclosure with the flanged edge facing away from the
enclosure. (see figure 3) The top of the flanged edge
should be even with the enclosure door.
3.2 Fasten the bracket to the base of the enclosure using
four of the supplied #6-32 Screws.
3.3 Repeat steps for remaining 3 Ceiling Mount Brackets.
Step 4: Prepare Ceiling Tile
4.1 When the enclosure will be mounted in a suspended
ceiling, a square hole that is approximately 12 1/2" x 12
1/2" must be cut in the ceiling tile.
4.2It is important that the hole be no smaller than 12 1/4"
x 12 1/4" and no larger than 12 3/4" x 12 3/4". This
will ease installation and prevent visible gaps around
the enclosure once installed.
Note: The bottom edges of the assembled enclosure
brackets can be used as a guide to trace the square
hole size onto the ceiling tile.
3
4
Option A
12.5"
12.5"
12.5"
Option B
12.5"
Step 5: Install Enclosure to Ceiling
5.1Hanger wire should be used to hang the enclosure
within a suspended ceiling. Important: Verify hanger
wire meets local building code. Weight of enclosure
and WAP does not exceed 10 lbs.
5.2Observe how the hanger wire used to hold the ceiling
support grid is secured to the building structure.
5.3Remove one tile adjacent to the tile the enclosure will
be mounted in.
5.4Secure four pieces of hanger wire (not included) to the
building structure. The hanger wire length will be
determined by the installer based on the buildi ng
structure dimensions above the suspended ceiling.
Extend the length of the hanger wire beyond the
surface of the ceiling by at least 6".
5.5Add the cut ceiling tile back to the ceiling support grid.
5.6Pull one of the four pieces of hanger wire to one corner
of the square opening in the ceiling tile. Pre-bend the
hanger wire at a 90° angle approximately 2 1/2" above
the surface of the ceiling tile. Repeat this step for the
remaining 3 hanger wires measuring to the three
remaining corners of the square opening.
5.7Insert the enclosure into the cut ceiling tile opening.
5.8While holding the enclosure flush with the surface of
the ceiling tile, route the hanger wire through one of the
eight 3/8" dia hanger wire mounting holes and bend up.
Pull the wire upward until the enclosure is flush with the
5
3/8” dia hanger wire
mounting holes
(8 places)
ceiling tile. Repeat this step using the three remaining
hanger wires to secure the three remaining corners of
the enclosure.
5.9Visually inspect the edges of the enclosure to verify no
gaps exist between the mounting brackets and surface of
the ceiling tile. If gaps exist, pull the hanger wire upward
until the enclosure is tight against the ceiling tile.
5.10 To secure the enclosure, wrap each hanger wire tightly
around itself a minimu m of three times.
5.11 Replace the adjacent ceiling tile.
For Technical Support: www.panduit .com/resources/install_maintain.asp
Page 5 of 8
Page 6
INSTALLATION INSTRUCTIONS CM310
Step 6: Grounding
6.1 Run cable from the Telecommunications Grounding
Busbar (TGB) to the enclosure and attach to the
grounding stud on the base.
6.2 Using supplied Grounding Cable, attach one end to the
grounding stud on the base (on top of the TGB cable)
and the other end to the grounding stud on the door.
6.3 Secure with the #10 Split Lock Washers and #10-32
Hex Nuts.
Step 7: Install Wireless Access Point
7.1 Attach mount plate supplied with Cisco 1130 access
point to the enclosure base with the Cisco supplied #632 x 1/4” flat head screws (note orientation)
7.2 Prepare the Cisco AP1130 access point for installation
by gently pushing the access point to the open position.
7.3 Line up the access point keyholes with the two keyhole
pads on the Cisco Supplied mounting plate.
7.4 Slide the WAP downward over the keyhole pads until
an audible “snap” is heard. Lightly pull the WAP in the
opposite direction to verify that it is properly locked into
place.
6
Grounding
Studs
7a
Cisco Supplied
Mounting Plate
Step 8: Install Surface Mount Box
8.1 Route the network cable to and into the enclosure.
Important: When mounting the enclosure in the ceiling,
it is recommended that an excess length of network
cable be stored outside of the enclosure when conduit
is not used. The length of cable placed outside the
enclosure above the ceiling should be long enough to
allow the enclosure to be removed from the ceiling for
maintenance without cutting the network cable from the
Cat5e jack that will be installed in the next step. This is
necessary because the Cat5e jack cannot be removed
through a 1/2” conduit knockout.
8.2 Terminate the Cat5e Jack Module to the network cable.
Refer to the PANDUIT website for jack termination
instructions if needed.
8.3 Mount the base of the 2 Position Surface Mount Box to
the back wall of the enclosure using provided double
sided tape.
8.4 Snap the terminated jack into position “1” of the box.
Place the network cable between the two cable
retention tabs on the back of the base.
8.5 Remove the breakout tab on the back of the cover.
8.6 Snap the cover onto the base.
Note: A second Cat5e Jack Module can be installed in
position “2” of the surface mount box to provide
access to the serial port on the WAP.
#6-32x1/4” Flat Head
Screws
WAP
7b
8
Surface
Mount
Box
For Technical Support: www.panduit .com/resources/install_maintain.asp
Page 6 of 8
Page 7
INSTALLATION INSTRUCTIONS CM310
Step 9: Install Fire Resistant Foam (if needed)
Note: Fire Resistant Foam used when network cable is
routed into the enclosure without the use of conduit in
flush wall mount and in-ceiling mount applications.
9.1 Place two pieces of fire resistant foam into the foam
retention bracket. Both pieces should be underneath
the network cable and the ground cable.
9.2 Place the remaining two pieces of fire resistant foam on
top of the cables.
9.3 Press down on the foam and slide the foam retention
plate into place. The expanding foam holds the
retention plate in place.
9
1
3
56
2
4
Step 10: Install Patch Cord
10.1 Insert one end of the 2' long Cat5e Patch Cord into the
RJ45 port located on the WAP.
10.2 Insert the other end of the patch cord into the Cat5e
jack located in the surface mount box.
10
Surface
Mount
Box
For Technical Support: www.panduit .com/resources/install_maintain.asp
Page 7 of 8
Page 8
INSTALLATION INSTRUCTIONS CM310
PZWIFIEPZWIFIE with PZWIFICB
Designed for Cisco Aironet™ 1200 Series (excludes Cisco Aironet™ 1232AP)
PZWIFIEDPZWIFIED with PZWIFIDCB
Designed for Cisco Aironet™ 1232AP
PZWIFIEWPZWIFIEW with PZWIFICB
Designed for Cisco Aironet™ 1130 series APs
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
E-mail:
cs@panduit.com
Fax:
(708) 444-6448
Page 8 of 8
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.