Pan-Punch 110 Tower System
© Panduit Corp. 2013
INSTALLATION INSTRUCTIONS
CABLE REQUIREMENT: Terminates most 22-26 AWG solid or stranded
IWC wire with a 0.05" (1.27mm) max. o.d., either PVC or Plenum rated.
NOTE: 300 PAIR TOWER SHOWN. INSTRUCTIONS ALSO APPLY TO THE 900 PAIR TOWER.
1. Mount tower to wall using #12 wood screws (not provided) or
equivalent. Some applications will require different mounting
hardware. Ensure that the bottom of the tower is at least 8" from
the floor to provide space for horizontal cable manager trough.
PN79H
2. Route cable bundle into tower and fan out individual cables into
their appropriate positions through the cutouts provided along the
tower leaving 12" to 18" of slack. Each cutout accommodates up
to 25 pair. Use cable ties to secure bundle to raised tabs on back
of tower.
3. Position base over slots in tower and secure with two #12
sheet metal screws (supplied). Place conductors into index
strip and install connecting blocks as per instruction sheet
PN51* (provided).
Screw here
4. Install jumper troughs between bases with two #12 sheet metal
screws (supplied).
Screw here
* Denotes instruction sheet revision letter.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 2

© Panduit Corp. 2013
INSTALLATION INSTRUCTIONS
PN79H
CABLE REQUIREMENT: Terminates most 22-26 AWG solid or stranded
IWC wire with a 0.05" (1.27mm) max. o.d., either PVC or Plenum rated.
5. To help contain cross-connections, install vertical cable managers (P110VCM300 for 300 pair and P110VCM900 for 900 pair) adjacent
to towers using #12 wood screws (not provided) or equivalent.
Attach horizontal cable manager trough to towers and vertical cable managers using #12 sheet metal screws and #12 external tooth
lockwashers (provided). Fasten securely to assure grounding. Attach ground lug (P/N:LAM2A2/0-14-6) with 1/4" x 3/4" machine screw,
nut, and 1/4" external tooth lockwasher (provided), to the bottom of the horizontal cable manager trough.
Component Quantity per Tower System
Base Trough Connecting Blocks Label Holders Labels
Part Number P110B100 P110JT P110CB3 P110CB4 P110CB5 P110CB4IG P110CB5IG P110LH DSL110
P110KT3004Y 3 3 - 60 12 - - 6 6
P110KT3005Y 3 3 - - 60 - - 6 6
P110KT9004Y 9 9 - 180 36 - - 18 18
P110KT9005Y 9 9 - - 180 - - 18 18
Notes:
1. Pan-Punch
2. Never install wire into a slot previously used for a larger gauge.
3. Be careful to strip back cable jacket only as required for termination.
4. Use care to maintain pair twists to within 0.50" (13mm) of the termination strip.
5. When stripping cable jacket, be careful not to cut the insulation on the individual wires.
6. Avoid sharp bends when routing cable.
As with all Wiring Accessories, the following statements apply:
1. Never install communications wiring during a lightning storm.
2. Never install communications wiring in wet locations unless the product is specifically designed for use in wet locations.
3. Never touch uninsulated communications wiring or terminals unless the communication line has been disconnected at the network interface.
4. Use caution when installing or modifying communication wiring.
product terminates most 22-26 AWG solid or stranded IWC wire with a 0.05" (1.27mm) max. o.d., either PVC or Plenum rated.
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
Page 2 of 2