COPPER COMPRESSION CONNECTORS
C
Panduit Corp. 2007
INSTALLATION INSTRUCTIONS T-PMPI-61-PC
COPPER COMPRESSION CONNECTOR INSTALLATION
1. Use a connector marked for the wire size and wire material to be used. NEVER
use a copper conductor on aluminum wire.
2. Strip wire insulation to approximate length shown on tool chart. DO NOT nick
or ring the conductor strands.
3. Clean the wire.
4. Insert stripped wire into connector until the wire stops.
5. Using installation tooling shown on other side, insert connector in die and crimp
between color bands or knurl markings. REQUIRED NUMBER OF
COMPRESSIONS SHOWN IN ( ).
6. After crimping, inspect for sharp edges, flash or burrs and remove if present.
HEAT SHRINK INSULATION INSTRUCTION
1. Refer to catalog for tubing size.
2. Cut tubing to length allowing insulation coverage as desired. Allow a minimum
of 1-1/2" inch overlap on wire insulation.
3. Shrink with a standard propane torch or heat gun. MOVING FROM CRIMPED
PORTION OF CONNECTOR TOWARD INSULATED WIRE. Adhesive flow at
ends indicate shrinkage complete.
LISTED
587H
For Technical Support: www.panduit.com/resources/install_maintain.asp
CERTIFIED
Page 1 of 2
Rev 03

C
Panduit Corp. 2007
INSTALLATION INSTRUCTIONS T-PMPI-61-PC
Tool Chart for Compression Connectors
Type LCBH, LCCH, and SCH with Copper Cable
* CD-940 dies to be used exclusively with CT-940CH and CT-2940 tools.
** CD-920 dies can be used with CT-940CH and CT-2940 tools with CD-940-DA die adapter.
NOTE:
See product package or contact factory for UL/CSA approved tooling/product combinations
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com