Panduit J318-412-2M Installation Manual

Page 1
PAN-TERM
WIRE JOINT
PART NUMBER
J318-412
Tinley Park, Illinois 60477-3091
PMPTI05
© Panduit Corp. 2002
• Circular mil range: 4860-27330
• For solid & stranded CU wire
LISTED 587H
CERTIFIED
• Use tool: CT-100 or CT-200
• Strip length 1/2" (11.1 mm)
• Twist all wires together
+ 1/32 – 0
CRIMPING INSTRUCTIONS - TOOL CT-100 & CT-200
1. Twist ends of stripped wire together and insert into wire joint (see above for strip length).
2. Insert wire joint in 12-10 crimping die. Center the crimping die over the wire joint (see below) and crimp by closing handles firmly.
3. Trim off excess wire.
pmpti05.qxd 8/2/02 1:55 PM Page 1
Page 2
Wire Combination Chart for Wire Joint J216-410
Wire Size
Number
of
Wires
#16 AWG
#14 AWG
#12 AWG
#10 AWG
Number of Additional
Wires of One Size
1 2 3 4 5 6 7 8 9
#16
AWG
1 to 9 1 to 8 1 to 7 1 to 6 1 to 5 1 to 4 1 to 3 1 or 2
1
1 to 5 1 to 5 1 to 3 1 to 3 1 to 3 1 or 2
1 0 0
1 to 3 1 to 3 1 or 2 1 or 2 1 or 2
1 0 0 0
0 0 0 0 0 0 0 0 0
1 2 3 4 5
#14
AWG
1 to 7 1 to 6 1 to 5 1 or 2 1 or 2
1 to 5 1 to 4 1 to 3 1 or 2
1
1 to 4 1 to 3 1 or 2 1 or 2
1
0 0 0 0 0
1 2 3
#12
AWG
1 to 6 1 to 5 1 or 2
1 to 4 1 or 2
1
1 to 3 1 or 2
1
2 0 0
1 2
#10
AWG
0 0
0 0
0 1
1 0
#18 AWG
2 to 11 1 to 10
1 to 9 1 to 7 1 to 6 1 to 6 1 to 3 1 or 2
1
1 to 9 1 to 8 1 to 6 1 to 5
0
1 to 8 1 to 6 1 to 4
1 0
1 2 3 4 5 6 7 8
9 10 11 12 13 14
#18
AWG
2 to 9 1 to 8 1 to 7 1 to 6 1 to 6 1 to 6 1 to 4 1 to 3 1 or 3 1 or 2
1 0 0 0
1 to 4 1 to 4 1 to 4 1 to 4 1 to 4 1 to 3 1 or 2
1 0 0 0 0 0 0
1 to 3 1 to 3 1 to 3 1 to 3 1 or 2 1 or 2
1 1 0 0 0 0 0 0
1 0 0 0 0 0 0 0 0 0 0 0 0 0
2 to 14 1 to 13 1 to 12 1 to 11 1 to 10
1 to 9 1 to 8 1 to 7 1 to 6 1 to 5 1 to 4 1 to 3 1 or 2
1
pmpti05.qxd 8/2/02 1:55 PM Page 2