DIRECT BURIAL
COMPRESSION CONNECTORS
C
Panduit Corp. 2015
GCE
INSTALLATION INSTRUCTIONS T-PMPI-289-PC
GCC6X6
GPC
Views using Cable Ties
Post Crimp
PG25
Crimp (1)*
Crimp Tools: CT-920, CT-920CH, CT-2931
CT-940CH/BJO
For full list of crimp tools go too www.panduit.com.
Warning: Do not use with CT-940CH or CT-2940/ST or
damage to crimp tool may result.
Crimping Views
Crimp (2)
LISTED
467
one crimp exceeds:
DB
RATED
CERTIFIED
22.2
Crimp (3)
3 crimps meets
TM
837
Post Crimp
PG25
PG25
*One crimp meets IEEE 837 for part numbers GCE1/0-1/0 and GCE6X61/0-1/0.
**IEEE837 - 2014: GCE500-250 and GCE250-250 for wire to wire terminations larger than 1/0 AWG requires two connectors with 1.5" spacing
between connectors unless connecting to a ground rod or rebar.
For GCC6X6500 and GCC6X6250, compliant when one of the elements is connected to a ground rod or rebar.
*** GCE500-500 is only with 3 crimps
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 2

ANTI-OX
INSTALLATION INSTRUCTIONS T-PMPI-289-PC
Ground Plate Assembly
Connector to be assembled so stud is flush or
protruding from the end of the connector prior
to crimping as shown.
Ground Plate Views
Wall Install
DB
RATED
LISTED
467
Note: Factory installed anti-oxidant may discolor over time, but product performance is not diminished.
Remove all non-conductive material from mating surfaces prior to installation.
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
Page 2 of 2
CERTIFIED
22.2
Meets
TM
837
Floor Install
3/8-16
Threaded Rod
E-mail:
cs@panduit.com
Fax:
708-444-6993
Rev 06