Panduit GACB-3 Installation Manual

GROUNDING AUXILIARY CABLE BRACKET
PART NUMBERS: GACB-2, GACB-3
C
Panduit Corp. 2011
GACB-2 on Wyr-Grid Pathway
1
2
#12-24 Screws (not included)
GACB-2
#12-24 Mounting
Screw
[5.08 N.m]
Wyr-Grid Pathway
GACB-2
INSTALLATION INSTRUCTIONS T-PMPI-299-PC
GACB-3 on Wyr-Grid Pathway
BRACKET MUST REST AGAINST WYR-GRID CROSS-WIRE
BRACKET TEETH MUST MAKE CONTACT WITH WYR-GRID WIRE
BRACKET MUST REST AGAINST WYR-GRID CROSS-WIRE
BRACKET TEETH MUST MAKE CONTACT WITH WYR-GRID WIRE
1
GACB-3
2
#12-24 Mounting
Screw
[5.08 N.m]
Wyr-Grid Pathway
GACB-3
Two Cable Tie Mounting Options (Cable Ties not included)
3
Telecommunications Equipment Bonding Conductors (TEBC)
#6 AWG PRE-TERMINATED JUMPERS
GACBJ68U
GACBJ612U
GACBJ618U
2 Hole, Slotted 1/4" Stud 1/2" - 5/8" Spacing
3
Telecommunications Equipment Bonding Conductors (TEBC)
Use GACBJ618U to bond Wyr-Grid system to ground bar
8" LENGTH
12" LENGTH
18" LENGTH
Paint Piercing Teeth
Use GACBJ618U to bond Wyr-Grid system to ground bar
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 2
C
Panduit Corp. 2011
INSTALLATION INSTRUCTIONS T-PMPI-299-PC
GACB-2 on LADDER RACK
1 1
#12-24 Mounting
Screw
[5.08 N.m]
GACB-2
Ladder Rack
LADDER RACK SPECS.
WIDTH = 3/8" HEIGHT = 1-1/2" - 2" MAX. PAINT THICKNESS = .0040" SOLID OR TUBE
#12-24 Mounting
GACB-3 on LADDER RACK
Ladder Rack
GACB-3
22
Screw
[5.08 N.m]
#12-24 Screws (not included)
Two Cable Tie Mounting Options (Cable Ties not included)
3
TEBC
Bond Sections Together using GACBJ68U, GACBJ612U, OR GACBJ618U
2 Hole, Slotted 1/4" Stud 1/2" - 5/8" Spacing
Paint Piercing Teeth
3
TEBC
Bond Sections Together using GACBJ68U, GACBJ612U, OR GACBJ618U
Use GACBJ618U to bond ladder rack system to ground bar
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
Use GACBJ618U to bond ladder rack system to ground bar
www.panduit.com
Page 2 of 2
E-mail:
cs@panduit.com
Phone:
800-777-3300
Rev 02