Panduit FSWB-C Installation Manual

Page 1
LC Fiber Optic Connectors
ITEM PART NUMBER DESCRIPTION
8 FJPMR Primer 9 FJPXY Anaerobic Adhesive
10
FHSCT (or) FHSCT-W
Heat Shrink Curing Tool (110VAC / 60Hz for 1.6mm/2.0mm installation)
Heat Shrink Curing Tool (230VAC / 50Hz for 1.6mm/2.0mm installation) 11 FKS Aramid Yarn Shears 12 FPP5-L 5µm Polishing Film (Alu
minum Oxide) 13 FPF1-V 1µm Diamond Polishing Film 14 FLCPAD 85 Durometer Polishing Pad 15 FSCDVR Screwdriver 16 FSCOPE 200x Microscope 17 FLCASCP 1.25mm Adapter for FSCOPE 18 FSTY Safety Stickers for fiber scraps 19 FSWB-C Cleaning Swabs 20 FSYR-X Syringes with needle tips 21 FTWZR Tweezers 22 FWP-C Cloth Wipes 23 PFX-0 Indelible Ink Marking Pen 24 FLOUPEX10 Eye Loupe 10X Power 25 -- Isopropyl Alcohol (Reagent Grade, 90% minimum concentration; not avail
able from Panduit) 26 FLCFPLF-X .05µm Lapping Film (For singlemode terminations only) 27 FWBTL Distilled Water Bottle (empty)
-- -- Distilled Water (not available from Panduit)
OPTIONAL PN335* LC Connector Stripping Template
DUPLEX
Duplex Clip
CONNECTOR ASSEMBLY
ITEMS REQUIRED FOR TERMINATION
SIMPLEX
Dust cap
Connector Body
Backbone
Crimp Sleeve
900µm Boot
Jacketed Boot
with heat shrink tubing
Field Polish Termination - Singlemode and Multimode
© Panduit Corp. 2018
READ ALL INSTRUCTIONS COMPLETELY BEFORE PROCEEDING
INSTALLATION INSTRUCTIONS
COMPONENT IDENTIFICATION
FS119A
* denotes stripping template revision letter.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 11
Page 2
© Panduit Corp. 2018
CLASS II LASER
INSTALLATION INSTRUCTIONS
FS119A
TABLE OF CONTENTS Page(s)
Safety Precautions 2 900µm Tight-Buffered Fiber Termination 3-6
1.6mm - 2.0mm Jacketed Cable Termination 7-11
SAFETY PRECAUTIONS
1. SAFETY GLASSES
WARNING: IT IS STRONGLY RECOMMENDED THAT SAFETY GLASSES BE WORN WHEN HANDLING BARE OPTICAL FIBER. THE BARE FIBER IS VERY SHARP AND CAN EASILY DAMAGE THE EYE.
2. ISOPROPYL ALCOHOL
WARNING: ISOPROPYL ALCOHOL IS FLAMMABLE. CONTACT WITH THE ALCOHOL CAN CAUSE IRRITATION TO THE EYES. IN CASE OF CONTACT WITH THE EYES, FLUSH WITH WATER FOR AT LEAST 15 MINUTES. ALWAYS USE ISOPROPYL ALCOHOL WITH PROPER LEVELS OF VENTILATION. IN CASE OF INGESTION, CONSULT A PHYSICIAN IMMEDIATELY.
3. RECOMMENDED ADHESIVE AND PRIMER
WARNING: THE RECOMMENDED ADHESIVE (PANDUIT PART# FJPXY) MAY CONTAIN MALEIC ACID AND METHACRYLIC ESTER. IN CASE OF EYE CONTACT, FLUSH WITH WATER FOR 15 MINUTES AND GET MEDICAL ATTENTION. WASH SKIN AFTER CONTACT. REQUEST M.S.D.S. FOR FURTHER SAFEGUARDS. CHECK “USED BY” DATE ON BOTTLE TO ENSURE BEST PERFORMANCE. WARNING: THE RECOMMENDED PRIMER (PANDUIT PART# FJPMR) MAY CONTAIN ACETONE. THE PRIMER IS HARMFUL IF INHALED OR SWALLOWED. IN CASE OF CONTACT WITH EYES OR SKIN, FLUSH WITH WATER. GET MEDICAL ATTENTION IN CASE OF INGESTION OR CONTACT WITH EYES. DO NOT INDUCE VOMITING. CHECK “USED BY” DATE ON BOTTLE TO ENSURE BEST PERFORMANCE.
4. DISPOSAL OF BARE FIBERS
WARNING: PICK UP AND DISCARD ALL PIECES OF BARE FIBER WITH STICKY TABS. DO NOT LET CUT PIECES OF FIBER STICK TO CLOTHING OR DROP IN THE WORK AREA WHERE THEY ARE HARD TO SEE AND CAN CAUSE INJURY.
5. LASER LIGHT PROTECTION
WARNING: LASER LIGHT IS INVISIBLE. THE INVISIBLE LIGHT IS POWERFUL ENOUGH TO DAMAGE YOUR EYES. SERIOUS DAMAGE TO THE RETINA OF THE EYE IS POSSIBLE. NEVER LOOK INTO THE END OF A FIBER WHICH MAY HAVE A LASER COUPLED TO IT. SHOULD ACCIDENTAL EYE EXPOSURE TO LASER LIGHT BE SUSPECTED, ARRANGE FOR AN EYE EXAMINATION IMMEDIATELY.
6. CABLE HANDLING
WARNING: FIBER OPTIC CABLE CAN BE DAMAGED BY EXCESSIVE PULLING, TWISTING, CRUSHING OR BENDING STRESSES. CONSULT THE APPROPRIATE SPECIFICATION SHEETS AS PROVIDED BY YOUR CABLE VENDOR. ANY DAMAGE MAY DECREASE OPTICAL PERFORMANCE.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 11
Page 3
© Panduit Corp. 2018
ADHESIVE
1.1
1/4" (6.4mm) MAX
2.3
3.1
900µm TIGHT-BUFFERED STRIPPING DIMENSIONS
IMPORTANT! Due to printing variations, use a rigid
Panduit laminated template.
scale for stripping dimensions, or the appropriate
2.2
2.1
INSTALLATION INSTRUCTIONS
900µm Tight-Buffered Fiber Termination
1. PREPARING ADHESIVE AND PRIMER
1.1 Remove the plunger from a syringe. Squeeze about 0.5ml of FJPXY Anaerobic Adhesive into the back of the syringe barrel. Insert the plunger. Point opening upward, and squeeze any air out of the barrel. Attach needle to syringe. Adhesive that is stored in a syringe may start to harden within 24 hours.
2. STRIPPING 900µm TIGHT-BUFFERED FIBER
2.1 Insert the fiber end through the small end of the 900µm boot. Slide the boot back out of the way.
2.2 Following the stripping dimensions, use the marking pen to place a mark .53" (13.5mm) from the end of the buffer.
2.3 With the fiber buffer stripper provided, strip the buffer.
FS119A
BUFFER STRIPPING GUIDELINES:
• Panduit recommends that you remove no more than 1/4" (6.4mm) of buffer at a time to avoid breaking the fiber. Refer to cable manufacturer's buffer stripping guidelines for specific recommendations.
• Hold the buffer stripper such that the arrow on the tool points in the direction of buffer removal.
• Noting the location of the tool's blades, position the fiber in the tool's V-notches. Squeeze the handles firmly, and pull tool in the direction of the arrow on the tool.
• Clean the buffer stripper blades after each strip by holding the handles open, pulling the casings back away from the blades, and letting them snap back against the blades.
3. ATTACHING FERRULE TO 900µm TIGHT-BUFFERED FIBER
Instructions intended for anaerobic adhesive only.
3.1 Clean the bare fiber using an alcohol (90% minimum concentration) soaked lint-free wipe. The fibers should be free of all coating and residue. Insert fiber without adhesive or primer into ferrule assembly to ensure a proper fit and to remove any debris which may be blocking the ferrule hole. Remove fiber, clean fiber again, and proceed to the next step.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 11
Page 4
© Panduit Corp. 2018
3.5
1. SCORE
2. PULL FIBER
4.1
4.1
Adhesive Bead
3.4
INSTALLATION INSTRUCTIONS
3.2 Apply primer onto the bare fiber with the brush from the primer bottle, and onto the first 1/8" (3.2 mm) of the buffer next to the
exposed fiber. Set fiber aside such that it will not collect debris while completing the next three steps.
3.3 Insert the needle of the adhesive filled syringe into the rear of the connector assembly until the needle bottoms against the rear of the ferrule.
3.4 While pressing the needle firmly against the rear of the ferrule, gently apply pressure on the plunger until a small bead of adhesive forms on the front tip of the ferrule. Wait 3 seconds before removing the needle from the ferrule assembly.
3.5 Carefully but quickly insert the bare fiber through the ferrule in a smooth forward motion. The fiber is fully inserted when the
buffer bottoms against the rear of the ferrule. The adhesive will begin to set within seconds.
Note: If adhesive oozes out the back of the assembly, you have injected too much. It is critical to the function of the connector that you wipe away all excess adhesive.
3.6 Allow one minute for the adhesive to harden before cleaving.
3.7 Clean the needle using a dry lint-free wipe. The needle should be free of any excess adhesive before preparing the next connector.
FS119A
4. CLEAVING 900µm TIGHT-BUFFERED FIBER
4.1 Using a carbide scribe to cleave, gently make one small score mark across the bare fiber just above the endface of the ferrule. Pull the fiber away from the ferrule and discard it on one of the sticky tabs provided. A short stub of fiber will protrude from the tip of the ferrule when viewed through the FLOUPEX10 Eye Loupe.
4.2 Clean the carbide blade and fingers using a dry lint-free wipe. This will prevent contamination of the connector during polish­ing and final assembly.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 11
Page 5
© Panduit Corp. 2018
3-4
WET
1µm
5.4
D
I
A
M
O
N
D
5.2
Polishing Puck with LC Adapter
Design prior to Design after July, July, 2018 2018
5.1
5µm
Ferrule Tip After 1µm Diamond Polish
AB CD
A = Ideal. No blemishes on core or cladding.
B = Good. Cladding is chipped, but core is not.
C = Poor. Scratch across core. Try repolishing
or else reterminate.
D = Unacceptable. Fiber has shattered.
Reterminate.
5.5
INSTALLATION INSTRUCTIONS
5. POLISHING 900µm TIGHT-BUFFERED FIBER
Carefully read this entire section before proceeding.
POLISHING GUIDELINES
• Keep the puck flat against the polishing film.
• Figure eights should be about 3" tall and 1.5" wide.
• Always polish on a clean area of the 1µm diamond polishing film, with figure eights traversing the film as shown in Figure 5.4.
• One sheet of 5µm (micron) polishing film will polish 2-4 ferrules.
• One sheet of 1µm diamond polishing film will polish 100 ferrules.
• One sheet of .05µm lapping film will polish approximately 18-20 ferrules.
• Clean the polishing puck and pad with a clean wipe moistened with alcohol after each step.
• DO NOT OVERPOLISH.
5.1 Hold a piece of 5µm Aluminum Oxide polishing film in the air and gently rub cleaved fiber stub against the film. Using a circular motion, continue rubbing until the end of the fiber is even with the end of the ferrule or adhesive bead. An indication of this is when the stub no longer leaves white traces on the film.
Note: Make sure to hold film so that your fingers are supporting the edges only and are not positioned directly behind fiber.
5.2 Thoroughly clean polishing puck and 85 durometer polishing pad using an alcohol soaked wipe. Place a sheet of 1µm diamond polishing film on the pad. Wet film by placing a quarter­sized amount of distilled water in the center of the pad.
5.3 Carefully insert connector into the polishing puck until the connector latches. Insure that the ferrule is protruding from the hole in the underside of the puck. It may be necessary to unlatch and reinsert the connector if the ferrule does not slide through initially.
5.4 Place the puck in the center of the distilled water on the pad. Keeping the puck flat against the film and pad, apply even pressure and polish by making figure eight motions. Continue for 3-4 figure eights.
5.5 Turn the puck over and inspect for any remaining adhesive, indicated by a dark color at the center of the ferrule. Repeat step
5.4 for 1-2 figure eights if adhesive is still present, then reinspect.
5.6 Clean the ferrule tip and puck with an alcohol soaked lint-free wipe. Clean the 1µm diamond polishing film using an alcohol soaked wipe after every 5 connectors.
5.7 Inspect the fiber endface using a microscope. If scratches remain, polish for an additional 1-2 figure eights on the 1µm diamond film and reinspect.
WARNING: NEVER LOOK INTO THE END OF A FIBER WHICH MAY HAVE A LASER COUPLED TO IT.
Note: Each time a mating takes place, clean the ferrule endface thoroughly with an alcohol soaked lint-free wipe.
5.8 For singlemode only: Place a sheet of the .05µm lapping film on the pad. Apply several drops of distilled water onto the center of the film.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 5 of 11
FS119A
Page 6
© Panduit Corp. 2018
0.625”
(16mm)
WET
5.10
.
0
5
µ
m
L
A
P
P
I
N
G
F
I
L
M
7.1
7.2
6.1
Boot against flange
INSTALLATION INSTRUCTIONS
5.9 For singlemode only: Place the puck in the center of the distilled water on the film and pad. Keeping the puck flat against the film and pad, apply even pressure and ONE TIME ONLY drag the puck in a straight line 0.625" (16mm).
CAUTION: Do not exceed 0.625" (16mm) to avoid fiber undercut
5.10 For singlemode only: Wipe the ferrule tip, pad and puck with a dry wipe.
5.11 For singlemode only: Clean the ferrule with a distilled water soaked wipe. Do not use alcohol to clean after using the .05µm lapping film.
5.12 Place a dust cap over the ferrule assembly.
6. ASSEMBLING CONNECTOR AND BOOT
FS119A
6.1 Push the boot forward onto the grooved area of the backbone until it is against the flange.
7. ATTACHING DUPLEX CLIP
7.1 With a connector held as shown (latch on top, ferrule facing away), insert the connector into one side of the duplex clip as shown (clip held with the ‘A->B’ polarity marking upright and facing forward). The upper tab of the clip should slide into the pocket underneath the latch of the connector, and the lower tab should slide under the connector housing and “snap”, locking it into place.
7.2 Repeat this procedure for the other connector, completing the duplexing step.
Note: When making cable assemblies, be sure to follow the correct ‘A->B’ polarity cross-over between connectors.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 6 of 11
Page 7
© Panduit Corp. 2018
1.6mm - 2.0mm JACKETED CABLE STRIPPING DIMENSIONS
IMPORTANT! Due to printing variations, use a rigid scale for stripping dimensions, or the appropriate Panduit laminated template.
2.3
2.4
2.5
2.6
2.3
2.2
Heat Shrink
2.1
1.1.1
ADHESIVE
1.1
INSTALLATION INSTRUCTIONS
1.6mm - 2.0mm Jacketed Cable Termination
1. PREPARING ADHESIVE AND PRIMER
1.1 Remove the plunger from a syringe. Squeeze about 0.5ml of FJPXY Anaerobic Adhesive into the back of the syringe barrel. Insert the plunger. Point opening upward, and squeeze any air out of the barrel. Attach needle to syringe. Adhesive that is stored in a syringe may start to harden within 24 hours.
2. STRIPPING 1.6mm - 2.0mm JACKETED CABLE
2.1 If using duplex cable, split the two cables approximately 6" (152mm) or as needed.
2.2 Insert cable through the small end of the jacketed boot first, then through the heat shrink side of the crimp sleeve. Slide both back out of the way.
2.3 Following the stripping dimensions, use the marking pen to mark each cable 1.14" (29mm) and 1.46" (37mm) from the end.
2.4 Strip off the cable at the aramid yarn cut mark. To reduce wear on the jacket stripper blades, do not slide the blades along the aramid yarn. Instead, use the tool to cut through the jacket, then pull off the jacket by hand. For 1.6mm - 2.0mm jacketed fiber, use the first hole (marked “.8MM” or #20AWG) from the tip of the jacket stripper.
2.5 Cut aramid yarn flush with the end of the jacket.
2.6 Strip off the cable at the jacket strip mark. Mark the buffer .93" (23.5mm) from the new jacket edge.
FS119A
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 7 of 11
Page 8
© Panduit Corp. 2018
3.5
Gap
Adhesive Bead
3.4
3.1
1/4" (6.4mm) MAX
2.7
2.7
1.6mm - 2.0mm JACKETED CABLE STRIPPING DIMENSIONS (cont.)
INSTALLATION INSTRUCTIONS
FS119A
2.7 Using the provided buffer stripper tool, carefully remove the buffer exposing the bare fiber.
BUFFER STRIPPING GUIDELINES:
• Panduit recommends that you remove no more than 1/4" (6.4mm) of buffer at a time to avoid breaking the fiber. Refer to cable manufacturer's buffer stripping guidelines for specific recommendations.
• Hold the buffer stripper such that the arrow on the tool points in the direction of buffer removal.
• Noting the location of the tool's blades, position the fiber in the tool's V-notches. Squeeze the handles firmly, and pull tool in the direction of the arrow on the tool.
• Clean the buffer stripper blades after each strip by holding the handles open, pulling the casings back away from the blades, and letting them snap back against the blades.
3. ATTACHING FERRULE TO 1.6mm - 2.0mm JACKETED CABLE
Instructions intended for anaerobic adhesive only.
3.1 Clean the bare fiber using an alcohol (90% minimum concen- tration) soaked lint-free wipe. The fibers should be free of all coating and residue. Insert fiber without adhesive or primer into ferrule assembly to ensure a proper fit and to remove any debris which may be blocking the ferrule hole. Remove fiber, clean fiber again, and proceed to the next step.
3.2 Apply primer onto the bare fiber with the brush from the primer bottle, and onto the first 1/8" (3.2 mm) of the buffer next to the exposed fiber. Set fiber aside such that it will not collect debris while completing the next three steps.
3.3 Insert the needle of the adhesive filled syringe into the rear of the connector assembly until it bottoms against the ferrule.
3.4 While pressing the needle firmly against the rear of the ferrule, gently apply pressure on the plunger until a small bead of adhesive forms on the front tip of the ferrule. Wait 3 seconds before removing the needle from the ferrule assembly.
3.5 In a smooth motion, carefully insert fiber into the connector assembly and through the ferrule. The fiber is fully inserted when the buffer bottoms against the ferrule. There will be a slight gap between the cable jacket and the backbone. Do NOT force the jacket up against the backbone. The adhesive will begin to set within seconds.
Note: If adhesive oozes out the back of the assembly, you have injected too much. It is critical to the function of the connector that you wipe away all excess adhesive.
3.6 Allow one minute for the adhesive to harden before cleaving.
3.7 Clean the needle using a dry lint-free wipe. The needle should be free of any excess adhesive before preparing the next connector.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 8 of 11
Page 9
© Panduit Corp. 2018
5.1
1. SCORE
2. PULL FIBER
5.1
4.4
B
A
Crimp die
pocket B
4.2
4.1
Flare aramid
yarn evenly
Gap
INSTALLATION INSTRUCTIONS
4. CRIMPING 1.6mm - 2.0mm JACKETED CABLE
Note: Be careful not to break the bare fiber protruding from the ferrule during this step.
4.1 Flare the aramid yarn evenly around the perimeter of the grooved area of the backbone of the ferrule assembly. Use tweezers for best results. There will be a slight gap between the cable jacket and the backbone.
4.2 Slide the crimp sleeve over the backbone, trapping the aramid yarn between the crimp sleeve and the grooved area of the backbone.
4.3 Align the front edge of the crimp sleeve with the front edge of the crimp die pocket B.
Note: The front edge of the crimp die pocket is the side with the ribs.
4.4 Making sure the crimp sleeve is seated against the backbone, crimp the crimp sleeve.
FS119A
5. CLEAVING 1.6mm - 2.0mm JACKETED CABLE
5.1 Using a carbide scribe to cleave, gently make one small score mark across the bare fiber just above the endface of the ferrule. Pull the fiber away from the ferrule and discard it on one of the sticky tabs provided. A short stub of fiber will protrude from the tip of the ferrule when viewed through the FLOUPEX10 Eye Loupe.
5.2 Clean the carbide blade and fingers using a dry lint-free wipe. This will prevent contamination of the connector during polish­ing and final assembly.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 9 of 11
Page 10
© Panduit Corp. 2018
3-4
WET
1µm
6.4
D
I
A
M
O
N
D
6.2
Polishing Puck with LC Adapter
Design prior to Design after July, July, 2018 2018
6.1
5µm
Ferrule Tip After 1µm Diamond Polish
AB CD
A = Ideal. No blemishes on core or cladding.
B = Good. Cladding is chipped, but core is not.
C = Poor. Scratch across core. Try repolishing
or else reterminate.
D = Unacceptable. Fiber has shattered.
Reterminate.
6.5
INSTALLATION INSTRUCTIONS
6. POLISHING 1.6mm - 2.0mm JACKETED CABLE
Carefully read this entire section before proceeding.
POLISHING GUIDELINES
• Keep the puck flat against the polishing film.
• Figure eights should be about 3" tall and 1.5" wide.
• Always polish on a clean area of the 1µm diamond polishing film, with figure eights traversing the film as shown in Figure 6.4.
• One sheet of 5µm (micron) polishing film will polish 2-4 ferrules.
• One sheet of 1µm diamond polishing film will polish 100 ferrules.
• One sheet of .05µm lapping film will polish approximately 18-20 ferrules.
• Clean the polishing puck and pad with a clean wipe moistened with alcohol after each step.
• DO NOT OVERPOLISH.
6.1 Hold a piece of 5µm Aluminum Oxide polishing film in the air and gently rub cleaved fiber stub against the film. Using a circular motion, continue rubbing until the end of the fiber is even with the end of the ferrule or adhesive bead. An indication of this is when the stub no longer leaves white traces on the film.
Note: Make sure to hold film so that your fingers are supporting the edges only and are not positioned directly behind fiber.
6.2 Thoroughly clean polishing puck and 85 durometer polishing pad using an alcohol soaked wipe. Place a sheet of 1µm diamond polishing film on the pad. Wet film by placing a quarter­sized amount of distilled water in the center of the pad.
6.3 Carefully insert connector into the polishing puck until the connector latches. Insure that the ferrule is protruding from the hole in the underside of the puck. It may be necessary to unlatch and reinsert the connector if the ferrule does not slide through initially.
6.4 Place the puck in the center of the distilled water on the pad. Keeping the puck flat against the film and pad, apply even pressure and polish by making figure eight motions. Continue for 3-4 figure eights.
6.5 Turn the puck over and inspect for any remaining adhesive, indicated by a dark color at the center of the ferrule. Repeat step
6.4 for 1-2 figure eights if adhesive is still present, then reinspect.
6.6 Clean the ferrule tip and puck with an alcohol soaked lint-free wipe. Clean the 1µm diamond polishing film using an alcohol soaked wipe after every 5 connectors.
6.7 Inspect the fiber endface using a microscope. If scratches remain, polish for an additional 1-2 figure eights on the 1µm diamond film and reinspect.
WARNING: NEVER LOOK INTO THE END OF A FIBER WHICH MAY HAVE A LASER COUPLED TO IT.
Note: Each time a mating takes place, clean the ferrule endface thoroughly with an alcohol soaked lint-free wipe.
6.8 For singlemode only: Place a sheet of the .05µm lapping film on the pad. Apply several drops of distilled water onto the center of the film.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 10 of 11
FS119A
Page 11
© Panduit Corp. 2018
7.2
7.3
8.1
Boot against
flange
9.1
9.2
0.625”
(16mm)
WET
6.10
.
0
5
µ
m
L
A
P
P
I
N
G
F
I
L
M
INSTALLATION INSTRUCTIONS
6.9 For singlemode only: Place the puck in the center of the
distilled water on the film and pad. Keeping the puck flat against the film and pad, apply even pressure and ONE TIME ONLY drag the puck in a straight line 0.625" (16mm).
CAUTION: Do not exceed 0.625" (16mm) to avoid fiber undercut
6.10 For singlemode only: Wipe the ferrule tip, pad and puck with a
dry wipe.
6.11 For singlemode only: Clean the ferrule with a distilled water
soaked wipe. Do not use alcohol to clean after using the .05µm lapping film.
6.12 Place a dust cap over the ferrule assembly.
7. CURING HEAT SHRINK TUBING
7.1 Turn the heat adjustment knob so the white line is centered in
the notch.
7.2 Turn heat shrink curing tool “on”. (The temperature of the hot
air stream at the nozzle should be 220°F - 240°F)
7.3 Hold onto the connector.
7.4 Bring the heat shrink tubing into the hot air stream. Hold the
heat shrink tubing about 1/2" away from the nozzle. Rotate the connector for 20-30 seconds so that the heat shrink tubing is completely cured onto the jacket.
7.5 Remove the connector from the hot air stream.
7.6 Turn heat shrink curing tool “off”.
FS119A
8. ASSEMBLING CONNECTOR AND BOOT
8.1 Slide the boot over the crimp sleeve and onto the backbone.
Push the boot over the flange towards the shoulder. The boot should snap in place onto the flange.
9. ATTACHING DUPLEX CLIP
9.1 With a connector held as shown (latch on top, ferrule facing
away), insert the connector into one side of the duplex clip as shown (clip held with the ‘A->B’ polarity marking upright and facing forward). The upper tab of the clip should slide into the pocket underneath the latch of the connector, and the lower tab should slide under the connector housing and “snap”, lock­ing it into place.
9.2 Repeat this procedure for the other connector, completing the
duplexing step.
Note: When making cable assemblies, be sure to follow the correct ‘A->B’ polarity cross-over between connectors.
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
Page 11 of 11
E-mail:
techsupport@panduit.com
Phone:
866-405-6654
Loading...