Opticom Rack Mount Fiber Enclosures
Part Numbers: FRME3, FRME4
© Panduit Corp. 2014
FRME3
1 FRME Enclosure
1 FRME Kit
1 Port I.D. Label
2 Enclosure Brackets
INSTALLATION INSTRUCTIONS
Assembly Instructions:
Determine the cable entry location on the enclosure. Remove the knockout
by inserting a screwdriver into the slot located in the center of the knockout
and apply a twisting upward motion, then lift out. Insert grommet following
proper cutting diagram. Snap in saddle clips. Grounding lug attaches to a
stud at the rear, inside the enclosure, on the top or bottom with a #10-32
nut. Apply laser warning label and caution label in a clearly visible location.
Apply port I.D. label(s) on the inside of the door.
FRME4
1 FRME Enclosure
1 FRME Kit
1 Port I.D. Label
2 Enclosure Brackets
GROMMET CUTTING DIAGRAM
Cut the small
circle for 1"
diameter
innerduct
Cut the large
circle for 1-1/2"
diameter
innerduct
FS097
Cut the straight
lines when not
using any
innerduct
Caution Label
Saddle Clip
Port I.D. Label
For Technical Support: www.panduit.com/resources/install_maintain.asp
Laser Warning Label
Grounding Lug
Grommet
Mounting Bracket
Page 1 of 2

© Panduit Corp. 2014
Mounting Instructions
INSTALLATION INSTRUCTIONS
Attach strain relief clip with the #10-32 screw and nut
provided.
FS097
Bracket orientation for 23 inch rack Bracket orientation for flush mount on a 19
inch rack
Attach the short leg of the bracket to
the enclosure.
Locate rack bracket on the front mounting
holes for flush mounting
Label Installation
Bracket orientation for projection mount on
a 19 inch rack
Locate rack bracket on the mid enclosure
mounting holes for projection mounting
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
Page 2 of 2