Panduit FRME1 Installation Manual

Page 1
Opticom Fiber Optic Rack Mount Enclosure
Part Number: FRME1
© Panduit Corp. 2011
INSTALLATION INSTRUCTIONS
FRME1
Assembly Instructions
Determine the cable entry location on the enclosure. Remove the knockout by inserting a screwdriver into the slot located in the center of the knockout and apply a twisting downward motion then lift out. Insert grommet following proper cutting diagram. Grounding Lug attaches to a stud at the rear, inside the enclosure on the top or bottom with a #10-32 nut. Apply Laser Warning Label and Caution Label in a clearly visible location. Apply Port I.D. Label(s) on the inside of the tray.
Contents:
(1) FRME Kit
GROMMET CUTTING DIAGRAM
Cut the small circle for 1" diameter innerduct
FRME Kit Contents: (1) Grounding Lug (2) Cable Ties (1) #10-32 x 3/8" Screw (1) #10-32 x 1/4" Screw (4) #12-24 x 1/2" Screws (4) M6 x 1.0 x 15MM Screws (1) Fiber Caution Label (1) Fiber Laser Warning Label (2) Grommets (2) #10-32 Hex Nuts (1) Strain Relief Clip
Cut the large circle for 1-1/2" diameter innerduct
Cut the straight lines when not using any innerduct
FS024
Fiber Caution Label
Spool
Port I.D. Label
Fiber Laser Warning Label
Grounding Lug
Grommet
Bracket
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 2
Page 2
© Panduit Corp. 2011
INSTALLATION INSTRUCTIONS
Attach Strain Relief Clip with the #10-32 screw and nut provided.
FS024
Bracket orientation for 23 inch rack
Attach the short leg of the bracket to the enclosure.
To remove the rear door, deflect the release tab and slide the door off its hinge.
Bracket orientation for projection mount on a 19 inch rack
Locate rack bracket on the mid enclosure mounting holes for projection mounting
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
Page 2 of 2
E-mail:
techsupport@panduit.com
Phone:
866-405-6654