Fiber optic cable is sensitive to excessive pulling, bending and crushing forces. Consult the manufacturer’s cable specification
sheet for the specific cable in use.
Follow TIA/EIA-568-A, 569, 606, and 607 installation guidelines where applicable.
WARNING: UNMATED CONNECTORS MAY EMIT INVISIBLE LASER RADIATION. DO NOT LOOK DIRECTLY INTO THE
END OF THE CONNECTOR. DO NOT INSPECT WITH MAGNIFYING DEVICES. MAINTAIN CAP ON UNMATED
CONNECTORS.
Care should be taken when opening and closing fully loaded drawer in order to protect fiber components.
FS001B
FOSMF
Splice Tray Base
Splice Holder - Fusion (FOSMF)
900µm tight buffered fiber
retention fingers
Splice Tray Cover
Hinge
Sub-unit tube
retention bridge
Figure 1
For Technical Support: www.panduit.com/resources/install_maintain.asp
Note: Opposite corner
from trunk cable entry
should be broken along
score line.
24 splices max for FOSMF
12 splices max for FOSMM
To FAPs
Trunk cable
from source
60mm or 45mm fusion
splice protector
sleeves for FOSMF.
4.0mm square (max.)
mechanical splice
housing for FOSMM
12-fiber
sub-unit
tube x 2
Typical cable routing for FOSMF or FOSMM
Route sub-unit tube(s) through retention bridge
as shown. Route 900µm buffered fiber from the
trunk cable and splice to pigtail. Use enough
cable length, approximately 1.2m (47") to ensure
one complete loop of individual fibers around
FOSM slack spools.
Pigtails leading to FAPs should be a minimum of
1m (39.4").
Figure 3
2.0"
1-1/4" heat
Approx.
shrink
tubing
Individual 900µm
buffered fibers
1.2m (47") minimum
length
Figure 4
For Technical Support: www.panduit.com/resources/install_maintain.asp
FCE1U, FCE1UA and FCE2U Fiber Optic Splice Module Installation
FOSM (4) capacity for FCE1U, FCE1UA
(8) capacity for FCE2U
FAPs (4) capacity for FCE1U, FCE1UA
(8) capacity for FCE2U
Break off FOSM latch
on top module only.
FOSMH1U
(FOSMH2U)
support
brackets
Figure 5A
Place “L” shape support brackets over #10-32
studs on sliding tray, note orientation. Place first
FOSM on top of “L” shape support brackets,
note orientation and secure with #10-32 hex nut.
Remaining FOSMs are stacked on top of each
other and snap in place after termination of
lower tray.
If 4 FOSMs are to be installed in the FCE1U or
FCE1UA, side latches on top module must be
broken off to close enclosure drawer.
Position FAPs between upright flanges as
shown. Once mounted, fully seat NyLatches to
secure FAPs.
FS001B
Isometric view showing drawer
fully extended and tilted down.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Fully extend drawer to ensure proper amount of
slack is used.
Finish splicing in each FOSM before adding or
stacking subsequent FOSMs.
Place FOSM holder over #10-32 studs on
sliding tray, note orientation, secure with
#10-32 hex nut. Place first FOSM on top of
FOSM Holder, note orientation. Remaining
FOSMs are stacked on top of each other
and snap in place after termination of lower
tray.
Position FAPs between upright flanges as
shown. Once mounted, fully seat
NyLatches to secure FAPs.
Fully extend tray to ensure proper amount
of slack is used.
Finish splicing in each FOSM before
adding/stacking subsequent FOSMs.
FOSM Holder
(P/N FOSMH4U)
FAPs
(12) capacity
Isometric view showing tray fully
open and tilted down (cables
omitted for clarity).
Figure 6
For Technical Support: www.panduit.com/resources/install_maintain.asp
FRME1U and FRME2U Fiber Optic Splice Module Installation
FOSM (3) capacity for FRME1U
(6) capacity for FRME2U
FAPs (3) capacity for FRME1U
(6) capacity for FRME2U
Break off FOSM latch
on top module only.
Figure 7
FS001B
Place first FOSM over #10-32 studs on sliding
tray, and secure with #10-32 hex nut.
Remaining FOSMs are stacked on top of
each other and snap in place after
termination of lower tray.
Position FAPs between upright flanges as
shown. Once mounted, fully seat NyLatches
to secure FAPs.
FMT1 and FMT2 Fiber Optic Splice Module Installation
FOSM (4) capacity for FMT1
(8) capacity for FMT2
FAPs (4) capacity for FMT1
(8) capacity for FMT2
Figure 8
To remove top cover (not shown), remove
screw at rear of enclosure, slide cover back
and off.
Utilizing double stick tape on underside, place
first FOSM into tray. Remaining FOSMs are
stacked on top of each other and snap in
place after termination of lower tray.
If 4 FOSMs are to be installed in the FMT1
side latches on top module must be broken
off to close enclosure drawer.
Position FAPs between upright flanges as
shown. Once mounted, fully seat NyLatches
to secure FAPs.
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com