Panduit FMD1, FMD2, FMT2, FMT1 Installation Instructions Manual

Page 1
Opticom Drawers and Trays
© Panduit Corp. 2014
INSTALLATION INSTRUCTIONS
FS067
FMD1 FMD2 FMT1 FMT2
Contents:
1 - Enclosure
3 - #10 Flat Washers
10 - Pan-Ty Cable Ties
2 - Adhesive Mounts
2 - Bend Radias Brackets
(For part numbers FMD1 and FMD2 ONLY)
CAUTION:
Fiber optic cable is sensitive to excessive pulling, bending and crushing forces. Consult the manufacturer’s cable specification sheet for the specific cable in use.
Follow TIA/EIA 568-A, 569, 606, and 607 installation guidelines where applicable.
DANGER: UNMATED CONNECTORS MAY EMIT INVISIBLE LASER RADIATION. DO NOT LOOK DIRECTLY INTO THE END OF THE CONNECTOR, DO NOT INSPECT WITH MAGNIFYING DEVICES. MAINTAIN CAP ON UNMATED CONNECTORS.
4 - #12-24 x 1/2" screws
1 - #10-32 x 5/16" screw
4 - #10-32 Hex Nuts
1 - Strain Relief Bracket
1 - Port Identification Label
(For part numbers FMD1 and FMD2 ONLY)
1 - Caution Label
1 - Laser Warning Label
2 - Spools
1 - 24" Spiral Wrap
(For part numbers FMD1 and FMD2 ONLY)
ASSEMBLY
(FMD2 shown)
Port identification label
Enclosure
Caution label
Bend radius bracket
Laser warning label
#10-32 x 5/16" screw
Strain relief bracket
Spool
Grommet
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 4
Page 2
© Panduit Corp. 2014
Cut the small circle for 1" diameter innerduct
Cut the large circle for 1-1/2" diameter innerduct
Cut the straight lines when not using any innerduct
DISCARD
DISCARD
INSTALLATION INSTRUCTIONS
To engage the cover, slide forward until the cover slides under the front tabs then secure in place with #10-32 screw.
Determine which grommet(s) will be used to bring the cable into the enclosure. Remove the knock-out at entry location of the fiber tray. Install grommet following the proper cutting diagram.
FS067
Place the strain relief bracket near area where the cable will enter the enclosure. Fasten with #10-32 hex nut.
Determine where the spools will be located. Remove the liner from the tape on each spool and place them inside the enclosure.
Install the hex nut and washer. This will be used to secure the strength member that comes out of the cable.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 4
Page 3
© Panduit Corp. 2014
1
2
To remove the bend radius bracket, disengage latch with a screwdriver.
Slot
INSTALLATION INSTRUCTIONS
Mount the enclosure to the rack using (4) #12-24 screws.
FS067
Secure the sliding tray with #10 washers and #10-32 hex nuts provided.
To install the bend radius brackets, slide the bracket onto tab with the slot facing outside then snap in place. (FMD SERIES ONLY)
Insert cable through the grommet. Secure the cable to the strain relief bracket using a cable tie. Strip 1 meter of jacket from the end of the cable. Attach the strength member of the cable to the #10-32 stud and #10-32 hex nut. Use the adhesive mount and cable tie to secure the cable between the#10-32 stud and the grommet.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 4
Page 4
© Panduit Corp. 2014
INSTALLATION INSTRUCTIONS
Insert the panels into the enclosure as shown. Once mounted, push the latches in to secure the panel.
Terminate the fibers with an appropriate connector. Mount each connector in the panel.
FS067
Gently loop the excess fiber around the spools. Replace the cover after all fibers are looped around the spools
Install the patchcords as needed.
To remove the front door: (FMD SERIES ONLY)
Attach Laser Warning Label and Caution Label where they are clearly visible.
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
Page 4 of 4