OPTICOM Furcation Kit
Part Numbers: FK2BJ, FK4BJ
© Panduit Corp. 2006
INSTALLATION INSTRUCTIONS PN155B
CONTENTS
FK2BJ
INCLUDES: TWO 1-METER FURCATION
TUBES AND ONE 3” X1/4” DIAMETER
HEAT SHRINK TUBE
OR
FK4BJ
INCLUDES: FOUR 1-METER FURCATION TUBES AND
ONE 3” X3/8” DIAMETER HEAT SHRINK TUBE
PRECAUTIONS
1. SAFETY GLASSES
WARNING: It is strongly recommended that
safety glasses be worn when handling bare
optical fiber. The bare fiber is very sharp and
can easily damage the eye.
2. DISPOSAL OF BARE FIBERS
WARNING: Pick up and discard all pieces of
bare fiber with sticky tabs. Do not let cut pieces
of fiber stick to clothing or drop in the work
area where they are hard to see and can
cause injury.
3. LASER LIGHT PROTECTION
WARNING: Laser light is invisible. The invisible light is powerful enough to damage your
eyes. Serious damage to the retina of the eye
is possible. Never look into the end of a fiber
which may have a laser coupled into it. Should
accidental eye exposure to laser light be suspected, arrange for an eye examination immediately.
4. CABLE HANDLING
WARNING: Fiber optic cable can be damaged
by excessive pulling, twisting, crushing or
bending stresses. Consult the appropriate
specification sheets as provided by your cable
vendor. Any damage may result in decreased
optical performance.
TOOLS
CABLE JACKET
STRIPPER (CST-115)
ARAMID YARN
CUTTER (FKC)
HEAT GUN
(HSG-115V-300)
MARKING PEN
(PFX-0)
UTILITY KNIFE
TAPE MEASURE
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 4

1
2
3
INSTALLATION INSTRUCTIONS PN155B
HEAT SHRINK TUBE
MULTIFIBER CABLE
MULTIFIBER CABLE
41.4 in (105cm) Maximum
4
5
0.5in (12.7mm)
FURCATION TUBING
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 4
0.5in (12.7mm)
BUFFERED FIBERS
COMBINED LENGTH OF BUFFER
AND FIBER REQUIRED FOR THE
CONNECTOR. (SEE CONNECTOR
INSTALLATION INSTRUCTIONS)
DRAW AN X ON THIS SECTION
(THIS WILL BE CUT OFF)
MARK ALL FURCATION TUBES
THAT WILL BE NEEDED

6
7
INSTALLATION INSTRUCTIONS PN155B
CUT FURCATION
TUBING TO SIZE
FURCATION TUBING
STRIP OUTER JACKET
8
9
CUT INNER TUBE FLUSH
WITH EACH END OF JACKET
SLIDE FURCATION TUBING OVER THE BUFFERED FIBERS
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 4

INSTALLATION INSTRUCTIONS PN155B
10
OVERLAP STRENGTH MEMBERS AND SLIDE
HEAT SHRINK TUBING FORWARD,
CENTERED OVER THE SPLICE
11
TERMINATE WITH AN
APPROPRIATE CONNECTOR
BUFFERED FIBERS
12
250o F (121o C)
EVENLY HEAT THE TUBING UNTIL
IT HAS FULLY RECOVERED AND
CONFORMS TO THE CABLES.
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
Page 4 of 4