Panduit FK2BJ, FK4BJ Installation Instructions Manual

Page 1
OPTICOM Furcation Kit
Part Numbers: FK2BJ, FK4BJ
© Panduit Corp. 2006
INSTALLATION INSTRUCTIONS PN155B
CONTENTS
FK2BJ
INCLUDES: TWO 1-METER FURCATION
TUBES AND ONE 3” X1/4” DIAMETER
HEAT SHRINK TUBE
OR
FK4BJ
INCLUDES: FOUR 1-METER FURCATION TUBES AND
PRECAUTIONS
1. SAFETY GLASSES
WARNING: It is strongly recommended that safety glasses be worn when handling bare optical fiber. The bare fiber is very sharp and can easily damage the eye.
2. DISPOSAL OF BARE FIBERS
WARNING: Pick up and discard all pieces of bare fiber with sticky tabs. Do not let cut pieces of fiber stick to clothing or drop in the work area where they are hard to see and can cause injury.
3. LASER LIGHT PROTECTION
WARNING: Laser light is invisible. The invisi­ble light is powerful enough to damage your eyes. Serious damage to the retina of the eye is possible. Never look into the end of a fiber which may have a laser coupled into it. Should accidental eye exposure to laser light be sus­pected, arrange for an eye examination imme­diately.
4. CABLE HANDLING
WARNING: Fiber optic cable can be damaged by excessive pulling, twisting, crushing or bending stresses. Consult the appropriate specification sheets as provided by your cable vendor. Any damage may result in decreased optical performance.
TOOLS
CABLE JACKET STRIPPER (CST-115)
ARAMID YARN CUTTER (FKC)
HEAT GUN (HSG-115V-300)
MARKING PEN (PFX-0)
UTILITY KNIFE
TAPE MEASURE
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 4
Page 2
1
2
3
INSTALLATION INSTRUCTIONS PN155B
HEAT SHRINK TUBE
MULTIFIBER CABLE
MULTIFIBER CABLE
41.4 in (105cm) Maximum
4
5
0.5in (12.7mm)
FURCATION TUBING
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 4
0.5in (12.7mm)
BUFFERED FIBERS
COMBINED LENGTH OF BUFFER AND FIBER REQUIRED FOR THE CONNECTOR. (SEE CONNECTOR INSTALLATION INSTRUCTIONS)
DRAW AN X ON THIS SECTION
(THIS WILL BE CUT OFF)
MARK ALL FURCATION TUBES THAT WILL BE NEEDED
Page 3
6
7
INSTALLATION INSTRUCTIONS PN155B
CUT FURCATION TUBING TO SIZE
FURCATION TUBING
STRIP OUTER JACKET
8
9
CUT INNER TUBE FLUSH WITH EACH END OF JACKET
SLIDE FURCATION TUBING OVER THE BUFFERED FIBERS
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 4
Page 4
INSTALLATION INSTRUCTIONS PN155B
10
OVERLAP STRENGTH MEMBERS AND SLIDE HEAT SHRINK TUBING FORWARD, CENTERED OVER THE SPLICE
11
TERMINATE WITH AN APPROPRIATE CONNECTOR
BUFFERED FIBERS
12
250o F (121o C)
EVENLY HEAT THE TUBING UNTIL IT HAS FULLY RECOVERED AND CONFORMS TO THE CABLES.
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
Page 4 of 4