45° Up/Down UTP Field Term Plug
Cat 6A/6/5E
(CPUDCAPBL-X)
Plug
45° Up/Down
Wire Cap
(FPUD6X88MTG)
Protective
Cap
45° Up/Down
Wire Cap
IMPORTANT!: Determine the desired cable direction before wiring the cap. The cap orientation, in
relation to the plug, must be kept consistent throughout the entire termination.
Understanding the Label
"Up" Orientation
"Down" Orientation
Follow solid line
instructions for
"Up" Orientation.
(pages 2-3)
Follow dotted line
instructions for
"Down" Orientation.
(pages 4-5)
and Wire Caps
Part Numbers: FPUD6X88MTG, FPUD6X88MTG-X, CPUDCAPBL-X
© Panduit Corp. 2017
INSTALLATION INSTRUCTIONS
PN617
IMPORTANT!:
Be sure that
strain relief is fully
retracted before
inserting cable.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 6

© Panduit Corp. 2017
IMPORTANT!
The Brown/White & Blue/
White wire pairs will
always connect to the
positions shown in the
plug housing.
"Up" Orientation
1.5”
(38.1mm)
0.5”
(12.7mm)
1.5”
(38.1mm)
0.5”
(12.7mm)
Cable End 1
1
Cable End 2
Bend wires to
ease inserting
them into the
cap.
Be sure cable is fully
inserted into wire cap
INSTALLATION INSTRUCTIONS
PN617
Do not pre-arrange
conductors.
2
3
4
Cable End 1 Shown
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 6
Cable
End
(1)
Cable
End
(2)

© Panduit Corp. 2017
6
T568B Wiring
T568A Wiring
Termination side Label side
1.
1. 2.
1.
1. 2.
2.
Termination side
Label side
Cable End 1
Cable End 2
Cable End 1
Cable End 2
(T568A not shown on wire map label)
8
Important!
Maintain orientation of
cap in relation to jack
from previous steps.
INSTALLATION INSTRUCTIONS
"Up" Orientation
PN617
9
For Technical Support: www.panduit.com/resources/install_maintain.asp
10
Page 3 of 6

© Panduit Corp. 2017
Be sure cable is fully
inserted into wire cap
1.5”
(38.1mm)
0.5”
(12.7mm)
1.5”
(38.1mm)
0.5”
(12.7mm)
1
Cable End 1
Cable End 2
"Down" Orientation
INSTALLATION INSTRUCTIONS
IMPORTANT!
The Brown/White & Blue/
White wire pairs will
always connect to the
positions shown in the
plug housing.
PN617
Do not pre-arrange
conductors.
2
Bend wires to
ease inserting
them into the
cap.
3
4
Cable End 1 Shown
For Technical Support: www.panduit.com/resources/install_maintain.asp
Cable
End
(1)
Cable
End
(2)
Page 4 of 6

© Panduit Corp. 2017
1.
1. 2.
6
T568B Wiring
T568A Wiring
1.
1.
2.
2.
Termination side
Label side
Termination side
Label side
(T568A not shown on wire map label)
Cable End 1
Cable End 2
Cable End 1
Cable End 2
Important!
Maintain orientation of
cap in relation to jack
from previous steps.
8
INSTALLATION INSTRUCTIONS
"Down" Orientation
PN617
9
10
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 5 of 6

© Panduit Corp. 2017
INSTALLATION INSTRUCTIONS
REMOVAL STEPS
Notes:
1. For specified performance, follow TIA/EIA 568-C installation guidelines.
2. Jack Modules can terminate 22-26 AWG solid data cable with 0.062" (1.57mm) maximum insulated conductor outside diameter.
3. Jack Modules may be re-terminated at least 20 times.
4. For technical and performance information, consult Panduit Technical Support.
As with all Wiring Accessories, the following statements apply:
1. Never install communications wiring during a lightning storm.
2. Never install communications wiring in wet locations unless the jack is specifically designed for use in wet locations.
3. Never touch uninsulated communications wiring or terminals unless the communication line has been disconnected at the network interface.
4. Use caution when installing or modifying communication wiring.
PN617
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
E-mail:
techsupport@panduit.com
Phone:
866-405-6654