Temperature & Humidity Sensors
Temperature and humidity sensors are designed to add comprehensive environmental monitoring to any iPDU.
Environmental sensors are designed with an embedded microchip that converts analog signals to digital format
before data travels to the PDU, providing greater data accuracy. This smart design also enables easy plug & play
installation that takes just moments to complete. Installation of the sensors and ongoing equipment maintenance is
further facilitated by using a quick disconnect coupler and standard ethernet cable (sold separately) that allow for the
convenient positioning of sensors, movement of equipment, and an easy disconnect method for removing rack
enclosure doors.
Note: The Temperature and Humidity Sensors are designed to connect to a G5 iPDU only. Connecting them to another
device may result in damage.
INVENTORY
OPTIONAL ACCESSORIES
EA001: Temperature Sensor
or
EB001: Temperature and
Humidity Sensor
EC001: 3 Temperature
and 1 Humidity Sensor

Customer Service: CS@panduit.com 800.777.3300 Technical Support: techsupport@panduit.com 866.405.6654page 2
IM025 REV 02
INSTALLATION INSTRUCTIONS
The following instructions apply to both the temperature and the humidity sensors:
1.
Secure the sensor box to the perforated rack enclosure door by threading a cable tie through the
recessed channel in the sensor box and through the door.
Note: There are two recessed channels and a magnet on the back of the sensor box to help secure the
sensor.
2.
Secure the RJ45 cable along the desired path to the PDU using the included cable ties.
3.
For the EC001 sensors only:
• Secure the T1 temperature probe near the top of the cabinet
• Secure the T2 temperature/humidity probe (body) near the center of the cabinet
• Secure the
T3 temperature probe near the
bottom of the cabinet
4.
If desired, use a RJ45 quick disconnect coupler and a standard ethernet cable to extend the length of
the sensor input cable and/or to serve as an easy disconnect point for rack door removal.
5.
Plug the RJ-45 cable into a Sensor Port on the iPDU or Sensor Hub (Panduit PN: EF001).