Page 1
© Panduit Corp. 2012
EXHAUST DUCT FOR 7009 & 9513
CISCO SWITCHES
Part Number(s): DERLCC7009A & DERLCC9513A
INSTALLATION INSTRUCTIONS
Rear of Cabinet
CM611B
(Hot Aisle)
For a Net-Access N-Type
1070 Depth Switch Cabinet
(N**1*)
7009 & 9513 Exhaust Duct
Slider Plate (2)
(ONLY WITH
DERLCC9513A)
Front of Cabinet
(Cold Aisle)
Horizontal
Stiffener
Power
Duct
Inner
Cover
Outer
Cover
Inner
Frame
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 16
Corner
Bracket
Power
Duct
Bracket
Page 2
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM611B
Table of Contents
Page #
Equipment Rail Spacing...............................................................................................................................
Preparing Outer Duct for Installation............................................................................................................
Attaching Horizontal Stiffener......................................................................................................................
Day 1 Side Duct Installation
Installing Frame....................................................................................................................................
Installing Outer Cover...........................................................................................................................
Day 2 Side Duct Installation
Installing Frame....................................................................................................................................
Installing Outer Cover...........................................................................................................................
Attaching Corner Bracket.............................................................................................................................
Attaching Slider Plates..................................................................................................................................
Attaching Inner Cover...................................................................................................................................
Cover Opening with Tape.............................................................................................................................
Locating Power Duct....................................................................................................................................
Installing Power Duct Mounting Bracket.....................................................................................................
Installing Power Duct...................................................................................................................................
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Tools Needed:
-Socket Wrench
-M5 Socket
-Phillips Head Screw Driver
M5 Nut
M5 X 10mm
Hex Head
Screw
For Technical Support: www.panduit.com/resources/install_maintain.asp
M3 X 8mm
Pan Head
Screw
M5 X 8mm
Button Head
Screw
Page 2 of 16
#12-24 X 1/2"
Round Head
Screw
Page 3
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
Equipment Rail Spacing
• Front equipment should be in the complete forward position.
• Front and back equipment rail spacing must be 24.5" apart.
24.5"
CM611B
Rear of Cabinet
(Hot Aisle)
Front Equipment
Rails
(In full forward position)
Front of Cabinet
(Cold Aisle)
Rear Equipment Rails
(24.5" apart from front
equipment rails.)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 16
Page 4
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
Preparing Side Duct for Installation
• Unscrew (8) M5 x 8mm button head screws rear cover. (Screws will be used later in installation.)
• Separate rear cover from outer cover.
• Unscrew (4) M3 x 8mm pan head screws from outer cover. (Screws will be used later in installation.)
• Separate outer cover from frame.
(4) M5 X 8mm
(4) M3 X 8mm
Pan Head Screws
Outer Cover
Button Head Screws
CM611B
Inner Cover
Frame
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 16
Page 5
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
Attaching Horizontal Stiffener
• Attach horizontal stiffener to outer cover with (1) M3 x 8mm pan head screw.
Outer
Cover
CM611B
Horizontal
Stiffener
M3 x 8mm
Pan Head Screw
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 5 of 16
Page 6
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM611B
DAY 1
SIDE DUCT
INSTALLATION
Installing Frame
• Align top of side duct frame with top of switch.
• Fasten duct frame to the cabinet front post with (2) M5 x 10mm hex head screws. (Only use the slots on the
top and bottom on the front of the frame. Middle slot will be used with outer cover.)
• Loosen (4) M3 pan head screws ((6) M3 pan head screws for 7009.) on the frame brace. Adjust frame brace
to align with cabinet rear equipment rail. Secure frame brace to cabinet rear equipment rail with (2) M5 x
10mm hex head screws. Fasten (4) M3 pan head screws.
• NOTE: If, when attaching frame, there is an opening between the frame and switch cut and attach
bulb seal along edge of frame as shown.
(2) M3 Pan
(4) M5 x 10mm
Hex Head Screws
Head Screws
Bulb
Seal
Rear of Cabinet
(Hot Aisle)
(2) M3 Pan
Head Screws
(For 7009
Only)
Frame
Brace
Top of
Switch
(2) M3 Pan
Head Screws
Frame
Top of
Frame
Switch
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 6 of 16
Front of Cabinet
(Cold Aisle)
Page 7
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
Installing Outer Cover
• Attach outer cover to frame by sliding the tabs on the outer cover into the slots in the frame.
• Fasten outer cover to the frame with (4) M3 x 8mm pan head screws.
• Attach outer cover to cabinet front post with (1) M5 x 10mm hex head screw.
• (After this page skip to page 10 for rest of installation)
Rear of Cabinet
(4) M3 x 8mm
Pan Head Screws
Frame
(Hot Aisle)
CM611B
Outer
Cover
M5 x 10mm
Hex Head Screw
Note: Tab on outer cover
needs to fit into slot in frame.
Rear
Post
Rear
Equipment
Rail
Front
Post
Front
Equipment
Rail
Front of Cabinet
(Cold Aisle)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 7 of 16
Page 8
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM611B
DAY 2
SIDE DUCT
INSTALLATION
Installing Frame
• Slide frame into cabinet from the rear of the cabinet.
• Align top of side duct frame with top of switch.
• Fasten duct frame to the cabinet front post with (2) M5 x 10mm hex head screws. (Only use the slots on the
top and bottom on the front of the frame. Middle slot will be used with outer cover.)
• Loosen (4) M3 pan head screws on the frame brace. Adjust frame brace to align with cabinet rear equipment
rail. Secure frame brace to cabinet rear equipment rail with (2) M5 x 10mm hex head screws. Fasten (4) M3
pan head screws.
• NOTE: If, when attaching frame, there is an opening between the frame and switch cut and attach
bulb seal along edge of frame as shown.
Front of Cabinet
(Cold Aisle)
Frame
(2) M3 Pan
Head Screws
Bulb
Seal
(2) M3 Pan
Head Screws
Frame
Brace
(4) M5 x 10mm
Hex Head Screws
Rear of Cabinet
(Hot Aisle)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 8 of 16
Page 9
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
Installing Outer Cover
• Slide outer cover into cabinet from the rear of the cabinet.
• Attach outer cover to frame by sliding the tab on the outer cover into the slot in the frame.
• Fasten outer cover to the frame with (4) M3 x 8mm pan head screws.
• Attach outer cover to cabinet front post with (1) M5 x 10mm hex head screw.
Front of Cabinet
(Cold Aisle)
CM611B
(4) M3 x 8mm
Pan Head Screws
Outer
Cover
Note: Tab on outer cover
needs to fit into slot in frame.
M5 x 10mm
Hex Head Screw
Rear of Cabinet
(Hot Aisle)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 9 of 16
Page 10
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
Attaching Corner Bracket
• Attach corner bracket to outer cover with (1) M5 x 8mm button head screw.
• Fasten corner bracket to cabinet equipment rail with (2) M5 x 10mm hex head screws. (Adjust corner bracket
if needed.)
Front of Cabinet
(Cold Aisle)
CM611B
Equipment
Rail
Rear of Cabinet
(Hot Aisle)
Outer
Cover
Corner
Bracket
M5 x 8mm
Button Head Screw
(2) M5 x 10mm
Hex Head Screws
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 10 of 16
Page 11
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM611B
Attaching Slider Plates (For 9513 Switch Only)
• Attach (1) slider plates to the top of the inner cover and (1) slider plates to the bottom of the inner cover with
(4) M5 x 8mm button head screws. (Do not tighten screws.)
• Slide slider plates into place to cover any opening by equipment rails and tighten screws.
(4) M5 x 8mm
Button Head Screws
(2) Slider
Plates
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 11 of 16
Page 12
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
Attaching Inner Cover
• Attach inner cover to outer cover with (4) M5 x 8mm button head screws. (Do not tighten screws.)
• Slide inner cover all the way toward the front of the cabinet. Tighten screws.
• Fasten inner cover to horizontal stiffener with (2) M3 x 8mm pan head screws.
• Note: Inner cover slides over outer cover.
Outer
Cover
CM611B
(4) M5 x 8mm
Button Head Screw
Inner
Cover
(2) M3 x 8mm
Pan Head Screw
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 12 of 16
Page 13
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM611B
Cover Opening with Tape
• Cut a piece of tape, that was provided, to the size of the opening between the inner frame and rear equipment
rail.
• Apply tape to opening creating a seal.
• NOTE: Cut and apply tape to any other existing openings as needed.
Rear
Equipment
Tape
Rail
Inner
Cover
Inner
Frame
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 13 of 16
Opening
Page 14
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
Locating Power Duct
• The Cisco 9513 switch require the power duct to be located in the top mounting position.
• The Cisco 7009 switch requires the power duct to be mounted in the bottom mounting position.
CM611B
Power Ducting Mounted
At Bottom Of Switch
Power Ducting Configuration for
Cisco 7009 Switch
For Technical Support: www.panduit.com/resources/install_maintain.asp
Power Ducting Mounted
At Top Of Switch
Power Ducting Configuration for
Cisco 9513 Switch
Page 14 of 16
Page 15
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM611B
Locating and Installing Power Duct Mounting Bracket
• To locate power duct mounting bracket measure distance from top of switch to the bottom edge of the power
duct mounting bracket.
• The location of the power duct mounting bracket for each switch is as follows:
-7009 = 23.39"
-9513 = 2.64"
• Attach power duct mounting bracket to the equipment rail with (2) #12-24 X 1/2" round head screws.
• NOTE: Install (2) cage nuts into rail for cage nut rails prior to power duct mounting bracket
installation.
Top of Switch
Front of Cabinet
(Cold Aisle)
-7009 = 23.39"
-9513 = 2.64"
(2) #12-24 X 1/2"
Round Head Screws
(Attach to Cage Nuts
for Cage Nut Rails)
Bottom Edge of
Power Duct
Mounting Bracket
Power Duct
Mounting Bracket
Rear of Cabinet
(Hot Aisle)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 15 of 16
Page 16
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM611B
Installing Power Duct
• Slide the power duct into place on the power duct mounting bracket until it is against the switch.
• Secure the power duct to the power duct mounting bracket and inner cover with (5) M5 x 8mm button head
screws and (5) M5 nuts.
• NOTE: Visually level duct and verify that the duct aligns with switch exhaust opening.
Front of Cabinet
(Cold Aisle)
(5) M5 x 8mm
Button Head Screw
(5) M5 Nuts
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
Rear of Cabinet
(Hot Aisle)
www.panduit.com
Page 16 of 16