Top / Bottom Left Hand Bracket Installation......................................................................................................................
Top / Bottom Right Hand Bracket Installation....................................................................................................................
Installing Side Duct Day 1: Without Switch or Side Panel Installed...................................................................................
Installing Side Duct Day 2: With Switch and Side Panel Installed
Separate Side Duct Sections..........................................................................................................................................
Section A of Side Duct Installation..................................................................................................................................
Section B of Side Duct Installation..................................................................................................................................
Side Duct Seal Plate Installation........................................................................................................................................
Device Placement for Net-Access Legacy Cabinets (CN***)
•Due to physical constraints posed by the front-to-back beams on the Net-Access Legacy cabinet, there are
certain areas of the cabinet that the device cannot be mounted when used in conjunction with this inlet duct.
•For Net-Access Legacy cabinets, front equipment rails need to be in full forward position and rear equipment
rails need to be 24.25” - 26.1” back.
•NOTES:
• Numbers-up RU numbering (#1 at bottom) assumed.
45 RU Net-Access CN*** Cabinet (Legacy)
Device KEEP-OUT
area - RU 41 - 45
Device can be installed
in RU 27 - 40
Device KEEP-OUT
area - RU 20 - 26
Device can be installed
in RU 6 -19
42 RU Net-Access CN*** Cabinet (Legacy)
Device KEEP-OUT
area - RU 20 - 42
Device can be installed
in RU 6 - 19
Device KEEP-OUT
area - RU 1 - 5
Device KEEP-OUT
area - RU 1 - 5
For Technical Support: www.panduit.com/resources/install_maintain.asp
Device Placement for Net-Access N-Type Cabinets (N***)
•For Net-Access N-Type switch cabinets, there are no device keep-out areas. The only restriction on device is
that 3 RU must be left open above and below the switch.
•For Net-Access N-Type cabinets front and rear equipment rails need to be 24.25”-24.50” apart.
•NOTES:
• Numbers-up RU numbering (#1 at bottom) assumed.
Device KEEP-OUT
area - RU 42 - 45
Device can be installed
in RU 4 - 41
Device KEEP-OUT
area - RU 40 - 42
Device can be installed
in RU 4 - 39
Device KEEP-OUT
area - RU 1 - 3
Device KEEP-OUT
area - RU 1 - 3
For Technical Support: www.panduit.com/resources/install_maintain.asp
•From the rear of the cabinet slide section B of the side duct into the cabinet. (Exactly as shown)
•Through opening in top right bracket lift side duct into place and slide slots on section B of side duct onto threaded studs on section
A of side duct.
•Secure section B to section A with (4) #10-32 nuts,
(4) #10-32 Nuts
Section A
of Side Duct
Front of Cabinet
(Cold Aisle)
Note:
Shaded area
represents
side panel.
Threaded
Stud
Slot in Section B
Use Opening in Top Right
Side Bracket to Slide
Section B onto Section A.
7009 Switch
Front to Back Support Brackets Removed for Clarity.
For Technical Support: www.panduit.com/resources/install_maintain.asp
•Install top and bottom seal plates to side duct by inserting threaded studs into the holes in the duct and side bracket. Secure the seal
plates in place with (4) #10-32 nuts.
Rear of Cabinet
(Hot Aisle)
Side Duct
(4) Holes in side
brackets and
duct.
Side Duct
Top Seal Plate
(4) #10-32 Nuts
Front of Cabinet
(Cold Aisle)
(4) Threaded
Studs
For Technical Support: www.panduit.com/resources/install_maintain.asp