Panduit CNLTD142A3 Installation Manual

Page 1
Duct System for a Switch Cabinet Mounted CNLTD142A3 (Cisco 7009)
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
Front of Cabinet
(Cold Aisle)
Component Guide
Note: Upper RH Bracket Has Notches On Top.
CM584A
Rear of Cabinet
(Hot Aisle)
For a Net Access Legacy
or Net-Access N-Type
Switch Cabinet
(N*** or CN***)
Upper LH Bracket
Lower LH Bracket
Upper RH Bracket
Note: Lower RH Bracket Has Notches On Bottom.
Lower RH Bracket
(4) Adjustment Brackets
Upper Inlet Duct Box
Lower Inlet Duct Box
Top Seal Plate
Side Ducting
Bottom Seal Plate
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 14
Page 2
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM584A
INDEX
Preparing Cabinet for 7009 Duct Installation....................................................................................................................
Device Placement..............................................................................................................................................................
Top / Bottom Left Hand Bracket Installation......................................................................................................................
Top / Bottom Right Hand Bracket Installation....................................................................................................................
Installing Side Duct Day 1: Without Switch or Side Panel Installed...................................................................................
Installing Side Duct Day 2: With Switch and Side Panel Installed
Separate Side Duct Sections..........................................................................................................................................
Section A of Side Duct Installation..................................................................................................................................
Section B of Side Duct Installation..................................................................................................................................
Side Duct Seal Plate Installation........................................................................................................................................
Upper / Lower Duct Box Installation...................................................................................................................................
Securing Vertical Blanking Panel.......................................................................................................................................
Tools Needed:
-Phillips Head Screwdriver
-Socket Wrench
-3/8” Socket
-5/16” Socket
PAGE
3 4 5 6 7
8
9 10 11 12 13
# 12 Star
Washer
Hardware Supplied:
# 12-24
Screw
# 10-32
Nut
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 14
Page 3
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
Preparing Cabinet for 7009 Duct Installation For Legacy Net-Access (CN***) Cabinets Only
If present, remove side panel bumper by unscrewing (4) # 12-24 screws and (4) # 12 washers. (As shown in View A)
Remove (1) # 12-24 bolt from the front of the vertical blanking panel. Save bolt to be reinstalled later. (As shown in View B)
Rear of Cabinet
(Hot Aisle)
View A
(4) 12-24 Screws
CM584A
Front of Cabinet
(Cold Aisle)
(4) # 12 Star Washers
Bumper
View B
(1) 12-24 Bolt
Vertical Blanking Panel
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 14
Page 4
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM584A
Device Placement for Net-Access Legacy Cabinets (CN***)
Due to physical constraints posed by the front-to-back beams on the Net-Access Legacy cabinet, there are certain areas of the cabinet that the device cannot be mounted when used in conjunction with this inlet duct.
For Net-Access Legacy cabinets, front equipment rails need to be in full forward position and rear equipment rails need to be 24.25” - 26.1” back.
NOTES:
Numbers-up RU numbering (#1 at bottom) assumed.
45 RU Net-Access CN*** Cabinet (Legacy)
Device KEEP-OUT
area - RU 41 - 45
Device can be installed
in RU 27 - 40
Device KEEP-OUT
area - RU 20 - 26
Device can be installed
in RU 6 -19
42 RU Net-Access CN*** Cabinet (Legacy)
Device KEEP-OUT
area - RU 20 - 42
Device can be installed
in RU 6 - 19
Device KEEP-OUT
area - RU 1 - 5
Device KEEP-OUT
area - RU 1 - 5
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 14
Page 5
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM584A
Device Placement for Net-Access N-Type Cabinets (N***)
For Net-Access N-Type switch cabinets, there are no device keep-out areas. The only restriction on device is that 3 RU must be left open above and below the switch.
For Net-Access N-Type cabinets front and rear equipment rails need to be 24.25”-24.50” apart.
NOTES:
Numbers-up RU numbering (#1 at bottom) assumed.
Device KEEP-OUT
area - RU 42 - 45
Device can be installed
in RU 4 - 41
Device KEEP-OUT
area - RU 40 - 42
Device can be installed
in RU 4 - 39
Device KEEP-OUT
area - RU 1 - 3
Device KEEP-OUT
area - RU 1 - 3
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 5 of 14
Page 6
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM584A
Top / Bottom Left Hand Bracket Installation
Measure distance between front and rear equipment rails.
Attach (1) adjustable bracket to each side bracket. (As shown)
Adjust bracket to fit equipment rail spacing.
Tighten adjustment bracket nuts.
Install (1) upper left hand bracket with (4) #12-24 screws and (4) #12 star washers. (Leave screws loose until Inlet Box is installed.)
Install (1) lower left hand bracket with (4) #12-24 screws and (4) #12 star washers. (Leave screws loose until Inlet Box is installed.)
NOTE: If cabinet equipment mounting rails have square holes, one grounding cage nut should be used in each mounting rail.
Rear of Cabinet
Equipment Rail Spacing
(Hot Aisle)
Upper
Left Hand Bracket
Equipment Rail Spacing
Adjustment Nuts
Adjustment Bracket
Upper
Left Hand
Bracket
(8) #12-24 screws
(8) #12 Star Washers
Lower
Left Hand Bracket
Adjustment Nuts
For Technical Support: www.panduit.com/resources/install_maintain.asp
Adjustment Bracket
Front of Cabinet
(Cold Aisle)
Page 6 of 14
Vertical Blanking Panels
Lower
Left Hand
Bracket
Page 7
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM584A
Top / Bottom Right Hand Bracket Installation
Measure distance between front and rear equipment rails.
Attach (1) adjustable bracket to each side bracket. (As shown)
Adjust bracket to fit equipment rail spacing.
Tighten adjustment bracket nuts.
Install (1) upper right hand bracket with (4) #12-24 screws and (4) #12 star washers. (Leave screws loose until Inlet Box is installed.)
Install (1) lower right hand bracket with (4) #12-24 screws and (4) #12 star washers. (Leave screws loose until Inlet Box is installed.)
Upper
Right Hand Bracket
Lower
Right Hand Bracket
Adjustment Bracket
Equipment Rail Spacing
Adjustment Bracket
Adjustment Nuts
Adjustment Nuts
Rear of Cabinet
(Hot Aisle)
(8) #12 Star Washers
(8) #12-24 screws
Upper
Right Hand
Bracket
Equipment Rail Spacing
For Technical Support: www.panduit.com/resources/install_maintain.asp
Front of Cabinet
(Cold Aisle)
Page 7 of 14
Lower
Right Hand Bracket
Vertical Blanking Panels
Page 8
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM584A
Installing Side Duct Day 1:
Without Switch or Side Panel in Place.
Side Duct Installation
Install Side Duct by sliding threaded studs on side duct into slots in upper and lower right hand brackets and secure with (4) #10-32 nuts.
NOTE: For Net-Access N-Type cabinets only, attach 1” thick foam seal along edge of side duct. (See Detail Below)
Rear of Cabinet
(Hot Aisle)
NOTE: For Net­Access N-Type Cabinets Only, attach provided strip of foam seal along edge of side duct.
(4) #10-32 Nuts
Side Duct
(4) Threaded Studs
Front of Cabinet
(Cold Aisle)
(4) Bracket Slots
Vertical Blanking Panels Removed for Clarity.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 8 of 14
Page 9
© Panduit Corp. 2012
Installing Side Duct Day 2:
With Switch and Side Panel in Place.
Separate Side Duct Sections
Remove (4) #10-32 nuts.
Separate Section A from Section B.
INSTALLATION INSTRUCTIONS
CM584A
Section B of Side Duct
Section A of Side Duct
(4) #10-32 Nuts
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 9 of 14
Page 10
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
Section A of Side Duct Installation
From the rear of the cabinet slide section A of the side duct into cabinet. (Exactly as shown)
Slide the threaded studs on the side duct into the slots in the upper and lower right hand brackets as shown.
Secure side duct to brackets with (4) #10-32 nuts.
Front of Cabinet
(Cold Aisle)
Note: Shaded area represents side panel.
CM584A
7009 Switch
(4) #10-32 Nuts
Section A of Side Duct
Rear of Cabinet
(Hot Aisle)
Slot in Bracket
Front to Back Support Brackets Removed for Clarity.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 10 of 14
Threaded Stud
Page 11
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM584A
Section B of Side Duct Installation
From the rear of the cabinet slide section B of the side duct into the cabinet. (Exactly as shown)
Through opening in top right bracket lift side duct into place and slide slots on section B of side duct onto threaded studs on section A of side duct.
Secure section B to section A with (4) #10-32 nuts,
(4) #10-32 Nuts
Section A of Side Duct
Front of Cabinet
(Cold Aisle)
Note: Shaded area represents side panel.
Threaded Stud
Slot in Section B
Use Opening in Top Right Side Bracket to Slide Section B onto Section A.
7009 Switch
Front to Back Support Brackets Removed for Clarity.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 11 of 14
Section B of Side Duct
Rear of Cabinet
(Hot Aisle)
Page 12
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM584A
Side Duct Seal Plate Installation
Install top and bottom seal plates to side duct by inserting threaded studs into the holes in the duct and side bracket. Secure the seal plates in place with (4) #10-32 nuts.
Rear of Cabinet
(Hot Aisle)
Side Duct
(4) Holes in side brackets and duct.
Side Duct
Top Seal Plate
(4) #10-32 Nuts
Front of Cabinet
(Cold Aisle)
(4) Threaded Studs
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 12 of 14
Bottom Seal Plate
Page 13
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM584A
Upper / Lower Duct Box Installation
Install (1) upper inlet duct box by sliding box into upper brackets, along built in guide flanges and securing with (2) #10-32 nuts.
Install (1) lower inlet duct box by sliding box into lower brackets, along built in guide flanges and securing with (2) #10-32 nuts.
Tighten all bracket screws that were intentionally left loose earlier.
Rear of Cabinet
(Hot Aisle)
Upper Inlet Duct Box
(2) #10-32 Nuts
Upper Brackets
Lower Inlet Duct Box
Front of Cabinet
(Cold Aisle)
Lower Brackets
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 13 of 14
Page 14
© Panduit Corp. 2012
INSTALLATION INSTRUCTIONS
CM584A
Securing Vertical Blanking Panel (For Legacy Net-Access (CN***) Cabinets Only)
Replace the (1) # 12-24 bolt that was removed on page 1.
Vertical Blanking Panel
(1) # 12-24 Bolt
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
Page 14 of 14
E-mail:
techsupport@panduit.com
Phone:
866-405-6654