Panduit CFAPPBL2A Installation Manual

OPTICOM QUICKNET Rack Mount Angled Fiber
Cassette Enclosures and Patch Panels
Part Numbers: FMT1A, FMT2A, CFAPPBL1A, CFAPPBL2A
© Panduit Corp. 2009
CFAPPBL1A
(sold separately)
CONTENTS: (#) indicates FMT2A quantity
WARNING: UNMATED CONNECTORS MAY EMIT INVISIBLE LASER RADIATION. DO NOT LOOK DIRECTLY INTO THE END OF THE CONNECTOR. DO NOT INSPECT WITH MAGNIFYING DEVICES. MAINTAIN CAP ON UNMATED CONNECTORS.
CAUTION:
Fiber optic cable is sensitive to excessive pulling, bending and crushing forces. Consult the manufacturer’s cable specification sheet for the specific cable in use.
Follow TIA/EIA-568A, 569, 606, and 607 installation guidelines where applicable. Care should be taken when opening and closing fully loaded drawer in order to protect fiber components.
INSTALLATION INSTRUCTIONS
FMT1A
CFAPPBL2A
(sold separately)
1 (2) - CABLE ENTRY GROMMET(S) 1 (2) - STRAIN RELIEF BRACKET(S) 2 - ADHESIVE BEVEL ENTRY CLIPS 2 - ADHESIVE BACKED MOUNTS
AK-TYs (6" pcs.)
4 - T 2 - SLACK SPOOLS (FMS1 or FMS2)
FS007A
FMT2A
1 - CAUTION LABEL 1 - LASER WARNING LABEL
ASSEMBLY VIEW showing Fiber Adapter Panels (FAPs) - sold separately
Fiber Adapter Panels (FAPs): Up to 4 for FMT1A Up to 8 for FMT2A
(sold separately)
Cover (field removable)
Trunk or Interconnect Cable Entry Grommet
PG16 Gland
(customer supplied)
Strain Relief Bracket
Enclosure
Angled Patch Panel
(CFAPPBL1A shown)
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 8
© Panduit Corp. 2009
Preparation and Rack Mounting
INSTALLATION INSTRUCTIONS
Cover
FS007A
#10-32 hex nuts and #10 flat washers
#10-32 screw
Figure 1
Figure 2
To remove the cover, unscrew the #10-32 screw, slide the cover back, lift up and off.
Attach the angled patch panel to the enclsoure with (2) #10 flat washers and (2) #10-32 hex nuts.
Determine where the cable will enter the enclosure. Carefully remove the knock-out so as not to damage the surrounding sheet metal.
DO NOT install the grommet at this stage. Grommet will be installed after the enclosure is mounted to the rack.
Figure 3
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 8
© Panduit Corp. 2009
INSTALLATION INSTRUCTIONS
FS007A
Mounting Brackets
(2) #12-24 x 1/2" screws Repeat for other side.
Place the mounting brackets at the desired position on the rack.
Figure 4A
Mount the enclosure to the rack using (4) #12-24 x 1/2" screws.
Use (4) M6 x 1 screws if mounting to a metric rack.
Angled Patch
Panel
(CFAPPBL1A shown)
Figure 4B
Angled patch panels may be mounted directly to the rack without an enclosure. Place at the desired position on the rack and secure with (4) #12-24 x 1/2" screws.
Use (4) M6 x 1 screws if mounting to a metric rack.
Figure 4C
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 8
© Panduit Corp. 2009
Grommet Cutting Diagram
Cut out the small
circle for 1" dia.
innerduct
INSTALLATION INSTRUCTIONS
Cut the straight
lines for smaller
bundle sizes
FS007A
After the enclosure is mounted to the rack, determine the size of the innerduct (if any) that will be used to bring the cable into the enclosure. Prepare grommet according to the proper cutting diagram to the left.
Cut out the small
circle for 1-1/4" dia.
innerduct
Cut out the large circle
for 1-1/2" dia.
innerduct
#10-32 hex nut
#10 flat washer
#10-32 x 5/16" screw
Cut the straight lines
when not using any
innerduct
Figure 5A
Grommet
Figure 5B
Install prepared grommet.
Install (1) #10 flat washer and (1) #10-32 hex nut over the stud on the enclosure as shown. This will be used to secure the strength member from the cable.
Strain Relief Bracket
For Technical Support: www.panduit.com/resources/install_maintain.asp
Install the strain relief bracket near where the cable will enter the enclosure. Secure with #10-32 x 5/16" screw and #10-32 hex nut.
#10-32 hex nut
Figure 6
Page 4 of 8
© Panduit Corp. 2009
INSTALLATION INSTRUCTIONS
QUICKNET Cassette Installation - sold separately
Cassettes: Up to 3 for FMT1A
Up to 6 for FMT2A
FAPB
(sold separately)
NyLatch fasteners
FS007A
Insert QUICKNET Pre-Terminated Fiber Optic Cassettes into the enclosure as shown. Once mounted, fully seat NyLatch fasteners to secure the cassettes.
A Fiber Access Blanking Panel (FAPB) may be installed in the open bay to close.
Figure 7A
Adhesive Bevel Entry Clips
(Note location and position of clips)
Grommet
Fixed
TAK-TY
Free Floating
TAK-TYs
Route fiber through the cable entry grommet to the fiber cassettes as shown.
AK-TYs to secure fiber cords at cable entry
Use T location and other points as shown.
Figure 7B
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 5 of 8
© Panduit Corp. 2009
INSTALLATION INSTRUCTIONS
Field Termination or Pre-Terminated Trunk Installation
Slack Spools FMS1 or FMS2
Fiber Adapter Panels (FAPs): Up to 4 for FMT1A Up to 8 for FMT2A
Figure 8A
FS007A
Using adhesive backing, place slack spools in enclosure, note spool orientation. Approximate location is 5" off back wall with spools 9" apart centered in the enclosure.
Position FAPs into the angled patch panel as shown. Once mounted, fully seat NyLatch fasteners to secure FAPs.
Individual fiber break out point
(See detail)
Strength Member
5"
[127mm]
9"
[228mm]
Adhesive Backed Mount with TAK-TY
Grommet
Fixed TAK-TY
Route fiber through the cable entry grommet as shown. Use enough cable length to ensure one complete loop of individual fibers around slack spools. Attach the strength member of the cable around the #10-32 stud, securing with the #10 flat washer and #10-32 hex nut previously installed.
AK-TYs to secure fiber cords at the cable
Use T entry location and other points as shown.
cable jacket
individual fiber
1.0"
[2.54mm]
Fiber Break out Detail
Be sure adhesive backed mount is positioned to secure the jacketed trunk cable. DO NOT
clip individual 900µm buffered fibers.
Figure 8B
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 6 of 8
© Panduit Corp. 2009
INSTALLATION INSTRUCTIONS
Fiber Optic Splice Module (FOSM) Installation - sold separately
FOSM: Up to 4 for FMT1A, Up to 8 for FMT2A
FS007A
Fiber Adapter Panels (FAPs): Up to 4 for FMT1A, Up to 8 for FMT2A.
Individual Fiber Break out Point
(See fiber break out detail on page 6)
Break off side latches on top module only (See Note)
Adhesive Bevel Entry Clip
(Note location and position of clips)
Figure 9A
Grommet
Recommended position for FOSM is 3" max from enclosure back wall.
Place first FOSM into the enclosure using double stick tape (not included). Note orientation. Remaining FOSMs are stacked on top of each other and snap in place.
Note: If 4 FOSMs are to be installed in the FMT1A, the side latches on the top module must be broken off to place the cover back on the enclosure.
Position FAPs into the angled patch panel as shown. Once mounted, fully seat NyLatch fasteners to secure FAPs.
Route fiber through cable entry grommet as shown. Use enough cable length to ensure one complete loop (approx. 45" [1.15m]) of individual fibers around FOSM slack spools.
3" MAX
76.2mm
* Denotes revision letter.
Route 900µm buffered fiber from the trunk cable and splice to pigtail per instructions in
FS001*, OPTICOM Fiber Optic Splice Module Installation Instructions.
AK-TYs to secure fiber cords at cable
Use T entry location and other points as shown.
Fixed
AK-TY
T
Figure 9B
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 7 of 8
© Panduit Corp. 2009
INSTALLATION INSTRUCTIONS
FST6 Fiber Splice Tray Installation - sold separately
Fiber Splice Tray
FS007A
3" MAX [76.2mm]
FSC24 Fiber Splice Holder Installation - sold separately
Position Splice Tray as shown. Reference CM92*, installation instructions for Fiber Splice Tray.
Figure 11
* Denotes revision letter.
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
Fiber Splice Holder
www.panduit.com
Figure 12
Reference Figure 8B for slack spool positioning.
See CM307*, installation instructions for fiber splice holder.
E-mail:
cs@panduit.com
Fax:
(708) 444-6448
Page 8 of 8