WARNING: UNMATED CONNECTORS MAY EMIT INVISIBLE LASER RADIATION. DO NOT LOOK DIRECTLY INTO THE END OF THE
CONNECTOR. DO NOT INSPECT WITH MAGNIFYING DEVICES. MAINTAIN CAP ON UNMATED CONNECTORS.
CAUTION:
Fiber optic cable is sensitive to excessive pulling, bending and crushing forces. Consult the manufacturer’s cable specification sheet for
the specific cable in use.
Follow TIA/EIA-568A, 569, 606, and 607 installation guidelines where applicable.
Care should be taken when opening and closing fully loaded drawer in order to protect fiber components.
Place the mounting brackets at the desired
position on the rack.
Figure 4A
Mount the enclosure to the rack using
(4) #12-24 x 1/2" screws.
Use (4) M6 x 1 screws if mounting to a metric
rack.
Angled Patch
Panel
(CFAPPBL1A shown)
Figure 4B
Angled patch panels may be mounted directly
to the rack without an enclosure. Place at the
desired position on the rack and secure with
(4) #12-24 x 1/2" screws.
Use (4) M6 x 1 screws if mounting to a metric
rack.
Figure 4C
For Technical Support: www.panduit.com/resources/install_maintain.asp
After the enclosure is mounted to the rack,
determine the size of the innerduct (if any) that
will be used to bring the cable into the enclosure.
Prepare grommet according to the proper cutting
diagram to the left.
Cut out the small
circle for 1-1/4" dia.
innerduct
Cut out the large circle
for 1-1/2" dia.
innerduct
#10-32 hex nut
#10 flat washer
#10-32 x 5/16" screw
Cut the straight lines
when not using any
innerduct
Figure 5A
Grommet
Figure 5B
Install prepared grommet.
Install (1) #10 flat washer and (1) #10-32 hex nut
over the stud on the enclosure as shown. This
will be used to secure the strength member from
the cable.
Strain Relief
Bracket
For Technical Support: www.panduit.com/resources/install_maintain.asp
Install the strain relief bracket near where the
cable will enter the enclosure. Secure with
#10-32 x 5/16" screw and #10-32 hex nut.
Field Termination or Pre-Terminated Trunk Installation
Slack Spools
FMS1 or FMS2
Fiber Adapter Panels (FAPs):
Up to 4 for FMT1A
Up to 8 for FMT2A
Figure 8A
FS007A
Using adhesive backing, place slack spools in
enclosure, note spool orientation. Approximate
location is 5" off back wall with spools 9" apart
centered in the enclosure.
Position FAPs into the angled patch panel as
shown. Once mounted, fully seat NyLatch
fasteners to secure FAPs.
Individual fiber
break out point
(See detail)
Strength Member
5"
[127mm]
9"
[228mm]
Adhesive Backed
Mount with TAK-TY
Grommet
Fixed TAK-TY
Route fiber through the cable entry grommet as
shown. Use enough cable length to ensure one
complete loop of individual fibers around slack
spools. Attach the strength member of the
cable around the #10-32 stud, securing with the
#10 flat washer and #10-32 hex nut previously
installed.
AK-TYs to secure fiber cords at the cable
Use T
entry location and other points as shown.
cable jacket
individual fiber
1.0"
[2.54mm]
Fiber Break out Detail
Be sure adhesive backed mount is positioned
to secure the jacketed trunk cable. DO NOT
clip individual 900µm buffered fibers.
Figure 8B
For Technical Support: www.panduit.com/resources/install_maintain.asp
Fiber Optic Splice Module (FOSM) Installation - sold separately
FOSM: Up to 4 for FMT1A, Up to 8 for FMT2A
FS007A
Fiber Adapter Panels (FAPs):
Up to 4 for FMT1A, Up to 8 for FMT2A.
Individual Fiber
Break out Point
(See fiber break out
detail on page 6)
Break off side
latches on top
module only
(See Note)
Adhesive Bevel
Entry Clip
(Note location and
position of clips)
Figure 9A
Grommet
Recommended position for FOSM is 3" max
from enclosure back wall.
Place first FOSM into the enclosure using
double stick tape (not included). Note
orientation. Remaining FOSMs are stacked
on top of each other and snap in place.
Note: If 4 FOSMs are to be installed in the
FMT1A, the side latches on the top module
must be broken off to place the cover back on
the enclosure.
Position FAPs into the angled patch panel as
shown. Once mounted, fully seat NyLatch
fasteners to secure FAPs.
Route fiber through cable entry grommet as
shown. Use enough cable length to ensure
one complete loop (approx. 45" [1.15m]) of
individual fibers around FOSM slack spools.
3" MAX
76.2mm
* Denotes revision letter.
Route 900µm buffered fiber from the trunk
cable and splice to pigtail per instructions in