•Trim foam seal to required lengths to cover one side of the wall panel.
•Note: Do not apply foam to the side of the row base cooler wall panel that will be against the cold aisle
containment wall panel that already has foam on it.
Wall Panel
CM640A
(1) .75 x .5 Foam
Seal
For Technical Support: www.panduit.com/resources/install_maintain.asp
•With the (2) M5 hex nuts on the blanking panel extension and the (4) M5 x 12mm button head screws on
the blanking panel loose, adjust the height of the blanking panels to form a complete and tight seal with
the top on the row base cooler unit.
•Tighten the (2) M5 x 12mm button head screws on the blanking panel.
•Remove the (2) M5 hex nuts from the blanking panel assembly.
•Remove blanking panel assembly from the wall panel.
(2) M5 Hex
Nuts
Blanking Panel
CM640A
Extension
(2) M5 x 12mm
Button Head
Screws
Adjust Height of
Blanking Panel and
Blanking Panel
Extension to Form
a Tight Seal.
Blanking
Panel
For Technical Support: www.panduit.com/resources/install_maintain.asp
•From under the wall panel, slide the blanking panel assembly into place with the studs on the blanking
panel assembly into the slots in the wall panel.
•Pressing the blanking panel assembly down against the row base cooler unit fasten the blanking panel
assembly to the wall panel with (2) M5 hex nuts.
•Any unused screw holes that are exposed can be plugged using the screws provided.
CM640A
For Technical Support: www.panduit.com/resources/install_maintain.asp
•Measure the distance from the bottom of the row base cooler unit to the floor.
•Apply the appropriate amount of either .5" x .75" or 1" x 1" foam seal to the top and/or bottom of the floor
seal bracket to make a tight fit between the row base cooler unit and the floor.
CM640A
Distance from the
Bottom of the In-Row
Cooling Unit and the
Floor
Foam Seal
(As Needed)
Floor Seal
Bracket
Foam Seal
(As Needed)
For Technical Support: www.panduit.com/resources/install_maintain.asp
•Slide floor seal assembly in between the floor and the row base cooler unit making sure that the floor seal
assembly forms a tight and complete seal to prevent air loss.
Row Base
Cooler
Unit
CM640A
Floor Seal
Assembly
For Technical Support: www.panduit.com/resources/install_maintain.asp