Panduit ACE02 Operating Instructions Manual

ACE02 Electronic Swinghandle with PROX Card Reader Operating Instructions
Package Contents
ACE02 Electronic Swinghandle with Proximity Reader (qty1)
M3x25 POZIDRIV
M3x14 POZIDRIV
Rotation Limiter (qty 1)
Rotation Limiter (qty1)
Pawl Screw (qty 1)
Lock Plug Screw (qty 1) (optional)
Top Mounting Bracket (qty 1)
Bottom Mounting Bracket (qty 1)
Operating Instructions (qty 1)
ACE02 Electronic Swinghandle with Proximity Reader
1. Handle
2. Prox Reader
3. Tri-Color Status LED
4. Lock Plug (optional)
Features
Installed 125kHz proximity reader module with Wiegand data output
Remote lock and unlock capability
Single or multi-point lock actuation
Momentary or continuous lock actuation
Tri-color LED (blue/magenta/red) to indicate lock and handle
status
DIN lock manual override
Accommodates both left and right doors
For indoor use only
WARNING: The ACE02 is shipped without a lockplug. This product must be paired with an approved lock to function properly. Use with an unapproved lockplug voids the product warranty.
Mounting Screws (qty 4)
Mounting Screw (qty 1)
Specifications
Actuator Module
Supply Voltage (V
): 12VDC to 24VDC (NOTE: Status LED will blink
SUPPLY
red if the supply voltage is out of range.) Standby Current: 50mA maximum at 12VDC Operating Current: 200mA maximum at 12VDC (with no external mechanical load applied to handle Stall Current: 1A maximum (at 12VDC, limited to 2 seconds) Operating Transit Time: 1 second maximum (NOTE: Power must be
present during transit times. If power is removed while the lock slide is in transit, it will complete its cycle when power is
restored.) Electronic Unlock Time: 3 seconds minimum Open Collector Outputs: Rated for V
Proximity Reader Module
, maximum load
SUPPLY
Supply Voltage (VCC): 12VDC to 24VDC Operating Current: 20mA maximum (no external devices attached) Transmit Frequency: 125kHz FSK DATA Signal Voltage: 5VDC DATA Pulse Interval Time: 40µs DATA Signal Delay: 2ms
Mounting and Installation
Please refer to product drawing for mounting and installation details.
NOTE: Use a #1 POZIDRI V® driver when installing the mounting
screws. See product drawing for additional details.
Wiring Diagrams
The ACE02 contains two separate functional modules: the actuator module and proximity reader module. The actuator module controls and monitors the locking function of the swinghandle. The proximity module reads the contents of a compatible p roximity card and converts it to Wiegand format.
These two modules operate independently of each other and require connection to an access control unit (not provided), as illustrated below, for the entire product to be fully functional.
visit www.panduit.com for latest version of this document Page 1 of 4
ACE02 Electronic Swinghandle with PROX Card
Pin
Description
Note
1
V
ground (must be same as proximity reader module)
2
V
12 to 24 VDC power supply input (may be connected to prox reader VCC input)
3
N/C
no connect
4
Control Signal
command input (9VDC up to supply voltage, 100 milliseconds minimum)
5
Electronic Lock Status
open collector output (rated for V
,
100mA max. load)
6
Mechanical Lock Status
open collector output (rated for V
,
100mA max. load)
Pin
Wire Color
Description
Note
1
Black
GND
ground (must be same as actuator module)
2
Red
VCC
12 to 24VDC power supply input V
SUPPLY
input)
3
Green
DATA0
DATA0 output
4
White
DATA1
DATA1 output
electronic lock
handle secured
Reader Operating Instructions
The actuator module of the swinghandle is accessed with a six-position connector on the rear of the unit, shown below.
GND
SUPPLY
The proximity reader module of the swinghandle is accessed with a four­position connector attached to a harness connected to the module’s circuit board. The module’s connector pinout is:
SUPPLY
SUPPLY
(may be connected to EML
Control Input Signal
This signal is used to control the electronic lock slide position.
for UNLOCKED position: Supply 9VDC minimum (do not exceed supply voltage) for at least 100 milliseconds. The lock will remain unlocked for as long as the signal is present, or a minimum of 3 seconds. Signal timing can typically be adjusted at the access control device. The control signal current draw is less than 10mA.
for LOCKED position: Supply an open contact or 0VDC (0 to
0.5V)
Electronic Lock Status Output and Mechanical Lock Status Output Signals
Electronic Lock Status Output Signal
This output will be LOW (GND) when the lock slide is electromechanically moved to the unlocked position. It will be in the open collector state (high­impedance) when in the locked position.
Mechanical Lock Status Output Signal
This output will be LOW (GND) when the handle is in the open position or when the keylock in the actuator is manually unlocked. It will be in the open collector state (high-impedance) when in the secured position.
NOTE: These outputs are open collector outputs rated for V
SUPPLY
with a maximum load of 100mA. To avoid damage to the ACE02, do not exceed voltage and current ratings.
Status LED and Output Signals
The latch is equipped with a tri-color (blue/magenta/red) LED visible from the front of the latch. This LED provides a visible notification of the latch status. The different latch states are described below. Please refer to the
Control Input Signal, Electronic Lock Status Output Signal, and Mechanical Lock Status Output Signal sections for further details on
these signals. Secured The latch is securely closed, prohibiting access.
The Status LED will be solid blue.
The electronic lock status output is at its open collector state.
The mechanical lock status output is at its open collector state.
NOTE: The mating connectors/harnesses are not provided with the
ACE02. Refer to spec sheet for mating connector/harness requirements.
visit www.panduit.com for latest version of this document Page 2 of 4
in housing, cam in locked position
“Secured” State
slide in locked position
ACE02 Electronic Swinghandle with PROX Card
Ton= 5ms
T
on
T
off
= 5ms
T
off
T
burst
T
burst
= 400ms (min)
control
input
electronic
handle
electronic
position
electronic
position
lock plug in
position
cam
cam not
Reader Operating Instructions
Electronically Released
The electronic lock slide is in the unlocked position and the handle can be pulled open.
The Status LED will alternate flashing blue/magenta.
The electronic lock status output is 0V while the lock slide is in
the unlocked position.
The mechanical lock status output is at its open collector state.
secured in housing, cam in locked position
lock slide in unlocked position
Handle not Fully Closed
This is an interim state and may occur while closing the handle when the cam is not secured by the electronic lock slide. The latch is not fully secured during this state.
The Status LED will alternate flashing blue/red if the cam is not detected. It will flash blue/red/red if the cam is detected, but the lock plate is not in the right position. This could be due to mechanical failure or tampering.
The electronic lock status output is 0V if the lock slide is in the unlocked position. It will be at its open collector state if it is in the lock position.
The mechanical lock status output is 0V if the cam is not detected. It will be at its open collector state if it is detected.
detected by
latch
“Electronically Released” State
Mechanically Released
The latch is released by opening the handle or moving the cam from its lock position.
The Status LED will flash blue.
The electronic lock status output will be at its open collector state
if the electronic lock slide is in the locked position. It will be 0V if the lock slide is in the unlocked position.
The mechanical lock status output is 0V.
NOTE: The lock sensor is an optical device that senses the presence of the lock pawl. Reflectivity of the lock pawl material can affect sensing. Use only approved locks.
lock slide in
locked
lock slide in
unlocked
detected by
latch
“Handle not Fully Closed” State
Electronic Lock Slide Error
The electronic lock slide does not respond to the command input signal.
The Status LED will flash magenta if the latch is secured. It will alternate flashing red/magenta if the latch is mechanically released.
The electronic lock status output is at its open collector state.
The mechanical lock status output will be at its open collector
state if the cam is in its lock position. It will be 0V if the mechanical key is moved from its lock position.
Error Input Command Sequence
The ACE02 can accept an input command from an external controller to flash the status LED red three times. This feature can be used to indicate that an error event has occurred (e.g. unauthorized access attempt).
The control input signal needs to meet the timing requirements shown below to flash the status LED red.
unlocked
“Mechanically Released” State
visit www.panduit.com for latest version of this document Page 3 of 4
FCC Compliance Statement
POZIDRIV
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential inst all at i on. This equi pment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determi ned by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
FCC Caution: This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1) This device may not cause harmful interference and
2) This device must accept any interference received, including interference that may cause undesired operation.
RF Exposure Warning: The equipment complies with RF exposure limits set forth for an uncontrolled environment. The antenna(s) used for this transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.
You are cautioned that changes or modifications not expressly approved by the party responsible for compliance could void your authority to operate the equipment.
Industry Canada Compliance Statement
This digital apparatus does not exceed the Class B limits for radio noise emissions from digital apparatus as set out in the interference-causing equipment standard entitled “Digital Apparatus,” ICES-003 of Industry Canada.
Cet appareil numérique respecte les limites de bruits radioélectriques applicables aux appareils num ériques de Cl asse B prescrit es dans la norme sur le material brouilleur: “Appareils Numériques,” NMB-003 édictée par l’Industrie.
is a registered trademark of the Phillips Screw Company
ACE02 Electronic Swinghandle with PROX Card Reader Operating Instructions
For technical support of this product contact: techsupport@panduit.com or v isit: www.panduit.com
visit www.panduit.com for latest version of this document Page 4 of 4
Loading...