Panasonic S-LINK SL-TPR4, S-LINK SL-TPR8 Instruction Manual

INSTRUCTION MANUAL
Sensor & Wire-saving Link System S-LINK
Relay Output Terminal Unit
SL-TPR4, SL-TPR8
MJE-SLTPR No.0063-18V
Thank you very much for purchasing Panasonic products. Read this Instruction Manual carefully and thoroughly for the correct and optimum use of this product. Kindly keep this manual in a convenient place for quick reference.
1
OVERVIEW
This product is an ultra-small S-LINK relay output terminal unit which permits relay replacement.
PART DESCRIPTION
2
SL-TPR4 / 4 channel relay output type
4-core flat cable 0.6m long
Address setting switch
Setting switch section
Switch cap removed condition
Transmission indicator (Green)
Relay removal key
2-mounting holes for M4 screws
SL-TPR8 / 8 channel relay output type
4-core flat cable 0.6m long
Address setting switch
Setting switch section
Switch cap removed condition
Transmission indicator (Green)
Relay removal key
2-mounting holes for M4 screws
PRECAUTIONS
3
Make sure that the power supply is off while wiring
Switch on the power supply after confirming that the wiring is
correct. If the power supply is switched on when the wiring is incorrect, there is a danger of malfunction or damage.
Do not use during the initial transient time (0.5 sec.) after the
power supply is switched on. If power is supplied from a commercial switching regulator,
ensure that the frame ground (F.G.) terminal of the power supply is connected to an actual ground. Do not run the wires together with high-voltage lines or power
lines or put them in the same raceway. This can cause malfunction due to induction. A switch cap is fitted on the setting switch section. Remove
the cap at the time of setting. After the setting, make sure to fit it back. Use tweezers, etc., having a tip width of approx. 0.8mm to
operate the switches. This product does not have a dust-proof or water-proof
construction. Do not use it in places having excessive water vapor, dust, corrosive gas or where it may come in direct contact with water or chemicals. Make sure to fit the cover before use.
Output hold setting switch
4-operation indicators (Orange)
output relays (4relays)
PA-N Relay APAN3124 made by Panasonic Corporation
Terminal block
DIN rail stopper
Output hold setting switch
8-operation indicators (Orange)
output relays(8relays)
PA-N Relay APAN3124 made by Panasonic Corporation
Terminal block
DIN rail stopper
.
WARNING
Never use this product with a device for personnel protection.
In case of using devices for personnel protection, use products
which meet laws and standards, such as OSHA, ANSI or IEC etc., for personnel protection applicable in each region or country. Before touching this product, remove any electrostatic charges
that may be present on your body. There is a danger of this product getting damaged due to the electrostatic charge.
SPECIFICATIONS4
Item Model No.
Supply voltage
Current consumption
FAN-in 3
Output (per relay)
Output operation
Number of output points
Transmission indicator
Operation indicator Orange LEDs (lights when the output relay is ON) Output hold function Incorporated Ambient temperature 0 to +55 (No dew condensation), Storage: -20 to +70 Ambient humidity 35 to 85% RH, Storage: 35 to 85% RH
Material
Cable 0.5mm Weight Accessories
Note: 1) This value can change due to the switching frequency, environmental conditions, and desired
reliability level, therefore it is recommended to check this with the actual load.
OUTPUT CIRCUIT DIAGRAM (per channel)
5
Color code
+24 DC (Brown)
S-LINK side
6
OUTPUT HOLD FUNCTION
The output state just before occurrence of an error can be stored
Type 4 channel relay output
(supplied from the S-LINK control unit or separate power supply) 75mA or less (when all outputs are ON, excluding connected devices)
Relay contact 1a
Nominal switching capacity : 250V 2A AC (resistive load)
Min. switching capacity : 5V 1mA DC (Note 1)Expected life: 100,000 operations or more
Mechanical life: 20 million operations or more
Output relay turns ON when the output signal from the signal transmission line is ON.
Green LED (blinks to indicate the synchronization signal transmission from the S-LINK control unit)
Case: PC-ABS resin, Cover: Polycarbonate DIN rail stopper: POM, Relay removal key: POM
Cover: 1 pc., Switch cap: 1 pc., Relay removal key: 1 pc.
D (White)
G (Black)
0V (Blue)
Main circuit
Internal circuit Output device side
SL-TPR4 SL-TPR8
(at rated voltage, switching rate 20 operations/min.)
4 points 8 points
approx 100g. approx 150g.
24V DC±10%
30V 2A DC (resistive load)
2
4-core flat cable 0.6m
Output relay
at the time of a shut-down on the signal transmission line. Hold ON (output stored) or Hold Clear (output not stored) can be
set by the output hold setting switch.
Hold ON Hold Clear
Output hold setting switch
Output stored
Output not stored
8 channel relay output
130mA or less (when all outputs are ON, excluding connected devices)
(switching rate 180 operations/min.)
SL-TPR4: Output 0 to 3
Output
SL-TPR8: Output 0 to 7
Output hold setting switch
The output hold function may not operate correctly under the following conditions:
1.
If the power supply connected to the control unit switches off slowly.
If it takes 5 sec., or more, for the supply voltage to fall from 24V to 10V.
2.
If the output is directly driven by a signal from an S-LINK input unit having the same address.
3.
If a control unit which does not have the mark is used.
MOUNTING
7
In case of mounting on DIN rail
Press in the DIN rail stopper
DIN rail stopper
beforehand. Fit the terminal unit rear portion
on the 35mm width DIN rail. Press down the terminal unit
front portion on the 35mm width DIN rail to fit it.
To dismantle, insert a flathead
*
35mm width DIN rail
Flathead screw driver
screwdriver in the DIN rail stopper and pull it out till it locks. Now, the terminal unit can be removed.
In case of mounting with screws
In case of mounting with screws, use M4 pan-head screws and the tightening torque should be 0.8Nm or less.
Cover
CLR.
ADDRESS
ON
HOLD
ON
3264
16 48 2
1
SEND
24V
0V
S-LINK
D
RELAY TERMINAL
G
BROWN
BLUE
WHITE
MADE IN JAPAN
BLACK
DIN rail stopper
M4 pan-head screw
Please arrange separately.
CLR.
ADDRESS
ON
HOLD
ON
1632 64 48 2
1
SEND
24V
0V
S-LINK
D
RELAY TERMINAL
G
BROWN
BLUE
WHITE
MADE IN JAPAN
BLACK
ADDRESS SETTING8
Make sure to switch off the power supply and remove electrostatic change from your body before carrying out address setting.
Address Nos. have been assigned to the
address setting switch as shown in the right figure.
Address setting switch
SL-TPR4
Output
Output 0 Output 1 Output 2 Output 3
Address
85 86 87 88
SL-TPR8
Output
Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7
Address
85 86 87 88 89 90 91 92
In case the first address is set outside the setting range, the outputs which are assigned addresses exceeding 127 cannot be used.
9
CONNECTION
●・Connection to 4-core flat cable
If the exclusive flat cable has been used for the S-LINK main /
Match the wire colors
Exclusive hook-up connector
Main / branch cable
branch cable, use the optional exclusive hook-up connectors to connect the 4-core flat cable of SL-TPR4 and SL-TPR8 to the main / branch cable by matching the wire colors.
4-core flat cable
CLR.
ADDRESS
ON
HOLD
ON
64
1632
48
2
1
SEND
24V
0V
S-LINK
D
RELAY TERMINAL
G
BROWN
BLUE
WHITE
MADE IN JAPAN
BLACK
●・Wiring on a terminal block
Use crimp terminals having dimensions given in the table below for wiring on a terminal block.
Dimensions of suitable crimp terminals
Y type Round type
5.6 3 or more
or less
4.5
4
or more
When using the above crimp terminals, the suitable wire conduc-
5.6
or less
4
tor cross-section area is 0.25 to 1.65mm The tightening torque should be 0.3 to 0.5Nm.
Since the terminal block is divided into upper and lower levels,
φ
4.5
or more
2
.
(Unit: mm)
3 or more
please make connection to the lower level first.
Plus screwdriver
1 2 4 8 16 32 64
The sum of the address Nos. for which the address setting
switch has been set to the 'ON' side becomes the first address. The setting range for the first address is
SL-TPR4: 0 to 124 SL-TPR8: 0 to 120
Example: In case the first address is to be set to 85
First address = 85
Address setting switch
= 64 + 16 + 4 + 1
1 2 4 8 16 32 64
ON ON ON ON
1 4 16 64 85
When the first address has been set, address for 4 outputs in
case of SL-TPR4, and for 8 outputs in case of SL-TPR8, are automatically assigned in the ascending order.
Example: If the first address is set to 85, the output addresses are
automatically assigned in the ascending order as shown below.
Terminal arrangement diagram
SL-TPR4
Terminal No.
Output 2
Output 3
Upper level side
Lower level side
DIN rail stopper
Output
Output 0 Output 1 Output 2 Output 3
Terminal No.
5 6 7 8 1 2 3 4
Output 0
Output 1
5 6 7 8
1 2 3 4
SL-TPR8
Output 0
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
9
10 11 12
1 2 3 4
13 14 15 16
5 6 7 8
DIN rail stopper
Output
Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7
Terminal No.
9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8
Output 7
Terminal No.
Upper level side
Lower level side