INSTRUCTION MANUAL
Sensor & Wire-saving Link System S-LINK
Relay Output Terminal Unit
SL-TPR4, SL-TPR8
MJE-SLTPR No.0063-18V
Thank you very much for purchasing Panasonic products. Read
this Instruction Manual carefully and thoroughly for the correct
and optimum use of this product. Kindly keep this manual in a
convenient place for quick reference.
1
OVERVIEW
This product is an ultra-small S-LINK relay output terminal unit
which permits relay replacement.
PART DESCRIPTION
2
● SL-TPR4 / 4 channel relay output type
4-core flat cable 0.6m long
Address setting switch
Setting switch section
Switch cap removed
condition
Transmission indicator (Green)
Relay removal key
2-mounting holes for M4 screws
●
SL-TPR8 / 8 channel relay output type
4-core flat cable 0.6m long
Address setting switch
Setting switch section
Switch cap removed
condition
Transmission indicator (Green)
Relay removal key
2-mounting holes for M4 screws
PRECAUTIONS
3
Make sure that the power supply is off while wiring
●
Switch on the power supply after confirming that the wiring is
●
correct. If the power supply is switched on when the wiring is
incorrect, there is a danger of malfunction or damage.
Do not use during the initial transient time (0.5 sec.) after the
●
power supply is switched on.
If power is supplied from a commercial switching regulator,
●
ensure that the frame ground (F.G.) terminal of the power
supply is connected to an actual ground.
Do not run the wires together with high-voltage lines or power
●
lines or put them in the same raceway. This can cause
malfunction due to induction.
A switch cap is fitted on the setting switch section. Remove
●
the cap at the time of setting. After the setting, make sure to fit
it back.
Use tweezers, etc., having a tip width of approx. 0.8mm to
●
operate the switches.
This product does not have a dust-proof or water-proof
●
construction. Do not use it in places having excessive water
vapor, dust, corrosive gas or where it may come in direct
contact with water or chemicals.
Make sure to fit the cover before use.
●
Output hold setting switch
4-operation indicators (Orange)
output relays (4relays)
PA-N Relay APAN3124
made by Panasonic
Corporation
Terminal block
DIN rail stopper
Output hold setting switch
8-operation indicators (Orange)
output relays(8relays)
PA-N Relay APAN3124
made by Panasonic
Corporation
Terminal block
DIN rail stopper
.
WARNING
Never use this product with a device for personnel protection.
・
In case of using devices for personnel protection, use products
・
which meet laws and standards, such as OSHA, ANSI or IEC
etc., for personnel protection applicable in each region or
country.
Before touching this product, remove any electrostatic charges
・
that may be present on your body. There is a danger of this
product getting damaged due to the electrostatic charge.
SPECIFICATIONS4
Item Model No.
Supply voltage
Current consumption
FAN-in 3
Output
(per relay)
Output operation
Number of output points
Transmission indicator
Operation indicator Orange LEDs (lights when the output relay is ON)
Output hold function Incorporated
Ambient temperature 0 to +55℃ (No dew condensation), Storage: -20 to +70℃
Ambient humidity 35 to 85% RH, Storage: 35 to 85% RH
Material
Cable 0.5mm
Weight
Accessories
Note: 1) This value can change due to the switching frequency, environmental conditions, and desired
reliability level, therefore it is recommended to check this with the actual load.
OUTPUT CIRCUIT DIAGRAM (per channel)
5
Color code
+24V DC (Brown)
S-LINK side
6
OUTPUT HOLD FUNCTION
The output state just before occurrence of an error can be stored
●
Type 4 channel relay output
(supplied from the S-LINK control unit or separate power supply)
75mA or less (when all outputs are
ON, excluding connected devices)
Relay contact 1a
・Nominal switching capacity : 250V 2A AC (resistive load)
・Min. switching capacity : 5V 1mA DC (Note 1)
・Expected life: 100,000 operations or more
・Mechanical life: 20 million operations or more
Output relay turns ON when the output signal from the signal
transmission line is ON.
Green LED (blinks to indicate the synchronization signal
transmission from the S-LINK control unit)
Case: PC-ABS resin, Cover: Polycarbonate
DIN rail stopper: POM, Relay removal key: POM
Cover: 1 pc., Switch cap: 1 pc., Relay removal key: 1 pc.
D (White)
G (Black)
0V (Blue)
Main circuit
Internal circuit Output device side
SL-TPR4 SL-TPR8
(at rated voltage, switching rate 20 operations/min.)
4 points 8 points
approx 100g. approx 150g.
24V DC±10%
30V 2A DC (resistive load)
2
4-core flat cable 0.6m
Output relay
at the time of a shut-down on the signal transmission line.
Hold ON (output stored) or Hold Clear (output not stored) can be
●
set by the output hold setting switch.
Hold ON Hold Clear
Output hold
setting switch
Output stored
Output not stored
8 channel relay output
130mA or less (when all outputs are
ON, excluding connected devices)
(switching rate 180 operations/min.)
SL-TPR4: Output 0 to 3
Output
SL-TPR8: Output 0 to 7
Output hold
setting switch

The output hold function may not operate correctly under the
following conditions:
1.
If the power supply connected to the control unit switches off slowly.
If it takes 5 sec., or more, for the supply voltage to fall from
24V to 10V.
2.
If the output is directly driven by a signal from an S-LINK input
unit having the same address.
3.
If a control unit which does not have the mark is used.
MOUNTING
7
●
In case of mounting on DIN rail
Press in the DIN rail stopper
①
DIN rail stopper
beforehand.
Fit the terminal unit rear portion
②
on the 35mm width DIN rail.
Press down the terminal unit
③
front portion on the 35mm width
DIN rail to fit it.
To dismantle, insert a flathead
*
②
35mm width DIN rail
Flathead screw driver
①
③
screwdriver in the DIN rail
stopper and pull it out till it
locks. Now, the terminal unit
can be removed.
●
In case of mounting with screws
・
In case of mounting with
screws, use M4 pan-head
screws and the tightening
torque should be 0.8N・m or
less.
Cover
CLR.
ADDRESS
ON
HOLD
ON
3264
16
48
2
1
SEND
24V
:
0V
S-LINK
D
:
RELAY TERMINAL
G
:
BROWN
:
BLUE
WHITE
MADE IN JAPAN
BLACK
DIN rail stopper
M4 pan-head
screw
Please arrange
separately.
CLR.
ADDRESS
ON
HOLD
ON
1632 64
48
2
1
SEND
24V
:
0V
S-LINK
D
:
RELAY TERMINAL
G
:
BROWN
:
BLUE
WHITE
MADE IN JAPAN
BLACK
ADDRESS SETTING8
Make sure to switch off the power supply and remove electrostatic
change from your body before carrying out address setting.
Address Nos. have been assigned to the
●
address setting switch as shown in the right
figure.
Address setting switch
SL-TPR4
Output
Output 0 Output 1 Output 2 Output 3
Address
85 86 87 88
SL-TPR8
Output
Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7
Address
85 86 87 88 89 90 91 92
In case the first address is set outside the setting range, the outputs
which are assigned addresses exceeding 127 cannot be used.
9
CONNECTION
●・Connection to 4-core flat cable
If the exclusive flat cable has
been used for the S-LINK main /
Match the
wire colors
Exclusive hook-up
connector
Main / branch cable
branch cable, use the optional
exclusive hook-up connectors to
connect the 4-core flat cable of
SL-TPR4 and SL-TPR8 to the
main / branch cable by matching
the wire colors.
4-core flat cable
CLR.
ADDRESS
ON
HOLD
ON
64
1632
48
2
1
SEND
24V
:
0V
S-LINK
D
:
RELAY TERMINAL
G
:
BROWN
:
BLUE
WHITE
MADE IN JAPAN
BLACK
●・Wiring on a terminal block
Use crimp terminals having dimensions given in the table below
for wiring on a terminal block.
Dimensions of suitable crimp terminals
Y type Round type
5.6
3 or more
or less
4.5
4
or more
When using the above crimp terminals, the suitable wire conduc-
・
5.6
or less
4
tor cross-section area is 0.25 to 1.65mm
The tightening torque should be 0.3 to 0.5N・m.
・
Since the terminal block is divided into upper and lower levels,
・
φ
4.5
or more
2
.
(Unit: mm)
3 or more
please make connection to the lower level first.
Plus screwdriver
1 2 4 8 16 32 64
The sum of the address Nos. for which the address setting
●
switch has been set to the 'ON' side becomes the first address.
The setting range for the first address is
SL-TPR4: 0 to 124
SL-TPR8: 0 to 120
Example: In case the first address is to be set to 85
First address = 85
・
Address setting switch
= 64 + 16 + 4 + 1
1 2 4 8 16 32 64
ON ON ON ON
1 + 4 + 16 + 64 = 85
When the first address has been set, address for 4 outputs in
●
case of SL-TPR4, and for 8 outputs in case of SL-TPR8, are
automatically assigned in the ascending order.
Example: If the first address is set to 85, the output addresses are
automatically assigned in the ascending order as shown
below.
●
Terminal arrangement diagram
SL-TPR4
Terminal No.
Output 2
Output 3
Upper level side
Lower level side
DIN rail stopper
Output
Output 0 Output 1 Output 2 Output 3
Terminal
No.
5 6 7 8
1 2 3 4
Output 0
Output 1
5 6 7 8
1 2 3 4
SL-TPR8
Output 0
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
9
10 11 12
1 2 3 4
13 14 15 16
5 6 7 8
DIN rail stopper
Output
Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7
Terminal
No.
9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8
Output 7
Terminal No.
Upper level side
Lower level side