Panasonic R410A User Manual

TECHNICAL & SERVICE MANUAL

INDOOR UNIT :
CS-MKS9NB4U & CZ-18BT1U CS-MKS12NB4U& CZ-18BT1U CS-KS18NB4UW& CZ-18BT1U
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
Capacity
9,000BTU / h
11,900BTU / h
17,500BTU / h
Indoor Model No.
Body (Panel)
CS-MKS9NB4U (CZ-18BT1U)
CS-MKS12NB4U (CZ-18BT1U)
CS-KS18NB4UW (CZ-18BT1U)
Semi-Concealed Type Indoor Unit
Product Code No.
Body (Panel)
Body
Panel
CS-MKS9NB4U (Body) & CZ-18BT1U (Panel) CS-MKS12NB4U (Body) & CZ-18BT1U(Panel) CS-KS18NB4UW (Body) & CZ-18BT1U(Panel)
< Applicable Multi-Outdoor Units >
CU-3KS19NBU (3-room multi unit) CU-4KS24NBU (4-room multi unit) CU-4KS31NBU (4-room multi unit)
Remote Controller
Wired Remote Controller
(Option)
REFERENCE NO. SM700881

SAFETY PRECAUTIONS

• Before doing repair work, please read the " SAFETY PRECAUTIONS" carefully and fully understand them.
• The precautionary items here are divided into " Warning" and " Caution" items. Items in particular which may cause death or serious injury to the service personnel if the work is not performed correctly, are included in the " Warning" table. However, even precautionary items identified as " Caution" also have the potential for serious consequences if not performed correctly. Important safety precautions are described for all items in both categories. Be sure to carefully follow all of them.
• Symbol Indication
: This symbol indicates items to which we need to pay attention.
In this triangle, a definite precautionary item is described.
: This symbol indicates the item to be prohibited.
In or close to this circle, a prohibited item is described.
: This symbol indicates the items requiring special attention or instruction.
In or close to this circle, a prohibited item is described.
• After doing repair work, perform a test run to confirm that there are no abnormalities. At the same time, explain the precautions in use to the user.
Warning
Before performing an overhaul, disconnect the power plug or power cable from the unit. Performing the work with the power supplied to the unit, may cause an electric shock.
When repair work or circuit inspection that requires power supply for the air conditioner, is to be performed, do not touch the charging section. Doing so may cause an electric shock.
Prohibit
For the step-up capacitor attached to the electric section, perform the repair work after sufficiently discharging it. Insufficient capacitor discharge may cause an electric shock.
Do not perform repair work on the electric sections with wet hands. Doing so may cause an electric shock.
Do not start or stop the air conditioner by means of connecting or disconnecting the power plug. Doing so may cause an electric shock or fire.
When conducting repair work only use components included in the parts list for the corresponding unit and perform the work with the appropriate tools. Incorrect or poor repair work may cause an electric shock or fire.
Never modify the unit. Doing so may cause an electric shock or fire.
Perform all electric work according to local applicable regulations related to electrical equipment or interior wiring regulation and make sure to use the exclusive circuit. Insufficient capacity to the electric circuit or defective arrangement results may cause an electric shock or fire.
Make sure to replace any power cable or lead wire showing any signs of scratch or deterioration. Failure to do so may cause an electric shock, overheating or fire.
Make sure that there is no dust on or slack in the power plug and insert fully into the socket. Dust or incomplete connections may cause an electric shock or fire.
Do not damage or process the power cord, as it may cause an electric shock or fire.
Prohibit
Prohibit
Prohibit
Prohibit
For the wiring between the indoor unit and outdoor unit, securely fix the specified cable onto the terminal plate. Poorly fixed wiring may cause a heat or fire.
After connecting the wiring between the indoor unit and outdoor unit, attach the terminal cover securely. Incomplete attachment of the terminal cover may cause overheating or fire.
2
Warning
If refrigerant gas blows off during the work, do not touch the refrigerant gas as it may cause frostbite.
If refrigerant gas leaks during the work, ventilate the room. If refrigerant gas catches fire, harmful gas may be generated.
Do not mix any gas other than the specified refrigerant gas in the refrigerating cycle. If air or other contaminants mix with the gas, pressure will become extremely high in the refrigerating cycle, which may cause a unit breakdown."
When the welded section of the compressor intake or discharge pipe is to be disconnected, perform it in a well-ventilated place after sufficiently recovering the refrigerant gas. Any residue gas may jet out refrigerant or refrigerating machine oil, which may cause an injury.
When the work is to be performed in a high place (About 2 meters or more), make sure to wear a safety helmet, gloves and safety belt. Insufficient safety gear may cause a serious injury in case of a fall.
When the unit is to be relocated, confirm that the new installation location has sufficient strength for the weight of the unit. Insufficient strength of the installation location and incomplete installation work may cause an injury due to the unit falling.
When the remote controller batteries are replaced, dispose of the old batteries out of the reach of children. If a child swallows a battery, make sure that the child gets immediate medical attention.
Caution
Prohibit
Prohibit
Do not wash the air conditioner with water, as this may cause an electric shock or fire.
For the repair work in places with high humidity or moisture, make sure to ground the unit. Failure to do so may cause an electric shock.
Confirm that the component attachment position, wiring condition, soldering condition and connector connection are normal. If not, it may cause overheating or fire.
Confirm that the temperature around the compressor is not too high, and then perform the repair work. Failure to do so may cause a burn.
Perform welding work in a place with good ventilation. If the work is performed in a poorly ventilated area, it might cause a lack of oxygen.
If the installation plate or attachment frame has deteriorated due to corrosion, etc., replace it. Failure to do so may cause an injury due to the unit falling.
When the cleaning is to be performed, make sure to turn off the power and pull out the plug. Touching the fan that is rotating at high speed may result in an injury.
When the indoor unit is to be removed, do not place it on an incline. Doing so may cause wet furniture because water left inside may trickle down.
Do not hold the sharp end of the unit or the aluminum fins, as it may cause an injury to your hand or finger.
Prohibit
Prohibit
Prohibit
After repairs, make sure to measure the insulation resistance and confirm that the value is 1 Mohm or more. Any insulation error may cause an electric shock.
After repairs, make sure to check the drainage of the indoor unit. Inappropriate drainage may cause wet furniture and floors due to water leakage.
3

TABLE OF CONTENTS

Page
SAFETY PRECAUTIONS
TABLE OF CONTENTS
APPLICABLE MULTI-OUTDOOR UNITS
1. OPERATING RANGE
2. SPECIFICATIONS
2-1. Unit Specifications 2-2. Major Component Specifications 2-3. Other Component Specifications
3. DIMENSIONAL DATA
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
5. ELECTRICAL DATA
5-1. Electric Wiring Diagrams
..............................................................................................................
...................................................................................................................
...................................................................................................................
.............................................................................................................
....................................................................................................................
..................................................................................................
....................................................................................................
....................................................................................
.......................................................................................
.......................................................................................
2
4
6
7
8 14 17
18
19
20
6. MAINTENANCE
6-1. Disassembly Procedure
7. FUNCTIONS
7-1. Operation Functions 7-2. Protective Functions
8.TROUBLESHOOTING (BEFORE CALLING FOR SERVICE)
8-1. Precautions before Performing Inspection or Repair 8-2. Method of Self-Diagnostics 8-3. Checking the Indoor and Outdoor Units 8-4. Trouble Diagnosis of Fan Motor 8-5. Noise Malfunction and Electromagnetic Interference
APPENDIX A Operating Instructions CS-MKS9NB4U & CZ-18BT1U , CS-MKS12NB4U & CZ-18BT1U
APPENDIX B Operating Instructions (CS-KS18NB4UW & CZ-18BT1U)
APPENDIX C INSTALLATION INSTRUCTIONS CS-MKS9NB4U & CZ-18BT1U , CS-MKS12NB4U & CZ-18BT1U , CS-KS18NB4UW & CZ-18BT1U
()
.....................................................................................................
...........................................................................................................
...........................................................................................................
..........................................................
.................................................................................................
..............................................................................
..........................................................................................
..........................................................
............................................................................................
............................................................................................
.............................................................................
21
28 30
31 31 33 37 38
A-1
A-2
A-3
4
Page
APPENDIX D Operating Instructions
............................................................................................
(CZ-RD515U)
APPENDIX E INSTALLATION INSTRUCTIONS (CZ-RD515U)
............................................................................
A-4
A-5
5
APPLICABLE MULTI-OUTDOOR UNITS
Multi-Outdoor Unit
Indoor Unit
CS-MKS9NB4U & CZ-18BT1U
CS-MKS12NB4U & CZ-18BT1U
CS-KS18NB4UW & CZ-18BT1U
3-Room
CU-3KS19NBU
YES
YES
YES
4-Room
CU-4KS24NBU
YES
YES
YES
4-Room
CU-4KS31NBU
YES
YES
YES
6

1. OPERATING RANGE

Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum
Minimum
95 °F DB / 71 °F WB
67 °F DB / 57 °F WB
115 °F DB
14 °F DB
7

2. SPECIFICATIONS

2-1. Unit Specifications

2-1-1.
Type
Voltage Rating
Performance
Electrical Rating
Features
Indoor Unit CS-MKS9NB4U & CZ-18BT1U
Semi-Concealed Type Indoor Unit
230V Single-Phase 60Hz
Total Capacity
Air Circulation (Hi/Me/Lo) ft Moisture Removal (High) Pints/h Available Voltage Range Running Amperes
--
Controls / Temperature Control Control Unit Timer
Airflow Direction (Indoor) Horizontal
Air Filter Refrigerant Operation Sound Refrigerant Tubing Connections Refrigerant inch (mm) Tube Diameter inch (mm) Wired Remote Controller (Option) CZ-RD515U
Narrow tube Wide tube
BTU/h
3
/min (m3/h)
IndoorFan Speeds
Vertical
dB-AIndoor : Hi/Me/Lo
kW
WPower Input
221(376)/206(350)/194(330)
V A
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps
Washable, Anti-Mold
33 / 32 / 31
Flare Type
<230V>
Cooling
9,000
2.65
3.4
187 to 253
0.1 16
-
Auto
R410A
1/4 (6.35) 3/8 (9.52)
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width Depth
Package Dimensions Height
Width Depth 28-1/8 (714)
Weight Ib. (kg)
Shipping Volume
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80 °F DB / 67 °F WB
Outdoor air temperature 95 °F DB / 75 °F WB
Net Shipping
Indoor Unit
(CS-MKS9NB4U & CZ-18BT1U)
inch (mm) (313)12-5/16
inch (mm) 22-5/8 (575) inch (mm) inch (mm) -
inch (mm) 24-13/16 (630) inch (mm)
Ib. (kg)
cu.ft (m
3
)
(625)24-19/32 (625)24-19/32
-
­(18.7)41.3
-
-
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
(CS-MKS9NB4U)
11-5/32 (283)
11-13/32 (290)
Individual Unit
Body
22-5/8 (575)
35.3 (16)
41.9 (19)
4.59 (0.13)
Panel
(CZ-18BT1U)
1-9/16 (40)
24-19/32 (625) 24-19/32 (625)
4-1/8 (105)
26-3/16 (665)
26-11/16 (678)
6.0 (2.7)
7.7 (3.5)
1.65 (0.04)
8
Indoor Unit CS-MKS9NB4U & CZ-18BT1U
Type
Voltage Rating
Total Capacity
BTU/h
kW
Air Circulation (Hi/Me/Lo) ft3/min (m3/h)
Performance
Moisture Removal (High) Pints/h Available Voltage Range Running Amperes
V A
WPower Input
--
Electrical Rating
Controls / Temperature Control Control Unit Timer
IndoorFan Speeds
Airflow Direction (Indoor) Horizontal
Vertical Air Filter Refrigerant
Features
Operation Sound
dB-AIndoor : Hi/Me/Lo Refrigerant Tubing Connections Refrigerant inch (mm) Tube Diameter inch (mm)
Narrow tube Wide tube
Wired Remote Controller (Option) CZ-RD515U
Semi-Concealed Type Indoor Unit
208V Single-Phase 60Hz
221(376)/206(350)/194(330)
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps
Washable, Anti-Mold
<208V>
Cooling
9,000
2.65
3.4
187 to 253
0.11 15
-
Auto
R410A
33 / 32 / 31
Flare Type
1/4 (6.35) 3/8 (9.52)
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width Depth
Package Dimensions Height
Width Depth 28-1/8 (714)
Weight Ib. (kg)
Shipping Volume
Net Shipping
Remarks: Rating conditions are:
Cooling: Indoor air temperature
Outdoor air temperature
80 °F DB / 67 °F WB 95 °F DB / 75 °F WB
Indoor Unit
(CS-MKS9NB4U & CZ-18BT1U)
inch (mm) (313)12-5/16
inch (mm) 22-5/8 (575) inch (mm) inch (mm) -
inch (mm) 24-13/16 (630) inch (mm)
Ib. (kg)
cu.ft (m
3
)
(625)24-19/32 (625)24-19/32
-
­(18.7)41.3
-
-
(CS-MKS9NB4U)
11-5/32 (283)
11-13/32 (290)
Individual Unit
Body
22-5/8 (575)
35.3 (16)
41.9 (19)
4.59 (0.13)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Panel
(CZ-18BTCS)
1-9/16 (40)
24-19/32 (625) 24-19/32 (625)
4-1/8 (105)
26-3/16 (665)
26-11/16 (678)
6.0 (2.7)
7.7 (3.5)
1.65 (0.04)
9
Indoor Unit CS-MKS12NB4U & CZ-18BT1U
Type
Voltage Rating
Total Capacity
BTU/h
kW
Air Circulation (Hi/Me/Lo) ft
Performance
Moisture Removal (High) Pints/h Available Voltage Range Running Amperes
3
/min (m3/h)
V A
WPower Input
--
Electrical Rating
Controls / Temperature Control Control Unit Timer
IndoorFan Speeds
Airflow Direction (Indoor) Horizontal
Vertical Air Filter Refrigerant
Features
Operation Sound
dB-AIndoor : Hi/Me/Lo Refrigerant Tubing Connections Refrigerant inch (mm) Tube Diameter inch (mm)
Narrow tube Wide tube
Wired Remote Controller (Option) CZ-RD515U
Semi-Concealed Type Indoor Unit
230V Single-Phase 60Hz
235(399)/206(350)/194(330)
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps
Washable, Anti-Mold
<230V>
Cooling
11,900
3.5
4.26
187 to 253
0.11 17
-
Auto
R410A
34 / 32 / 31
Flare Type
1/4 (6.35) 3/8 (9.52)
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width Depth
Package Dimensions Height
Width Depth 28-1/8 (714)
Weight Ib. (kg)
Shipping Volume
Net Shipping
Remarks: Rating conditions are:
Cooling: Indoor air temperature
Outdoor air temperature
80 °F DB / 67 °F WB 95 °F DB / 75 °F WB
Indoor Unit
(CS-MKS12NB4U & CZ-18BT1U)
inch (mm) (313)12-5/16
inch (mm) 22-5/8 (575) inch (mm) inch (mm) -
inch (mm) 24-13/16 (630) inch (mm)
Ib. (kg)
cu.ft (m
3
)
(625)24-19/32 (625)24-19/32
-
­(18.7)41.3
-
-
(CS-MKS12NB4U)
11-5/32 (283)
11-13/32 (290)
Individual Unit
Body
22-5/8 (575)
35.3 (16)
41.9 (19)
4.59 (0.13)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Panel
(CZ-18BT1U)
1-9/16 (40)
24-19/32 (625) 24-19/32 (625)
4-1/8 (105)
26-3/16 (665)
26-11/16 (678)
6.0 (2.7)
7.7 (3.5)
1.65 (0.04)
10
Indoor Unit CS-MKS12NB4U & CZ-18BT1U
Type
Voltage Rating
Total Capacity
BTU/h
kW
Air Circulation (Hi/Me/Lo) ft3/min (m3/h)
Performance
Moisture Removal (High) Pints/h Available Voltage Range Running Amperes
V A
WPower Input
--
Electrical Rating
Controls / Temperature Control Control Unit Timer
IndoorFan Speeds
Airflow Direction (Indoor) Horizontal
Vertical Air Filter Refrigerant
Features
Operation Sound
dB-AIndoor : Hi/Me/Lo Refrigerant Tubing Connections Refrigerant inch (mm) Tube Diameter inch (mm)
Narrow tube Wide tube
Wired Remote Controller (Option) CZ-RD515U
Semi-Concealed Type Indoor Unit
208V Single-Phase 60Hz
235(399)/206(350)/194(330)
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps
Washable, Anti-Mold
<208V>
Cooling
11,900
3.5
4.26
187 to 253
0.12 16
-
Auto
R410A
34 / 32 / 31
Flare Type
1/4 (6.35) 3/8 (9.52)
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width Depth
Package Dimensions Height
Width Depth 28-1/8 (714)
Weight Ib. (kg)
Shipping Volume
Net Shipping
Remarks: Rating conditions are:
Cooling: Indoor air temperature
Outdoor air temperature
80 °F DB / 67 °F WB 95 °F DB / 75 °F WB
Indoor Unit
(CS-MKS12NB4U & CZ-18BT1U)
inch (mm) (313)12-5/16
inch (mm) 22-5/8 (575) inch (mm) inch (mm) -
inch (mm) 24-13/16 (630) inch (mm)
Ib. (kg)
cu.ft (m
3
)
(625)24-19/32 (625)24-19/32
-
­(18.7)41.3
-
-
(CS-MKS12NB4U)
11-5/32 (283)
11-13/32 (290)
Individual Unit
Body
22-5/8 (575)
35.3 (16)
41.9 (19)
4.59 (0.13)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Panel
(CZ-18BT1U)
1-9/16 (40)
24-19/32 (625) 24-19/32 (625)
4-1/8 (105)
26-3/16 (665)
26-11/16 (678)
6.0 (2.7)
7.7 (3.5)
1.65 (0.04)
11
Indoor Unit CS-KS18NB4UW & CZ-18BT1U
Type
Voltage Rating
Total Capacity
BTU/h
kW
Air Circulation (Hi/Me/Lo) ft
Performance
Moisture Removal (High) Pints/h Available Voltage Range Running Amperes
3
/min (m3/h)
V A
WPower Input
--
Electrical Rating
Controls / Temperature Control Control Unit Timer
IndoorFan Speeds
Airflow Direction (Indoor) Horizontal
Vertical Air Filter Refrigerant
Features
Operation Sound
dB-AIndoor : Hi/Me/Lo Refrigerant Tubing Connections Refrigerant inch (mm) Tube Diameter inch (mm)
Narrow tube Wide tube
Wired Remote Controller (Option) CZ-RD515U
Semi-Concealed Type Indoor Unit
230V Single-Phase 60Hz
341(579)/294(500)/253(430)
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps
Washable, Anti-Mold
<230V>
Cooling
17,500
5.15
4.89
187 to 253
0.15 22
-
Auto
R410A
44 / 40 / 36
Flare Type
1/4 (6.35) 1/2 (12.7)
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width Depth
Package Dimensions Height
Width Depth 28-1/8 (714)
Weight Ib. (kg)
Shipping Volume
Net Shipping
Remarks: Rating conditions are:
Cooling: Indoor air temperature
Outdoor air temperature
80 °F DB / 67 °F WB 95 °F DB / 75 °F WB
Indoor Unit
(CS-KS18NB4UW & CZ-18BT1U)
inch (mm) (313)12-5/16
inch (mm) 22-5/8 (575) inch (mm) inch (mm) -
inch (mm) 24-13/16 (630) inch (mm)
Ib. (kg)
cu.ft (m
3
)
(625)24-19/32 (625)24-19/32
-
­(18.7)41.3
-
-
(CS-KS18NB4UW)
11-5/32 (283)
11-13/32 (290)
Individual Unit
Body
22-5/8 (575)
35.3 (16)
41.9 (19)
4.59 (0.13)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Panel
(CZ-18BT1U)
1-9/16 (40)
24-19/32 (625) 24-19/32 (625)
4-1/8 (105)
26-3/16 (665)
26-11/16 (678)
6.0 (2.7)
7.7 (3.5)
1.65 (0.04)
12
Indoor Unit CS-KS18NB4UW & CZ-18BT1U
Type
Voltage Rating
Total Capacity
BTU/h
kW
Air Circulation (Hi/Me/Lo) ft
Performance
Moisture Removal (High) Pints/h Available Voltage Range Running Amperes
3
/min (m3/h)
V A
WPower Input
--
Electrical Rating
Controls / Temperature Control Control Unit Timer
IndoorFan Speeds
Airflow Direction (Indoor) Horizontal
Vertical Air Filter Refrigerant
Features
Operation Sound
dB-AIndoor : Hi/Me/Lo Refrigerant Tubing Connections Refrigerant inch (mm) Tube Diameter inch (mm)
Narrow tube Wide tube
Wired Remote Controller (Option) CZ-RD515U
Semi-Concealed Type Indoor Unit
208V Single-Phase 60Hz
341(579)/294(500)/253(430)
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps
Washable, Anti-Mold
<208V>
Cooling
17,500
5.15
4.89
187 to 253
0.16 22
-
Auto
R410A
44 / 40 / 36
Flare Type
1/4 (6.35) 1/2 (12.7)
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width Depth
Package Dimensions Height
Width Depth 28-1/8 (714)
Weight Ib. (kg)
Shipping Volume
Net Shipping
Remarks: Rating conditions are:
Cooling: Indoor air temperature
Outdoor air temperature
80 °F DB / 67 °F WB 95 °F DB / 75 °F WB
Indoor Unit
(CS-KS18NB4UW & CZ-18BT1U)
inch (mm) (313)12-5/16
inch (mm) 22-5/8 (575) inch (mm) inch (mm) -
inch (mm) 24-13/16 (630) inch (mm)
Ib. (kg)
cu.ft (m
3
)
(625)24-19/32 (625)24-19/32
-
­(18.7)41.3
-
-
(CS-KS18NB4UW)
11-5/32 (283)
11-13/32 (290)
Individual Unit
Body
22-5/8 (575)
35.3 (16)
41.9 (19)
4.59 (0.13)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Panel
(CZ-18BT1U)
1-9/16 (40)
24-19/32 (625) 24-19/32 (625)
4-1/8 (105)
26-3/16 (665)
26-11/16 (678)
6.0 (2.7)
7.7 (3.5)
1.65 (0.04)
13

2-2. Major Component Specifications

2-2-1. Indoor Unit
Indoor Unit (Body) CS-MKS9NB4U
Control PCB
Part No.
Controls
Control Circuit Fuse
Fan
Type Q'ty ... Dia. and Length
Fan Motor
Type Model ... Q'ty No. of Poles Rough Measure RPM (Cool)
Rating Voltage / Nominal Output Coil Resistance
(Ambient Temp. 68 °F (20 °C))
Safety Device
Type Over- Current Protection Over- Heat Protection
Run Capacitor Micro F
inch (mm)
Ohm
VAC
CB-CS-MKS9NB4U
Microprocessor
250V 3A
Turbo
1 ... D12-5/8 / L5-3/4 (D322/L147)
DC Motor
SIC-62FW-D866-2 ... 1
8
440
DC280V / 23W
-
Internal Controller
Yes Yes
-
-
Drain Pump
Model ... Q'ty Rating Voltage, Hz
(Ambient Temp. 68 °F (20 °C)) Safety Device
Heat Exchanger Coil
Coil
Rows Fins per inch
Input
Type Open
W
Ohm
°F (°C)
2
(m2)
ft
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
PLD-12230ST-1 ... 1
AC208 to 240V, 60Hz
Aluminum Plate Fin / Copper Tube
Indoor Unit (Panel) CZ-18BT1U
Flap Motor
Type Stepping Motor
Model ... Q'ty
Rating Coil Resistance Ohm
(Ambient Temp. 77 °F (25 °C))
Each Pair of Terminal : 380 +/- 7%
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
MP24ZN-12V ... 2
10.8
333 +/- 10%Coil Resistance
Thermal Fuse
293 (145)
2
18.1
2.94 (0.273) Face Area
DC 12V
14
Indoor Unit (Body) CS-MKS12NB4U
Control PCB
Part No.
Controls
Control Circuit Fuse
Fan
Type Q'ty ... Dia. and Length
Fan Motor
Type Model ... Q'ty No. of Poles Rough Measure RPM (Cool)
Coil Resistance
(Ambient Temp. 68 °F (20 °C))
Safety Device
Type Over- Current Protection Over- Heat Protection
Run Capacitor Micro F
inch (mm)
Ohm
VAC
CB-CS-MKS12NB4U
Microprocessor
250V 3A
Turbo
1 ... D12-5/8 / L5-3/4 (D322/L147)
DC Motor
SIC-62FW-D866-2 ... 1
8
470
DC280V / 23WRating Voltage / Nominal Output
-
Thermal Fuse
Yes Yes
-
-
Drain Pump
Model ... Q'ty Rating Voltage, Hz
Input
W
PLD-12230ST-1 ... 1
AC208 to 240V, 60Hz
Ohm
(Ambient Temp. 68 °F (20 °C)) Safety Device
Type Open
°F (°C)
Heat Exchanger Coil
Coil
Aluminum Plate Fin / Copper Tube Rows Fins per inch
2
(m2)
ft
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Indoor Unit (Panel) CZ-18BT1U
Flap Motor
Type Stepping Motor
Model ... Q'ty
Rating Coil Resistance Ohm
(Ambient Temp. 77 °F (25 °C))
Each Pair of Terminal : 380 +/- 7%
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
MP24ZN-12V ... 2
10.8
333 +/- 10%Coil Resistance
Thermal Fuse
293 (145)
2
18.1
2.94 (0.273) Face Area
DC 12V
15
Indoor Unit (Body) CS-KS18NB4UW
Control PCB
Part No.
Controls
Control Circuit Fuse
Fan
Type Q'ty ... Dia. and Length
Fan Motor
Type Model ... Q'ty No. of Poles Rough Measure RPM (Cool)
Coil Resistance
(Ambient Temp. 68 °F (20 °C))
Safety Device
Type Over- Current Protection Over- Heat Protection
Run Capacitor Micro F
inch (mm)
Ohm
VAC
CB-CS-KS18NB4U
Microprocessor
250V 3A
Turbo
1 ... D12-5/8 / L5-3/4 (D322/L147)
DC Motor
SIC-62FW-D866-2 ... 1
8
650
DC340V / 20WRating Voltage / Nominal Output
-
Internal Controller
Yes Yes
-
-
Drain Pump
Model ... Q'ty Rating Voltage, Hz
Input
W
PLD-12230ST-1 ... 1
AC208 to 240V, 60Hz
Ohm
(Ambient Temp. 68 °F (20 °C)) Safety Device
Type Open
°F (°C)
Heat Exchanger Coil
Coil
Aluminum Plate Fin / Copper Tube Rows Fins per inch
2
(m2)
ft
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Indoor Unit (Panel) CZ-18BT1U
Flap Motor
Type Stepping Motor
Model ... Q'ty
Rating Coil Resistance Ohm
(Ambient Temp. 77 °F (25 °C))
Each Pair of Terminal : 380 +/- 7%
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
MP24ZN-12V ... 2
10.8
333 +/- 10%Coil Resistance
Thermal Fuse
293 (145)
2
18.1
2.94 (0.273) Face Area
DC 12V
16

2-3. Other Component Specifications

Indoor Unit CS-MKS9NB4U & CZ-18BT1U CS-MKS12NB4U & CZ-18BT1U CS-KS18NB4UW & CZ-18BT1U
• Indoor air temp sensor
(Model:KTEC-35-S98)
10
9
8
7
6
5
Resistance (k ohm)
4
3
2
1
0
59 68 77 86 95 104
50
(10) (15) (20) (25) (30) (35) (40)
Temperature °F (°C)
• Indoor heat exchanger sensor
(Model:PT2M-51H-S3)
200
180
160
140
120
100
Resistance (k ohm)
80
60
40
20
0
32 50 68 86 104 122 140 158 176 194 (0) (10) (20) (30) (40)(50) (60) (70) (80) (90)
Temperature °F (°C)
17

3. DIMENSIONAL DATA

Indoor Unit CS-MKS9NB4U & CZ-18BT1U CS-MKS12NB4U & CZ-18BT1U CS-KS18NB4UW & CZ-18BT1U
7-11/16
8
4-29/32
A View
1-3/16
21/32
3-1/8
(534)
AA
21-1/32
23-5/8 (600)
Suspension bolt pitch
Ceiling opening dimensions
Center of
panel
7
(flared)
1/4" (flared)
dia.
dia. 1/2"
23-5/8 (600)
21-1/32 (534)
Ceiling opening dimensions
Suspension bolt pitch
12-7/16
12-7/8
5
22-5/8 (575)
6-5/16 6-11/16
2-3/32
1-25/32
1-3/16 (30)
11-5/32 (283)
8-15/32
3
6
1-25/32
4-19/32
Less than 31/32 Less than 31/32
The length of the suspension
2
14-3/32 (358)
24-19/32 (625)
2
25/32
bolts should be selected so that
there is a gap of 1-3/16" or
the ceiling (21/32" or more
below the lower surface of the
main unit), as shown in the
figure at right. If the suspension
bolts is too long, it will contact
the ceiling panel and the unit
cannot be installed.
24-19/32 (625)
13-5/32 (334)
2
1
5-9/16
2-3/4 1-9/32
2
(liquid tube)
Air intake
Discharge outlet
Refrigerant tubing
1
2
3
(gas tube)
22-5/8 (575)
Refrigerant tubing
Drain tube connection port VP20 (outer dia. 1")
Power supply port
Suspension bolt hole (4 - 1/2" x 1-1/8" hole)
Fresh air intake duct connection port (dia. 3-7/8")
4
5
6
7
8
18
2-3/32
3-5/8
7-23/32
1-27/32 1-3/32
Unit : inch (mm)

4. REFRIGERANT FLOW DIAGRAM

4-1. Refrigerant Flow Diagram

Indoor Unit CS-MKS9NB4U & CZ-18BT1U CS-MKS12NB4U & CZ-18BT1U
Indoor unit
O.D. 3/8" (9.52 mm)
Heat exchanger
Strainer
Indoor Unit CS-KS18NB4UW & CZ-18BT1U
Indoor unit
Heat exchanger
Strainer
O.D. 1/4" (6.35 mm)
O.D. 1/2" (12.7 mm)
O.D. 1/4" (6.35 mm)
Cooling cycle
Cooling cycle
19

5. ELECTRICAL DATA

5-1. Electric Wiring Diagrams

Indoor Unit CS-MKS9NB4U & CZ-18BT1U CS-MKS12NB4U & CZ-18BT1U CS-KS18NB4UW & CZ-18BT1U
FLAP (R)
FLAP (W)
IND LAMP ASSY
COIL-1
BLK
2
2
BLK
1
1
COIL-1
WHT BRN
BLU
ORG
BLK
2P (RED)
2
2
1
1
ROOM
2P (YEL)
3
3
FS
1
1
3P (RED)
5
5
4
4
3
3
FLAP
2
2
5P (WHT)
1
1
7
7
6
6
5
5
4
4
IND
3
3
7P (WHT)
2
2
1
1
4
4
3
3
2
2
1
1
4P (WHT)
8FA2-5250-46900-2
ROOM
BLK
VLT
BLU PNK YEL
ORG RED BRN
GRN BLK
WHT
BLK
BLK BLK
FLOAT SWITCH
6
6
5
5
4
4
3
3
2
2
1
1
THERMISTOR
ORG
5
5
BLU
4
4
BRN
3
3
WHT
2
2
BLK
1
1
WHT
5
5
BRN
4
4
BLU
3
3
ORG
2
2
BLK
1
1
10
10
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
TERMINAL BASE
2 3
1
TO OUTDOOR UNIT
BRN
DP
DRAIN PUMP
FAN MOTOR
GND
RED
FM
YEL
ORG
GRN/YEL
CORE
FERRITE
PNK
BLU
7
7
6
6
5
5
4
4
3
3
2
2
1
1
VLT
7
7
6
6
5
5
4
4
3
3
2
2
1
1
YEL/(RED)
3
3
YEL/(RED)
1
1
BLU YEL
WHT
BLK
RED
1 2 3 4 5 6
1 2 3 4 5 6
RED
WHT
BLK
PWM/POW 7P (RED) PWM/POW 7P (RED) RC
DP
3P (BLU)
DCM
6P (BLU)
AC1 AC2 SI
SERIAL
2P (WHT)
1 1
2 2
RED
WHT
1 1
2 2
SERIAL
2P (WHT)
3P (RED)
6P (WHT)
GRN
BOX BOX
CONTROLLER CONTROLLER
20

6. MAINTENANCE

6-1. Disassembly Procedure

To avoid electrical shock hazard, be sure to disconnect power before
Warning
6-1-1. Remove the air intake grill.
(1) Slide the 2 latches each to the corresponding arrow direction. (Fig. 1 and Fig. 2)
Open downward the air intake grill located on the latch side.
(2) Undo the air intake grill drop preventive hook. (Fig. 3)
Undo the 2 hinges for the grill and remove the air intake grill.
attempting to disassemble the unit. When a footstool, etc. is used for disassembling the indoor unit, be careful not to fall down. If you fall down, you might be injured seriously.
Latch
Hinge
Latch
Air intake grill
Fig.1
Hinge
Fig.2 Fig.3
6-1-2. Disconnect the connectors in the control box.
(1) Remove the 2 screws and remove the control box cover. (Fig. 4)
(2) Disconnect the connectors CN04 (FLAP 5P), CN12 (RC 4P) and CN13 (IND 7P). (Fig. 5)
Control PCboard
Hook
CN13
CN04
CN12
Screw Control box cover
Fig.4 Fig.5
21
6-1-3. Remove the ceiling panel.
(1) Open the clamp (4 locations) and remove the 2 lead wires from the clamps. (Fig. 6)
(2) Remove the 4 screws fixing the corner cover (at 3 locations) and indicator cover (at 1 location). (Fig. 6)
(3) Press the center 1 of the cover and remove the cover with the section 2 pulled down. (Fig. 7)
(4) Remove the strap (3 locations) from the hook on the ceiling panel. (Fig. 8)
NOTE
(5) Remove the bolt (4 locations) with a washer and remove the ceiling panel. (Fig. 9)
There is no strap on the indicator cover.
Indicator cover
Screw
Screw
Clamp
Corner cover
Lead wire
Clamp
Corner coverCorner cover
Pull down section 2.
Fig.6 Fig.7
Bolt
Cover
Center 1
Strap
Remove the strap from the hook.
Bolt
Fig.8 Fig.9
22
6-1-4. Remove the indoor air temperature sensor.
(1) Disconnect the connector CN08 (ROOM 2P) in the control box and remove the indoor air temperature
sensor. (Fig. 10)
Indoor air temperature sensor
Fig.10
6-1-5. Remove the power box and control box.
(1) Remove a screw and remove the terminal cover. (Fig. 11)
(2) Remove the 2 screws and remove the power box cover. (Fig. 11)
(3) Disconnect the power lines (No. 1 and No. 2) / signal line (No. 3) and ground cable from the terminals in
the power box. (Fig. 12)
CN08
Terminal cover
Screw
Screw
Power box cover
Ground cable
Fig.11
1
2
3
Terminal
Fig.12
23
Power lines / Signal line
(4) Disconnect the connector CN07 (DP 2P) in the power box. (Fig. 13)
Remove a screw and disconnect the ground cable. (Fig. 13)
(5) Disconnect the connector CN03 (DCM 6P) in the power box. (Fig. 14)
(6) Remove the 4 screws and remove the power box. (Fig. 14)
(7) Disconnect the connectors CN06 (FS 3P) and CN09 (COIL-1 2P) in the control box. (Fig. 15)
(8) Remove the 2 screws and remove the control box. (Fig. 15)
Screw
Ground cable
Screw
12 3
CN07
Fig.13
Screw
Screw
Screw
CN03
Fig.14
Screw
CN09
Screw
CN06
Fig.15
24
NOTE
For the removal of the following components, perform any work after removing the indoor
unit (main body) from the ceiling.
Main body lower section Heat exchanger sensor Drain pump
Float switch Turbo fan Fan motor
Heat exchanger
1. Perform the work after draining the water to prevent the water leakage from the drain pan.
Put a bucket, etc., under the drain cap and remove the drain cap to drain the water.
(Fig. 16)
2. Refer to the installation instructions for recovery of refrigerant or removal of the power
cable or tubing.
6-1-6. Remove the main body lower section.
(1) Remove the 4 screws. (Fig. 16)
(2) Remove the 2 screws. (Fig. 17)
(3) Disconnect the connector CN03 (DCM 6P) in the power box. (Fig. 18)
(4) Lift the main body lower section and remove it from the main body upper section.
Screw
Screw
Screw
Drain cap
Main body lower sectionMain body lower section
Screw
Fig.16
Main body lower section
Main body upper section
Screw
CN03
Fig.18Fig.17
25
6-1-7. Remove the heat exchanger sensor.
(1) Remove the heat exchanger sensor from the sensor holder. (Fig. 19)
Fig.19
6-1-8. Remove the drain pump and float switch.
(1) Remove the 2 screws (Fig. 20)
(2) Loosen the clamp and disconnect the drain hose from the drain pump. (Fig. 20)
(3) Remove the drain pump from the main body upper section. (Fig. 20)
(4) Remove a nut and remove the float switch. (Fig. 21)
Heat exchanger sensor
Holder
Drain pump
Screw
Float switch
Nut
Drain hose
Clamp
Fig.20 Fig.21
26
6-1-9. Remove the turbo fan and fan motor.
(1) Remove a nut and remove the turbo fan. (Fig. 22)
(2) Remove the 2 screws and 3 nuts, and remove the fan motor. (Fig. 23)
Turbo fan
Fig.22 Fig.23
6-1-10. Remove the heat exchanger.
(1) Remove the 3 screws. (Fig. 24)
(2) Remove the 3 screws. (Fig. 25)
(3) Remove the heat exchanger from the main body upper section with the heat exchanger lifted.
Nut
Screw Nut
Fan motor
ScrewHeat exchanger
Screw
Fig.24 Fig.25
27
Main body upper section
Screw

7. FUNCTIONS

7-1. Operation Functions

Emergency operation SENSOR DRY
Emergency operation is available when the remote controller malfunctions, has been lost, or otherwise cannot be used.
To operate the system, press the OPERATION button,
which is also used as the receiver, below the unit display.
Each time this button is pressed, the OPERATION lamp changes color to indicate the type of operation. Select the desired type of operation.
COOL STOP
(GREEN) (Lamp Off)
• The set temperature is 4°F(2°C) below the detected room temperature in the case of cooling operation. The flap and fan speed settings are AUTO.
During DRY operation, the system adjusts the room
temperature and fan speed according to the conditions in the room, in order to maintain a comfortable room environment.
SENSOR DRY operation
• DRY operation is as shown in the figure below.
Load
COOL zone
A zone
B zone
Conditions are monitored at all times when the room temperature is below 59°F(15°C).
DRY A
The compressor operation frequency varies. The indoor fan operates with 1/f fluctuation.
DRY B
The compressor operates at a low operating frequency. The indoor fan operates with 1/f fluctuation.
Monitor
• Monitoring operation takes place when the room temperature is below 59°F temperature.
• When the monitoring range is entered, the compressor stops, and the indoor fan operates with 1/f fluctuation.
(15°C), or more than 5°F(3°C) below the set
PAM- control
• In order to further improve inverter performance, control is switched between PWM control at low operation speeds, and PAM control at high operation speeds, making the most effective use of power.
28
HIGH POWER
NIGHT SETBACK
This function acts to raise the power but keeps the AC system in the same operating mode. This function is set with the HIGH POWER button on the remote controller. (It can be set regardless of the temperature and fan speed settings.)
HIGH POWER operation from remote controller The unit operates at maximum output for 30 minutes,
regardless of the desired temperature.
The fan speed is 1 step above "High."
Frequency
MAX
0
30 min. 5 min.
Start End
Time
NOTE
When HIGH POWER operation ends, the unit operates at low
Hz for 5 minutes, regardless of the thermostat OFF conditions.
When in DRY mode, operation is in the cooling zone.
When NIGHT SETBACK operation is set, the temperature and
fan speed settings will be adjusted automatically to allow comfortable sleep.
When NIGHT SETBACK operation is set, " mark" appears on
the remote controller. The main unit display lamp also becomes dimmer.
COOL and DRY modes
When the night setback mode is selected, the air conditioner automatically raises the temperature setting 2°F(1°C) when 30 minutes have passed after the selection was made, and then another 2°F(1°C) after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected. This enables you to save energy without sacrificing comfort. This function is convenient when gentle cooling is needed.
Setting temperature
Press the NIGHT SETBACK button
2°F(1°C)
2°F(1°C)
30 min. 30 min.
Time
Lamp colors
OPERATION lamp
DRY operation Orange COOL operation Green FAN operation Green DEFROSTING operation Red and Orange alternately
OPERATION lamp Green
TIMER lamp Green
HIGH POWER lamp Green
Timer backup
Operation stops if there are no operator controls for 25 hours or
longer after unit operation switched from OFF to ON by use of ON timer operation.
29

7-2. Protective Functions

Freeze prevention
During COOL or DRY operation, freezing is detected and operation is stopped when the temperature of the indoor heat exchanger matches the conditions below.
1.
Freeze-prevention operation is engaged when the
temperature of the indoor heat exchanger is below 43°F(6°C).
2.
Restart after freeze-prevention operation occurs when the
temperature of the indoor heat exchanger reaches 46°F(8°C) or above.
46
(8)
43
(6)
36
(2)
temperature °F(°C)
Indoor heat exchanger
a.
Area: Automatic capacity control
b.
When the temperature drops below Point A, the operation
*
A
abcd
C
B
frequency is reduced by a certain proportion.
c.
Area: Frequency increase is prohibited.
d.
When the temperature reaches Point C or above, freezing
prevention is ended and control is the same as in the
a
area.
* When the temperature drops to below 36°F(2°C)
(continuously for 2 minutes or longer), the compressor stops. Once the freeze condition is detected, the air conditioner will work less than the maximum frequency until it is turned off.
30
Loading...
+ 82 hidden pages