Panasonic PT-D5600U, PT-D5600UL, PT-DW5000U, PT-DW5000UL User Manual

Installation
Warnings and Cautions
!
!
!
!
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
OUTPUT
Warning
Warning
Dangerous Voltage Warning: warns of situations in which a high voltage can cause physical injury and/or equipment damage. The text next to this symbol describes ways to avoid the danger.
General Warning:warns of situations that can cause physical injury and/or equipment damage by means other than electrical. The text next to this symbol describes ways to avoid the danger.
General Safety Instructions
Warning
Warning
Warning
Be sure to read, understand, and follow all safety instructions.
Only qualified electricians should carry out all electrical installation and maintenance work on reactors.
All wiring must be in accordance with the National Electrical Code (NEC) and/or any other codes that apply to the installation site.
Recommendations and Considerations
When installing the KLR/KDR Reactors on
the OUTPUT side of the Variable
Frequency Drive (VFD), please use the following guidelines:
Reactors should be mounted as close to the output terminals of the VFD as possible.
TCI suggests that the reactor be used in applications where the motor lead length is less than 100 feet. For applications with motor lead lengths greater than 100 feet, TCI offers KLC/KLCUL Output Filters and KMG MotorGuard High Performance Sinewave Filters.
Reactors are sized by the Full Load Amps located on the motor nameplate.
Performance and Protection for Drives
Reactor
Guide
Warning
Warning
Warning
Disconnect all power before working on the equipment. Do not attempt any work on a powered reactor.
The reactor, VFD, motor, and other connected equipment must be properly grounded.
The VFD terminals and connected cables are at a dangerously high voltage when power is applied to the VFD, regardless of motor operation.
Please contact TCI Technical Support or your TCI distributor for application information regarding the use of these reactors on the load or output side of the VFD, or in applications where inductors are used.
KLR/KDR Line Reactor
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation Instruction
INPUT
Recommendations and Considerations
When installing the KLR/KDR Line Reactors
on the INPUT side of the Variable
Frequency Drive (VFD), please use the following guidelines when wiring the unit:
The KLR/KDR Line Reactor is a 3­phase device and should be wired in series and positioned on the input side of the VFD.
TCI recommends that these reactors be wired as close to the front end of the VFD as possible.
In standard 40° C ambient or less installations, a clearance of 3 inches on all sides of the reactors and its enclosure is recommended for assisting in heat dissipation and ample wire bending space. This is a general guideline for typical applications. If the reactor is being installed next to a heat sensitive instrument or control device, we recommend reviewing specific requirements or heat limitations. Line reac­tor heat loss information is available in the standard TCI product literature or on the web at Trans-Coil website.
Field Wiring Information
Below is the typical wiring diagram for the 3-phase reactor applied to the front end of the Variable Frequency Drive (VFD).
Single-phase applications are acceptable, howev­er, it is important to size the unit based on the sin­gle phase Full Load Amperage of the VFD. The input and output connections should be on termi­nals A and C to ensure proper performance.
Wiring Diagram
LOAD
All Terminal Block connectors will be marked. A1, B1, and C1 are the input terminals where the 3 phases of incoming power are to be wired. As a result, A2, B2, and C2 are the output terminals. Units with copper bus or ring lug terminals are not marked. In these cases, either the upper terminals or the lower terminals can be used as the input terminals, as long as the selec­tion is consistent. For example, if an upper terminal is selected as the input, all upper terminals must be input terminals. Wiring from the output terminals should connect to the input of the VFD.
Refer to NEC wiring practices for appropriate wire sizes for your application.
These reactors are designed to be floor-mounted, or wall-mounted. Large open-style devices should be panel mounted by incorporating a bracket that would act as a shelf to support the reactor and/or enclosure. When installing an open style device in an existing control cabinet, drive cabinet, motor control center, or other large enclosure, the reactor should be mounted in the lower half of the cabinet to prevent hot spots or pockets of heat. Locating the reactor in the lower half of the cabinet typically allows better thermal dissipation and heat convection.
The KLR/KDR input line reactor should be located as close to the drive as possible to have the greatest success in both protecting the VFD as well as mitigating line harmonics. We recommend this be 10 feet of cable or less.
LINE
* For single-phase applications, use coils A and C. Isolate terminals B1 and B2.
Product Specifications
u 3-Phase, 600 Volt Class u UL Recognized; File E-116124 u CE Marked u CSA Approved u Current rated device u 200% rated current for 3 minutes u Ambient Temperature: 40° C u Patented Bobbin Construction on
units smaller than 110 amps
u Distributed Gap Technology
Loading...