VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-XC1228AP
Photo/Label for reference only.
Specifications
Nominal V oltage
Rated Capacity (20 hour rate)
Dimensions
Length
Width
Height
Total Height
6.496 inches (165 mm)
4.921 inches (125 mm)
6.890 inches (175 mm)
7.07 inches (179.5 mm)
Approx. mass
Standard Terminals
and Resin
UL94HB M5 Threaded Post
Characteristics
20 hour rate (1.4A)
Capacity
(note)
77˚F (25˚C)
Internal Resistance
Temperature
dependency
of capacity
(20 hour rate)
Self discharge
77˚F (25˚C)
Charge
Method
(Constant
Voltage)
Cycle use
(Repeating
use)
(Note) The above characteristics data are average values obtained
within three charge/discharge. Cycles not the minimum values.
10 hour rate (2.65A)
5 hour rate (4.8A)
1 hour rate (18A)
1.5 hour rate discharge
Cut-off voltage 10.5 V
Fully charged battery
77˚F (25˚C)
104˚F (40˚C)
77˚F (25˚C)
32˚F (0˚C)
5˚F (-15˚C)
Residual capacity
after standing 3 months
Residual capacity
after standing 6 months
Residual capacity
after standing 12 months
Initial current
Control voltage
12V
28Ah
24.34 lbs. (11 kg)
LC-XC1228AP
28Ah
26.5Ah
24Ah
18Ah
14A
Approx. 10mΩ
102%
100%
85%
65%
91%
82%
64%
11.2 A or smalle
14.5V to 14.9V
(per 12V cell 25˚C
For main power supplies.
Cycle long life type.
Dimensions (mm)
Terminal type: LC-XC1228AP: M5 threaded post
+
6.496±0.079 (165±2)
5.28 (134)
3.54 (90)
6.43 (163.4)
1.79 (45.5)
0.33 (8.3)
0.09 (2.2)
0.47 (12)
0.39 (9.8)
4.921±0.079 (125±2
0.47 (12)
6.890±0.079 (175±2)
4.88 (124)
Battery case resin: Standard (UL94HB) Color is black.
Discharge characteristics 77°F (25°C)
14.4
13.8
13.2
12.6
12.0
11.4
10.8
10.2
9.6
9.0
T erminal V oltage (V)
8.4
7.8
7.2
0 1 10 100
Duration of Discharge (minutes)
28A
(Note)
1.4A
7A
1000 200
Duration of discharge vs. Discharge current
2000
1000
0˚C
25˚C
13510305010
Discharge Current (A)
Duration of Discharge (minutes)
100
10
1
40˚C
(Note)
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject
to modification without notice. Contact Panasonic for the latest information.
VRLA BATTERIES AUGUST 2003