Panasonic LC-X1228AP User Manual

VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
)
r
)
LC-X1228P/LC-X1228AP
For standby power supplies. Expected trickle life: Approx. 6 years at 25°C, Approx. 10 years at 20°C.
Dimensions (mm)
Terminal type: LC-X1228AP: M5 threaded post
6.496±0.079 (165±2)
5.28 (134)
3.54 (90)
Photo/Label for reference only.
(a) The photo and dimensions represent LC-X1228AP.
Nominal V oltage
Rated Capacity (20 hour rate)
Dimensions
Length
Width
Height
Total Height
6.496 inches (165 mm)
4.921 inches (125 mm)
7.07 inches (179.5 mm)
LC-X1228AP 6.890 inches (175 mm) LC-X1228P 7.067 inches (179.5 mm)
Approx. mass
Standard Terminals
and Resin
Optional Terminals
and Resin
Please contact Panasonic for availability on optional items. Optional items may be subject to minimum
order quantities.
UL94HB M5 Bolt and Nut
UL94HB M5 Threaded Post
UL94V-0 M5 Bolt and Nut
UL94V-0 M5 Threaded Post
12V
28Ah
24.34 lbs. (11 kg) LC-X1228P LC-X1228AP
LC-P1228P LC-P1228AP
Characteristics
20 hour rate (1.40A)
Capacity
77˚F (25˚C)
(note)
10 hour rate (2.65A) 5 hour rate (5.00A) 1 hour rate (21.0A)
1.5 hour rate discharge Cut-off voltage 10.5 V
Internal Resistance
Temperature dependency
of capacity
(20 hour rate)
Fully charged battery
77˚F (25˚C)
104˚F (40˚C)
77˚F (25˚C) 32˚F (0˚C)
5˚F (-15˚C)
Residual capacity
Self discharge
77˚F (25˚C)
after standing 3 months
Residual capacity
after standing 6 months
Residual capacity
Charge Method
(Constant
after standing 12 months
Trickle use
Initial current
Control voltage
Voltage)
(Note) The above characteristics data are average values obtained
28.0Ah
26.5Ah
25.0Ah
21.0Ah
9.80A
Approx. 6.0m
102% 100%
85% 65%
91% 82% 64%
4.20 A or smalle
13.6V to 13.8V
(per 12V cell 25˚C
Discharge characteristics 77°F (25°C)
13.5
13.0
12.5
12.0
11.5
11.0
10.5
10.0
9.5
9.0
8.5
Terminal voltage (V)
8.0
Duration of discharge vs. Discharge current
30 20
15 10
5 4
3 2
1.5 1
50 40
30
Duration of discharge
20
(Minute) (Hour)
10
5 3
6.43 (163.4)
Battery case resin: Standard (UL94HB) Color is black.
56A
0 1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 40
(Minute) (Hour)
Duration of discharge
32˚F (0˚C)
5˚F (-15˚C)
1 5 10 50 100 500
Discharge current (A)
within three charge/discharge. Cycles not the minimum values.
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VRLA BATTERIES AUGUST 2005
LC-X1228P: M5 bolt and nut
1.79 (45.5)
4.921±0.079 (125±2
0.33 (8.3)
0.09 (2.2)
0.47 (12)
0.39 (9.8)
6.890±0.079 (175±2)
0.47 (12)
4.88 (124)
Optional (UL94V-0) Color is grey.
(Note)
2.8A
14A
28A
104˚F (40˚C)
77˚F (25˚C)
7A
1.4A
(Note)
Loading...