Individual Data Sheets
LC-P0612P
Contents indicated (including the recycle marking, etc.)
Specifications
Nominal voltage
Nominal capacity (20 hour rate)
Dimensions
Approx. mass
Terminal
Characteristics
Capacity
(25°C)
Internal resistance
Temperature dependency
of capacity (20 hour rate)
Self discharge
(25°C)
are subject to change without notice.
Length
Width
Height
Total Height
Faston 187 or
Faston 250 with hole
20 hour rate
10 hour rate
5 hour rate
1 hour rate
Fully charged battery
(25°C)
40°C
25°C
0°C
-15°C
After 3 months
After 6 months
After 12 months
6V
12Ah
151mm
50mm
94mm
100mm
2kg
12.0Ah
11.3Ah
10.4Ah
8.1Ah
15mΩ
102%
100%
85%
65%
91%
82%
64%
For standby power supplies.
Expected trickle design life: 10 – 12 years at 20°C according to Eurobat.
Dimensions (mm)
Terminal type (option)
4.75
53.6
2.3
(187)
6.35
5.4
(250)
Battery case resin: Flame-retardant (UL94 V-0)
Duration of discharge vs Discharge current
30
20
10
)ruoh(
5
3
egrahcsid fo noitaruD
60
0 °C
30
)etunim(
10
5
3
1
0.3
1
Discharge current (A)
40 °C
-15 °C
3
10 30 100
25 °C
Watt Table
Cut-off V 3min 5min 10min 15min 20min 30min 45min 1h 1.5h 2h 3h 4h 5h 6h 10h 20h 24h
4.8V 340 279 192 149 124 91.3 68.7 52.4 35.1 27.2 19.0 14.4 12.0 10.9 6.66 3.61 3.01
4.95V 325 269 186 144 121 88.3 67.5 51.8 35.0 27.1 18.9 14.4 12.0 10.9 6.66 3.61 3.01
5.1V 304 253 181 141 118 88.3 66.9 51.2 34.5 26.9 18.7 14.4 12.0 10.8 6.60 3.61 3.01
5.25V 278 237 171 136 115 86.0 66.3 50.1 34.2 26.6 18.4 14.3 12.0 10.8 6.60 3.60 3.00
5.4V 247 217 161 131 113 83.1 61.6 48.9 33.1 26.0 18.1 14.2 11.9 10.7 6.54 3.59 2.99
Ampere Table
Cut-off V 3min 5min 10min 15min 20min 30min 45min 1h 1.5h 2h 3h 4h 5h 6h 10h 20h 24h
4.8V 61.1 50.1 34.3 25.9 21.3 15.6 11.7 8.90 5.95 4.60 3.20 2.41 2.01 1.81 1.11 0.602 0.502
4.95V 58.4 48.2 33.3 25.0 20.8 15.1 11.5 8.80 5.92 4.58 3.18 2.41 2.01 1.81 1.11 0.602 0.502
5.1V 54.6 45.4 32.4 24.5 20.3 15.1 11.4 8.70 5.85 4.55 3.15 2.41 2.00 1.80 1.10 0.601 0.501
5.25V 50.0 42.6 30.6 23.6 19.9 14.7 11.3 8.50 5.80 4.50 3.10 2.40 2.00 1.80 1.10 0.600 0.500
5.4V 44.5 38.9 28.7 22.7 19.4 14.2 10.5 8.30 5.60 4.40 3.05 2.38 1.99 1.79 1.09 0.598 0.498
Valve Regulated Lead-Acid Batteries
68
(Wattage/Battery)
(Ampere/Battery)
Individual Data Sheets
Charging Method
Trickle Use
Control voltage: 6.8 - 6.9V; Initial current: 1.8A or smaller
Influence of Temperature on Trickle life
100
)sraeY( efiL ecivreS
10
1
0.1
10 20 30 40 50060
䚭㻃
Charging Voltage
2.275 V / Cell
Temperature (°C)
Constant-voltage and constant-current charge
characteristics for Trickle use
Cut off voltage
Discharge current
Cut off voltage (V) 5.25 5.1 4.95 4.65 4.35
0.6A -
2.4A
2.4A - 6A6A 12A
12A -
24A
Residual capacity vs storage period
120
)%( oitaR noitneteR yticapaC
100
80
60
40
20
0
0 2 4 6 8 101214161820
40 °C
(104 °F)
Storage Period (Month)
30 °C
(86 °F)
5 °C
(41 °F)
25 °C
(77 °F)
Discharge capacity by temperature
and by discharge current
24A -
36A
160
140
0.3
)%( ytitnauQ egrahC
0.2
0
0.1
120
100
80
60
40
20
AC
tnerruC e
rahC
Charge Quantity (to-Discharge Quantity)
0
048121620
Charge Time (h)
Discharge characteristics
7.5
7
6.5
)V(egatlov lanimreT
6
5.5
5
4.5
4
3.5
Battery Voltage
Discharge
1
100 % (0.05 CA*20H)
50 % (0.05 CA*10H)
Charge
2
Charge Voltage 6.825V
(2.275 V / Cell)
Charge Current 0.15 CA
3
Temperature 25 °C (77°F)
Charge Current
36 A
8
7
)V( egatloV yrettaB
6
5
4
3
2
1
0
120
100
)%( yticapaC
80
60
40
20
0
-20 -10 0 10 20 30 40 50
Battery temperature (°C)
0.6 A
3 A
1.2 A
0.05 CA
0.1 CA
0.2 CA
0.5 CA
1 CA
2 CA
3 CA
6 A
12 A
3
2.5
01
(minute) (hour)
1052
20
40
60
2 4 6 8 10 20
40
Duration of discharge
69
Valve Regulated Lead-Acid Batteries