Panasonic KW7M Installation Manual

KW7M
Basic setting to measure by Eco-POWER METER
When wiring the main unit and the current transformer (CT) and setting the mode 1 after power on, you can measure the power In order to use the other functions, the settings of the each parameter are necessary.
What to do
Measure Power
Output Alarm
Collect data
via RS485
Mount / Connection
Connect the current transformer (CT)
Wire the main unit
Wire output
line
Wire
communication
Set the basic settings (MODE1)
Power on the main unit
p.10
Settings
Set alarm (MODE1)
communication
output
Set
setting
(MODE2)
data with power
monitoring mode
p.15
How to use
Check alarm
output
5.3
data via
communication
device
6
7
Cautions for Your Safety
Read the manual carefully before installing, running and maintenance for proper operation. Before using, master the knowledge of the equipment, safety information and all of other notes. This manual uses two safety flags to indicate different levels of danger.
WARNING
Always take precautions to ensure the overall safety of your system, so that the whole system remains safe in the event of failure of this product or other external factor.
Do not use this product in areas with inflammable gas. It could lead to an explosion.
Exposing this product to excessive heat or open flames could cause damage to the
lithium battery or other electronic parts.
CAUTION
To prevent abnormal exothermic heat or smoke generation, use this product at the
values less than the maximum of the characteristics and performance that are assured in these specifications.
Do not dismantle or remodel the product. It could lead to abnormal exothermic heat or
smoke generation.
Do not touch the terminal while turning on electricity. It could lead to an electric shock.
Use the external devices to function the emergency stop and interlock circuit.
Connect the wires or connectors securely. The loose connection might cause abnormal
exothermic heat or smoke generation.
Do not allow foreign matters such as liquid, flammable materials, metals to go into the
inside of the product. It might cause exothermic heat or smoke generation.
Do not undertake construction (such as connection and disconnection) while the power
supply is on.
Do not use at secondary side circuit of inverter. It might cause exothermic heat or
damage.
A handling error could cause serious physical injury to an operator and in the worst case could even be fatal.
A handling error could cause serious physical injury to an operator or damage to the equipment.
Copyright and trademark
Panasonic Electric Works Co., Ltd. owns the copyright of this manual.
We stiffly refuse the reproduction of without permission from this manual.
Modbus Protocol is a communication protocol that the Modicon Inc. developed for PLC.
Other company names and the product names are the trademarks or registered
trademarks of each company.
Introduction
Thank you very much indeed for purchasing “KW7M Eco-POWER METER”. In this manual, we explain the usage of “KW7M Eco-POWER METER” in detail. Please use it correctly after understanding the content enough.
Table of Contents
Cautions before using ............................................................................................................................
Chapter 1 Unit’s Features and Structure
1.1 Features................................................................................................................................................... 1
1.2 Unit’s Name and Part Numbers............................................................................................................... 1
1.2.1 Main unit......................................................................................................................................... 1
1.2.2 Dedicated Current Transformer (CT) with Connector.................................................................... 1
1.2.3 Options........................................................................................................................................... 1
1.3 Measurement items ................................................................................................................................. 1
Chapter 2 Parts Name and Working
2.1 Parts Names............................................................................................................................................ 2
2.2 Select Keys’ Functions ............................................................................................................................ 2
Chapter 3 Wi
3.1 Main unit terminal arrangement............................................................................................................... 3
3.2 Wiring Diagrams ...................................................................................................................................... 4
3.3 For Output connection............................................................................................................................. 6
3.4 RS-485 Communication........................................................................................................................... 6
3.5 Low Voltage Directive.............................................................................................................................. 7
Chapter 4 S
4.1 Operation procedure................................................................................................................................ 8
4.2 Setting Mode Explanation......................................................................................................................10
4.2.1 MODE1......................................................................................................................................... 10
4.2.2 MODE2......................................................................................................................................... 15
4.2.3 MODE3......................................................................................................................................... 18
Chapter 5 Various Functions
5.1 LOCK mode........................................................................................................................................... 19
5.2 Display while communication................................................................................................................. 19
5.3 Display when pulse output.....................................................................................................................19
5.3.1 Output depends on integrated electric power .............................................................................. 19
5.3.2 Instantaneous electric power alarm ............................................................................................. 19
5.3.3 Current alarm ............................................................................................................................... 19
5.3.4 Stand-by power alarm.................................................................................................................. 20
Chapter 6 Display of each Value
6.1 Outline for the Working of Monitor Display............................................................................................ 21
6.2 Integrated electric power ....................................................................................................................... 22
6.3 Instantaneous electric power................................................................................................................. 22
6.4 Current................................................................................................................................................... 23
6.5 Voltage...................................................................................................................................................23
6.6 Electricity Charge................................................................................................................................... 24
6.7 Display when LED turns off ................................................................................................................... 24
ring ......................................................................................................................................3
ettings....................................................................................................................................8
..................................................................................................................19
............................................................................................................21
Chapter 7 MEWTOCOL Communications
7.1 Communication Procedures .................................................................................................................. 25
7.2 Communication timing ........................................................................................................................... 25
7.3 MEWTOCOL Communication................................................................................................................ 26
7.3.1 Overview of MEWTOCOL-COM(RS-485)....................................................................................26
7.3.2 Data Register List.........................................................................................................................27
7.3.3 Error Codes.................................................................................................................................. 28
7.3.4 Command..................................................................................................................................... 28
7.4 MODBUS (RTU) Communication.......................................................................................................... 30
7.4.1 Overview of MODBUS (RTU)....................................................................................................... 30
7.4.2 Data Register List.........................................................................................................................33
..................................................................................................1
.........................................................................................................2
..............................................................................................25
Chapter 8 Specifications.........................................................................................................................
8.1 Main unit ................................................................................................................................................ 34
8.2 Input Specifications................................................................................................................................ 35
8.3 Pulse output (Transistor output) Specifications..................................................................................... 35
8.4 Communication Specifications............................................................................................................... 36
8.5 Dedicated Current Transformer Specifications...................................................................................... 37
8.6 Self-diagnostic function.......................................................................................................................... 37
8.7 Power Failure Memory........................................................................................................................... 37
Chapter 9 Dimensions
9.1 Main unit ................................................................................................................................................ 38
9.2 Dedicated CT......................................................................................................................................... 38
9.3 DIN rail mounting................................................................................................................................... 40
............................................................................................................................38
34
Cautions before using
Installation environment
Do not use the Unit in the following environments.
Where the unit will be exposed to direct sunlight and where the ambient temperature is outside
the range of -10 to 50 C.
Where the ambient humidity is outside the range of 30 to 85 % RH (at 20 non-condensing)
and where condensation might occur by sudden temperature changes
Where inflammable or corrosive gas might be produced Where the unit will be exposed to excessive airborne dust or metal particles Where the unit will be exposed to water, oil or chemicals Where organic solvents such as benzene, paint thinner, alcohol, or strong alkaline solutions
such as ammonia or caustic soda might adhere to the product
Where direct vibration or shock might be transmitted to the product, and where water might wet
the product
Please use the Unit according to the specifications described in this manual. Otherwise, it
may malfunction or cause fire and an electric shock.
Connect to the power supply in compliance with the rating. Refer to the wiring diagram to ensure proper wiring for the power supply, input and output. Do not perform wiring or installation with a live line. It may also lead to circuit burnout or fire by
way of the secondary CT side opening.
Do not add voltage and current to an output terminal from outside. Do not use at secondary side circuit of inverter.
Installation
Installation and wiring must be performed by expert personnel for electrical work or electric
piping.
The power supply terminal and voltage input terminal of the main unit is common. Therefore if
additional noise effects the power supply line, incorrect measurements may result.
Eco-POWER METER is designed to be used in a control panel. As to measurement
If there is some distortion by harmonic or waveform, it may not measure correctly. Please check with the actual system before adopting it.
Static electricity
Discharge static electricity touching the grounded metal etc. when you touch the unit. Excessive static electricity might be generated especially in a dry place.
Cleaning
Wipe dirt of the main unit with soft cloth etc. When thinner is used, the unit might deform or be
discolored.
Power supply
Connect a breaker to the voltage input part for safety reasons and to protect the device.
The breaker that connects to the voltage input part must arrange at the position easily reached, and display shows it is the breaker of the equipment.
Do not turn on the power supply or input until all wiring is completed.
Before power on
Please note the following points when turning on power at the first time.
Confirm there are neither wiring rubbish nor especially an electrical conduction when installed. Confirm neither the power supply wiring, the I/O wiring nor the power-supply voltage are wrong. Tighten the installation screw and the terminal screw surely. Use an electric wire applicable to the rated current.
i
KW7M Eco-POWER METER

Chapter 1 Unit’s Features and Structure

1.1 Features

KW7M Eco-POWER METER is a watt-meter of DIN rail installation type. Electric power, voltage, current, etc. are measured using AC voltage and AC current input via one of the following systems.
Eco-POWER METER is designed chiefly to manage saving energy. It is neither intended nor can it be legally used for billing.

1.2 Unit’s Name and Part Numbers

1.2.1 Main unit

Phase and Wire system Rated input Current transformer Terminal type Model No.
Single-phase two-wire system Single-phase three-wire system Three-phase three-wire system
100 / 200V AC

1.2.2 Dedicated Current Transformer (CT) with Connector

Rated primary current Model No.
5A
50A 100A AKW4802C 250A AKW4803C 400A AKW4804C
AKW4801C

1.2.3 Options

Product name Contents Model No. Mounting rails DIN rail AT8-DLA1
Dedicated CT type
(5A, 50A(common)/
100A/250A/400A)
Screw terminal AKW7111
Mounting plate Use to fix to DIN rail ATA4806
Terminal screw driver Using when wiring Phoenix terminal AFP0806

1.3 Measurement items

Item Unit Data range
Instantaneous electric power kW
Integrated electric power kWh
Current
Voltage
Eco-POWER METER is designed chiefly to manage saving energy.
It is neither intended nor can it be legally used for billing.
L1CT1-phase current L2CT2-phase current
Voltage between 1-2 V Voltage between 2-3 V
Electricity charge ※ 0.00〜99999999
0.00999999.99
0.009999999.9
0.06000
A
0.06000
A
0.0〜〜9999
0.09999
1
KW7M Eco-POWER METER

Chapter 2 Parts Name and Working

2.1 Parts Names

Display indicator Lighting or Blinking according to the display
LOCK indicator Lighting while in lock mode
T/R indicator Blinking while communication
OUT indicator Lighting when pulse output
Display each value Display Electric energy, Instantaneous
power, Current, Voltage, Electricity charge
MODE Key
Display each setting value
SET Key ITEM / Key SHIFT / Key

2.2 Select Keys’ Functions

Key Functions
<MODE>
<SET>
ITEM
<
△
SHIFT
<
▽
<SET>+<MODE>
<SET>
(continuous press
about 3-sec)
>
>
Use to select mode Use to set each value entered To select measured display To shift each mode To change each setting value To select measured display To shift each mode To change each setting value Reset the measured value
All keys locked Release lock mode while in lock mode
2
KW7M Eco-POWER METER

Chapter 3 Wiring

3.1 Main unit terminal arrangement

Be sure to wire correctly according to the terminal arrangement and wiring diagrams.
No. Functions
1 1, R, R 2 2, N, S 3 3, T, T 4 No connection (N.C.)
Power supply
(common)
Measured
voltage input
5 6 7 8
− +
Pulse
output
RS-485
9 E
The input voltage to each terminal is as follows.
Phase and wire Terminal Input voltage
Single-phase, two-wire Single-phase, three-wire Three-phase, three-wire
12 123 123
100-120/200-240VAC (100-120/200-240V〜)
100-120VAC (100-120V〜:3W)
100-240VAC (200-240V 3〜)
Caution for Wiring
1) Terminal fastening torque should be 0.5 to 0.6 Nm for No.1 to No.4 (M3 screw) and
0.22 to 0.25 Nm for No.5 to No.9 (M2 screw).
2) Use wire with its cross section of 0.14~1.5mm use wire with its cross section of 0.14~1.0mm
2
(AWG#26~14) for voltage input terminal (No.1, 2, 3),
2
(AWG#26~16) for pulse output terminal (No.5, 6), use wire with its cross section of 0.3~1.0mm2(AWG#22~16) for communication terminal (No.7, 8, 9). When connecting 2 or more wires to communication terminal, use same wire with its cross section of
0.3 to 0.34mm
2
.
3) This has no built-in power switch, circuit breaker or fuse. Therefore it is necessary to install them in the circuit near this unit.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
4) We recommend the below ferrules (terminals) for wiring.
(We don’t recommend them when 2 or more wires are connected.)
Terminal No. Product number for Ferrule (PHOENIX CONTACT)
No.1 to No.4 (M3 screw) No.5 to No.9 (M2 screw)
(When 1 wire is connected.)
AI 0.25-8YE AI 0.34-8TQ AI 0.5-8WH AI 0.75-8GY AI 1.0-8RD AI 1.5-8BK
AI 0.25-8YE AI 0.34-8TQ AI 0.5-8WH
3
KW7M Eco-POWER METER

3.2 Wiring Diagrams

Please connect a breaker to the voltage input part for safety reasons and to protect the device.
Measure load of 100-200V system
Single-phase two-wire system One current transformer (CT) is required to measure a single-phase, two-wire system.
Single-phase, three-wire/ Three-phase, three-wire system Two CTs are required to measure a single-phase, three-wire system or three-phase, three-wire system.
Measure load of 400V system
VT (Voltage transformer) is needed to measure over 240VAC. Use a commercial VT, its secondary rating is 110V. *Grounding VT’s neutral line is recommended for the unit protection when VT breaks down.
Power supply
side
Power supply
side
1 2
1 2 3
① ② ③ ④
⑤ ⑥ ⑦ ⑧ ⑨
① ② ③ ④
⑤ ⑥ ⑦ ⑧ ⑨
KL
White Black
k
CT1
KL
K L
White Black
White Black
k
CT1
k
Load side
CT2 Do not connect to CT2.
Load side
CT2
Single-phase, two-wire
1 2
Single-phase, three-wire / Three-phase, three-wire
1 2 3
VT
② ③ ④
VT
①② ③
* After wiring, turn on the power supply and turn off and power on again.
4
KW7M Eco-POWER METER
A
How to attach the Current Transformer (CT) One CT is needed when measuring 1P2W. Two CTs are needed when measuring 1P3W/3P3W. Using
all CTs for one Eco-POWER METER should be the same.
Check beforehand that the thickness of the electric wire is smaller than the through-hole of the CT. When connecting CT, connect the secondary side to the terminal of the main unit first, and after that
wire the primary side to a load electric wire. Incorrect order might cause an electric shock or break CT.
The CT has polarity. Wire correctly according to the K and L marks.
Wrong direction can’t measure correctly.
When closing CT, check that there is no foreign materials on the divided face. And make sure it is
closed securely once the wire is in place; if not the measurement value will be not accurate.
When CTʼs cable is extended, it is possible to extend up to about 10m with the cable of AWG#22 or
more cross section under the environment without noise at all. Please use the thick cable as much as possible.
To connect CT with secondary side current 5A How to connect for measuring by combination with CT (secondary side current 5A)
(1) Select 5A at CT type setting mode (CT-T). (2) Set the primary current of measured CT (secondary side current 5A) at primary side current of
CT setting mode (CT-1). < ex > If the measured CT is 400A/5A, set to ”400”.
(3) Clamp the dedicated CT for 5A (AKW4801C), which is connected to the main unit first, to
secondary side of the CT (secondary side current 5A). CT direction (KL) should be set for the commercial CT direction.
Set the CT (secondary side current 5A) and the AKW4801C approximately 1m apart. If the two CTs are set too close each other, it may not measure accurately due to magnetic field
interference.
(Connection example) With ammeter etc.
Power supply
Breaker
mmeter etc.
Secondary current
K
CT with 2nd current 5A
L
L K
Dedicated CT (For 5A)
AKW4801C
Eco-POWER
METER
Load
5
KW7M Eco-POWER METER
Without ammeter
Power supply
Breaker
Secondary current
K
CT with 2nd current 5A
L
Load
Shorted or resistor less than 0.1Ω
L K
Eco-POWER
Dedicated CT (For 5A)
AKW4801C
METER

3.3 For Output connection

Since the transistor output is insulated from the internal circuit by a photo-coupler, it can be used both as a NPN output and PNP (equal value) output.
Eco-POWER METER
Eco-POWER METER
NPN output
Pulse (+) PNP output
5
Load Load
Pulse (−)
6
- +
Pulse (+)
5
Pulse (−)
6
- +
Power supply for Load
Power supply for Load

3.4 RS-485 Communication

Recommended Cable Use the transmission cables shown below for Eco-POWER METER RS-485 communication system.
1) Use shielded type twist cables.
2) Use only one type of the transmission cables. Do not mix different types of the cables.
3) Use twist pair cables under a bad noise environ ment.
4) Be sure to connect with daisy chain the RS-485 transmission line between each unit.
one end of the shielded wire to an earth ground.
5) Use 2 recommended cables with the same cross section of 0.3 to 0.34mm
2
to connect to the
RS-485 (+) and RS-485 (-) terminals.
Connect
6
KW7M Eco-POWER METER
RS-485 Wiring and setting of terminal station
1) When using shielded cable for the RS-485 transmission line, ground one end.
Use a class D dedicated earth for grounding. Do not share a ground with other earth lines. (Fig.1)
2) Be sure to connect with daisy chain the RS-485 transmission line between each unit.
Do not use a splitter. (Fig.2)
3) With a terminal station, RS-485 (E) (No.9) and RS-485 (-) (No.8) should be shorted. (Fig.1)
(Fig.1)
To RS-485 device
Sheilded cable
Eco-POWER METER
General station
(+) (+)
(−)
(E)()(
Sheilded cable
Eco-POWER METER
Terminal station
E
)
Shorted
Class D grounding Class D grounding
(Fig.2)
Correct wiring
Incorrect wiring
×
Terminal Terminal

3.5 Low Voltage Directive

When using in the application confirming to EN61010-1/IEC61010-1, make sure to satisfy the following conditions. (1) Pulse output part secure only basic insulation. In order to secure reinforced (double) insulation
demanded by EN 61010-1/ IEC61010-1, secure basic insulation or more with load side and reinforced (double) insulation with communication system side.
(2) Provide the voltage input part with an EN60947-1 or EN60947-3 compliant circuit breaker.
The breaker that connects to the voltage input part must arrange at the position easily reached, and display shows it is the breaker of the equipment.
(3) Use a wire with basic insulation or more for a wire cramped (or connected) CT.
Environmental conditions
・Overvoltage category Ⅱ, Pollution degree 2 ・Indoor use ・An ambient temperature of –10 to 50℃ ・An ambient non-condensing humidity of 35 to 85%RH (at 20℃) ・Altitude of 2000m or less
Mount the product in a place with
A minimum of dust, and an absence of corrosive gases No flammable, explosive gasses Few mechanical vibrations or shocks No exposure to direct sunlight No large capacity electromagnetic switches or cables through which large current is flowing
7
Loading...
+ 35 hidden pages