When wiring the main unit and the current transformer (CT) and setting the basic setting after power on,
you can measure the power
The basic setting of MOD E1 is n ecessary to measure.
In order to use the other functions, t he set t ings of the each parameter are necessary.
What to do
Output Alarm
line
output
(MODE1)
function
settings
(MODE1,2)
P14,21
Collect data
via RS485
communication
setting
Log data
setting
(MODE4)
Read out
log data
SD memory
card
setting
(MODE4)
Set calendar timer and initialize memory of main unit (*) (MODE4)
output from
other device
line
pulse measurement
p.21
*Be sure t o set calendar timer (clock) and
initialize memory of main unit before measuring.
How to use
data with power
monitoring mode
output
5.2
display
data via
communication
device
with option mode
insert
SD memory card
Check count value
with power
monitoring mode
i
Read the manual carefully before installing, running and maintenance for proper operation.
the whole
could cause damage to the
lithium battery or other electronic parts.
t abnormal exothermic heat or smoke generation, use this product at the
Do not allow foreign matters such as liquid, flammable materials, metals to go into the
heat or
damage.
ther company names and the product names are the trademarks or registered
Cautions for Your Safety
Befor e using, mas ter the knowledge of the equipment, safety information and all of other
notes.
This manual uses two safety flags to indicate different levels of danger.
WARNING
●Always take precautions to ensure the overall safety of your system, so that
system remains safe in the event of failure of this product or other external factor.
●Do not use this product in areas with inflammable gas. It could lead to an explosion.
●Exposing this product to excessive heat or open flames
CAUTION
●To preven
values less than the maximum of the characteristics and performance that are assured
in these specifications.
● Do not dismantle or remodel the product. It could lead to abnormal exothermic heat or
smoke generation.
●Do not touch the terminal while turning on electricity. It could lead to an electric shock.
●Use the external devices to function the emergency stop and interlock circuit.
●Connect the wires or connectors securely. The loose connection might cause abnormal
exothermic heat or smoke generation.
●
inside of the product. It might cause exothermic heat or smoke generation.
●Do not undertake construction (such as connection and disconnection) while the power
supply is on.
●Do not use at secondary side circuit of inverter. It might cause exothermic
A handling error could cause serious physical injury to an operator
and in the worst case could ev en be fatal.
A handling error could cause serious physical injury to an operator
or damage to the equipment.
Copyright and trademark
● Panasonic Electric Works SUNX Co., Ltd. owns the copyright of this manual.
● We stiffly refuse the reproduction of without permission from this manual.
●Modbus Protocol is a communication protocol that the Modicon Inc.developed for PLC.
●O
trademarks of each company.
ii
Introduction
Thank you very much indeed for purchasing
‘KW1M-H Eco-POWER METER’.
In this manual, we explain t he usage of ‘KW1M-H
Eco-POWER METER’ in detail.
Please use it correctly after under st anding the content
enough.
iii
Table of Contents
Chapter 1 Unit’s Features and Structure ................................................................................................... 1
1.1 Unit’s Name and Model Numbers ............................................................................................................ 1
1.1.1 Main unit ......................................................................................................................................... 1
Chapter 2 Parts Name and Working .......................................................................................................... 4
2.1 Parts Names ............................................................................................................................................ 4
5.3 Counter function ..................................................................................................................................... 32
5.3.2 Change the Preset Value ............................................................................................................. 32
5.4 Log data writing function ........................................................................................................................ 33
5.4.1 In case that you insert SD memory card ...................................................................................... 33
5.4.2 In case that SD memory card is always inserted to card slot ...................................................... 33
5.4.3 Unit memory ................................................................................................................................. 34
5.4.4 Format for written file .................................................................................................................... 35
5.4.5 File name and Saved folder ......................................................................................................... 37
5.4.6 Logging data ................................................................................................................................. 38
5.5 Demand function .................................................................................................................................... 39
5.6 Clock Correction function ....................................................................................................................... 41
iv
Chapter 6 Display of each Val ue .............................................................................................................. 42
6.1 Working of Monitor Display .................................................................................................................... 42
6.2 Power Monitoring mode ......................................................................................................................... 45
6.2.1 Integrated electric power .............................................................................................................. 45
6.2.2 Instantaneous electric power ........................................................................................................ 45
6.2.3 Current .......................................................................................................................................... 46
6.2.4 Voltage ......................................................................................................................................... 46
6.2.6 Carbon dioxide conversion value ................................................................................................. 47
6.2.7 Power factor ................................................................................................................................. 47
6.2.8 Frequency ..................................................................................................................................... 48
6.2.9 Hour meter .................................................................................................................................... 48
6.2.10 Pulse input value ........................................................................................................................ 49
6.5 Other indication ...................................................................................................................................... 58
6.5.1 Power On indication ..................................................................................................................... 58
6.5.2 Indication while communication.................................................................................................... 58
7.1 Communication Procedures .................................................................................................................. 59
7.2 Communication timing ........................................................................................................................... 59
7.3 MEWTOCOL Communication ................................................................................................................ 60
7.3.1 Overview of MEWTOCOL-COM (RS485) .................................................................................... 60
7.3.2 Data Register List (MEWTOCOL) ................................................................................................ 61
7.4 MODBUS (RTU) Communication .......................................................................................................... 65
7.4.1 Overview of MODBUS (RTU) ....................................................................................................... 65
7.4.2 Data Register List ......................................................................................................................... 68
Chapter 8 Specification s .......................................................................................................................... 71
8.1 Main unit ................................................................................................................................................ 71
8.4 Communication Specifications ............................................................................................................... 73
8.5 Main Unit Memory Specifications .......................................................................................................... 74
8.6 External Memory Specific ations ............................................................................................................ 75
8.6.1 Demand power ............................................................................................................................. 76
8.7 Self-diagnostic function .......................................................................................................................... 76
8.8 Power Failure Memor y ........................................................................................................................... 76
8.9 Applicable standard ............................................................................................................................... 77
8.10 Dedicated Current Transformer Specifications .................................................................................... 78
9.1.1 Main unit ....................................................................................................................................... 79
9.2 How to mount to DIN rail ........................................................................................................................ 80
9.3 How to connect / replace the battery ..................................................................................................... 80
Do not use the Unit in the following environment s .
・Where the unit will be exposed to direct sunlight and w her e t he ambient temperature is outsid e
the range of -10 to 50 °C.
・Where the ambient humi dit y is outside the range of 30 t o 85 % R H (at 20℃, non-condensing)
and where condensation m ight occur by sudden temperature c hanges
・Where inflammable or corrosive gas might be produced
・Where the unit will be exposed to excessive airborne dust or metal particles
・Where the unit will be exposed to water, oil or chemicals
・Where organic solvents such as benzene, paint thinner, alcohol, or strong alkaline s olutions
such as ammonia or caust ic soda might adhere to the produ ct
・Where direct vibration or shock might be transmitted to the product, and where water might wet
the product
・Where the place near high-voltage cable, high-v oltage device, power line, pow er device.
・Where the place near a machinery with transmission function such as a m at eur radio.
・Where the place near a mach iner y which occurs the big switching serge
Please use the Unit according to the specifications described in this manual. Otherwis e, i t
may malfunction or cause fire and an electric shock.
・Connect to the power su pply in compliance with the rating.
・Refer to the wiring diagram to ensure proper wiring for t he pow er supply, input and output.
・Do not perform wiring or insta ll at ion with a live line. It may also lead to circuit burnout or fire by
way of the secondary CT sid e opening.
Installation
・Installation and wiring m us t be performed by expert personnel for electrical work or ele ct r ic
piping.
・The power supply termin al an d voltage input terminal of the ma in un it is common. Therefore if
additional noise effects t he power supply line, incorrect measurements may result.
・Eco-POWER METER is designed to be used in a control panel.
・Do not add an excess power t o t he display. It might break the inner l iquid crystal.
As to measurement
・If there is some distortion by harmonic or waveform, it may not mea sur e correctly.
Please check with the actual system before adopt s it.
・This can’t measure the power that flows reverse such as a regenerativ e electric power.
If you measure a reverse power, it shows ‘0.00kW’ and it doesn’t count.
・It might not measure an instantaneous current such as an i nr us h current or an welding machine.
・When measuring the below loads, it might not satisfy with the accuracy guarantee.
Out of rating cur r ent , Load w it h l ow power factor,
Load with windi ng cur r ent , Load with ferromagnetic f ield
・Power factor operation is a method assuming balanced load. The error might be big when it
measures unbalanced load.
Static electricity
・Discharge static electricity touching the grounded metal etc. when you touch t he unit .
・Excessive static electricit y might be generated especial ly in a dry place.
Cleaning
・Wipe dirt of the main unit wit h soft cloth etc. When thinner is used, t he unit might deform or be
discolored.
vi
■
■
Power supply
・Connect a breaker to the voltage input part for safety reasons a nd to protect the device.
The breaker that connect s to t he voltage input part must arrange at t he pos ition easily reached,
and display shows it is the breaker of the equipment.
・Do not turn on the power supp ly or input until all wiring is completed.
Before power on
Please note the following poi nts when turning on power at the first time.
・Confirm there are neither wiring rubbish nor especially an electri c al conduction when installed.
・Confirm neither the power supply wiring, the I/O w iring nor t he pow er-supply voltage are wr ong.
・Tighten the installation screw and the terminal scr ew surely.
・Use an electric wire applicable to the rated current.
vii
KW1M-H Eco-POWER METER
AKW1121B
(CT connector color; Blue)
AKW1121
(CT connector color; Wihte)
Log function
Available
Demand function *
Available
Single-phase two-wire
Rated
primary current
Connector
color
Blue
AKW4801B
White
AKW4801C
Blue
AKW4802B
White
AKW4802C
Blue
AKW4803B
White
AKW4803C
Blue
AKW4804B
White
AKW4804C
Blue
AKW4808B
White
AKW4808C
Rated primary
current
Connector
color
Blue
AKW4506B
White
AKW4506C
Blue
AKW4507B
White
AKW4507C
Blue
AKW4508B
White
AKW4508C
Chapter 1 Unit’s Features and Structure
KW1M-H Eco-POWER METER is the suitable size wattmeter f or installing in a control board.
It measures electrical power, voltage, current and so on using AC voltage and AC current in put.
It also works ad an hour meter, which is measured power-on or power-off time.
1.1 Unit’s Name and Model Numbers
1.1.1 Main unit
Product name KW1M-H Eco-POWER METER SD card type
Model No.
・
Phase and Wire system
Power supply 100-240V AC 50/60Hz
Measured voltage input
Measured current input 50A / 100A / 250A / 400A / 600A
Current transformer Dedicated CT type
Terminal type Screw Terminal (M3 + / - screw)
* Demand function by puls e input is available for Ver. 1. 20 or more.
Note) AKW1121B and AKW1121 are not compatible.
Please be aware that only AKW1121B and AKW4x0xB (CT) can be used together.
Dedicated current transformer for 600A 600A
Note) AKW480xB and AKW480xC are not compatible.
Dedicated Current Transformer (CT) Through type
Product name
Dedicated current transformer for 50A/100A 50A / 100A
Dedicated current transformer for 250A/400A 250A / 400A
Dedicated current transformer for 600A 600A
Model No
Model No
Note) AKW450xB and AK W45 0xC are not compatible.
1
KW1M-H Eco-POWER METER
Product name
Model No
Data collection software
Monitoring and logging t he m easured
values.
Download from our website.
Power display tool
KW View
It makes graph by using data
from Eco-POWER METER
Download from our website.
Free of charge
Functions
Supported version
- 600A CT input
Ver.1.05 or more
- Simple demand measurement
Ver.1.10 or more
- Pulse-through with pulse output
Ver.1.40 or more
Others
Mounting rail AT8-DLA1
Fastening plate ATA4806
Battery *1)Required to back up memory and calendar AFPG804
Mounting frame AKW1822
Extension cable for CT 3m AKW4703
Extension cable for CT 5m AKW4705
*1) Included with the product when shipped.
1.1.3 Tool
Product name Functions Model No
・
KW Monitor
Free of charge
Note) Members registration is required to download.
1.1.4 Firmware
For using the additional fu nct ions of KW1M-H
- Demand measurement by pulse input
- Clock correction function (±30 sec./month)
- Remove SD memory card function
- Clock correction function (±1 sec./month)
Note) You can’t use the additional functions without the supported firmware.
Ver.1.20 or more
Ver.1.30 or more
2
KW1M-H Eco-POWER METER
Item
Unit
Data range (Display)
kWh/
MWh
0.00 to 9999.99MWh
(9-digit display) 0.00 to 9999999.99kWh
0.00 to 1.00
(
)
Integrated electric power converted
by pulse
kWh/
MWh
Present
demand
Estimated
demand
Ratio of
demand
1.2 Measurement items
Integrated electric power ( Act ive)
Instantaneous electric power (Active) kW 0.00 to 9999.99
R-current
Current
T-current
R(RS)-voltage
Voltage
T(TS)-voltage
Electricity charge *1 0.00 to 999999
Conversion value Carbon dioxide kg-CO2 0.00 to 999999
A 0.0 to 6000.0 S-current
V 0.0 to 9999.9 S(RT)-voltage
Power Factor
(Identify leading phase(-) and lagging phase)
Within the range of phase angle θ=-90 to 90 degree
Frequency Hz 47.5 to 63.0
Hour meter
ON-time
OFF-time
hour 0.0 to 99999.9
Pulse counter 0 to 999999
0.000kWh to 9999.99MWh
kW 0. 00 t o 9999. 99
Demand
kW 0. 00 t o 9999. 99
*2
estimated
% 0.0 to 9999.9
*1 Eco-POWER METER is designe d chiefly to manage saving energy.
It is neither intended nor can it be lega lly used for billing.
*2 Please use this demand function as your standard. The demand value calculated with this function is
not guaranteed.
3
KW1M-H Eco-POWER METER
Display each value
With 7-seg
Key
Functions
Use to shift setting mode
(only available while outp ut t he st and -by alarm)
Lighting while power on
Blinking while communication
①
⑥
② ⑦
④
③
⑤
⑧ ⑪
⑨ ⑩
・
・Use to set each value enter ed
・Reset stand-by alarm while output the alarm
<SET>
(continuous press 3-sec)
<SHIFT/▽>
<ITEM/△>
<SET>+<MODE>
<SET>+<ITEM/△> ・To shift power monitoring mode and option mode
<SET>+<SHIFT/▽> ・To shift power monitoring mode and simple dema nd m ode
・All keys locked
・Release lock mode while in lock mode
・To select measured valu e display (While monitoring)
・To select setting value (While setting mode)
・To select measured valu e display (While monitoring)
・To select setting value (While setting mode)
・
4
KW1M-H Eco-POWER METER
L
P1
P3
+
Terminal
Phase and wire
Terminal
Input voltage
Operating
power supply
two-wire
100
Single-phase,
two-wire
three-wire
Three-phase,
three-wire
four-wire
Chapter 3 Wiring
Be sure to wire correctly a cc ording to the terminal arrangem ent and wiring diagrams.
After completing wiring, be sure to attach the terminal cover for safety r easons.
3.1 Terminal arrangement
No. Function
①
②
N
③
④
⑤
P0
⑥ P2
⑦
⑧ +
⑨ -
⑩
E
⑪
⑫ -
⑬ +
⑭ -
The input vol t age to each terminal is as f ol l ows.
1) Terminal fastening torque should be 0.5 to 0.6N・m. In case of using a crimping terminal, use it with
insulating sleeve applic able to M3 screw.
2) This has no built-in power switch, circuit breaker for power supply part. To protect the device, it is
necessary to install power switch and circuit breaker in the power supply circuit.
And this has no built-in power switch, circuit brea ker or fuse for measured voltage input parts.
Therefore it is necessary to install them in the circu it near this unit.
3) We recommend a wire with the cross s ect ion of 0.75 to 1.25mm
2
for power supply line and measur ed
voltage input line.
4) Use flame-resistant cable for each wiring.
5
KW1M-H Eco-POWER METER
3.2 Wiring Diagrams
Please connect a breaker (3 to 15A) to the voltage input part for safety reasons and to protect the
device. Grounding the secondary side of VT (Voltage transformer) and CT (Current transformer) is not
necessary with low-voltage circuit.
◆When measuring a load with rated input voltage (100-200V system/ 400V system)
Single-phase two-wire system
*One current transformer (CT) is required.
Do not wire ⑥ ⑦ terminals. They are connected internal.
Single-phase three-wire / Three-phase three-wire system
*Two current transformers are required.
Three-phase four-wire system
*Three current transfor mers are required.
Do not wire ⑦ terminal. It is connected internal.
6
KW1M-H Eco-POWER METER
Single-phase, three-wire system
Three-phase, three-wire system
◆When measuring a load with exceed input voltage
Voltage transformer (VT) is needed when you measure a load with over rated input voltage ( 440V).
Use VT, those secondary r at ing i s 110V.
Grounding the secondary side of VT and CT is not necessary with low-voltage circuit.
Single-phase two-wire system
Three-phase, four-wire sy st em
◆Using the clock correcti on function by frequency of the measured voltage
It corrects the clock by using the measured voltage frequency input to P1-P0 as a reference
frequency.
When P1 -P0 terminals are not connected or it set OFF for clock correction function, it doesn’t correct
the clock.
3.3 How to attach the Current Transformer (CT)
・One current transformer (CT) is needed to measure 1P2W system. Two CTs are needed to measure a
1P3W/3P3W system. Three CTs are needed to measure a 3P4W system. Using all CT should be the
same.
・Check beforehand that the t hickness of the electric wire is s ma ller than the through-ho le of the CT.
・When connecting CT, connect the secondary side to the terminal of the main unit first, and after that
wire the primary side to a load electric wire.
Incorrect order might ca use an electric shock or brea k C T.
・The CT has polarity. Wire correctly according to the K and L m arks.
Wrong directi on c an’t measure correctly.
・When closing clam p-on type CT, check that there is no foreign materials on the divided face. And
make sure it is closed securely once the wire is in place; if not the measurement value will be not
accurate.
・When CT’s cable is extended, it is possible to extend up to about 10m with the cable of AWG#22 or
more cross section under the environment without noise at all. Please use the thick cable as much as
possible. *Please check beforehand with the actual s ystem in case of extending the cable.
・If there is some distortion by harmonic or waveform, it may not mea sur e correctly. Please check with
the actual system before adopting it.
・Separate the wiring (strong electric part) of the measured voltage input terminal (operating power
supply terminal) from the CT c able. It may not satisfy the accuracy due to noise.
・Only same color housing of cable and connector of CT can be co nnected.
That of different color (blu e and white) can't be connected.
7
KW1M-H Eco-POWER METER
Secondary current
Dedicated CT for 5A
Ammeter etc.
L K
K
L
Eco-POWER
Secondary current
K
L
L K
Eco-POWER
Ω
◇To connect CT with secondary side current 5A
How to set for measuring by combination with CT (secondary side current 5A)
(1) Select 5A at CT type sett ing mode (CT-T).
(2) Set the primary current of measured CT (secondary side current 5A) at primary side current of
CT setting mode (CT-1).
<ex> If the measured CT is 400A/5A, set to’400’.
(3) Clamp the dedicated CT for 5A, which is connected to the main unit first, to secondary side of
the CT (secondary side current 5A). CT direction (K→L) should be set for the commercial CT
direction.
*Set the CT (secondary side current 5A) and the dedicated CT for 5A approximately 1m apart.
If the two CTs are set too close each other, it may not measure accurately due to magnetic
field interference.
(Connection example)
With Ammeter etc.
Power supply
Breaker
CT with 2nd current 5A
METER
Load
Without Ammeter
Power supply
Breaker
CT with 2nd current 5A
Shorted or resistor less th an 0. 1
Load
Dedicated CT for 5A
METER
8
KW1M-H Eco-POWER METER
P.IN +
P.IN -
Eco-POWER
(+)
Insulated
(sensor etc.)
Measured voltage input
(Fig. A)
Good example
Eco-POWER
(+)
Auto transformer
(Fig.B) No Good example
Do not ground the secondary side.
Do not use an auto-transformer.
Operating power sup pl y
Measured voltage input
Operating power sup pl y
Measured voltage input
Insulated
Input equipment
Input equipment
(+)
3.4 For input connection
・Contact input
Use highly reliable metal plated contacts. Since the contact’s
bounce time leads directly to error in the count value, use
contacts with as short a bounce time as possible. In general,
select 30Hz for max. counting speed.
・Non-contact input (Transistor input)
⑬ ⑭
Connect with an open collector. Use the transistor with the
following specifications. V
=20V min. IC=20mA min. I
CEO
=6μA max
CBO
Use transistors with a residual voltage of less than 1.5V when the transistor is ON.
*Short-circuit impedance should be less than 1 kΩ.
(When the impedance i s 0Ω, drain current is approx. 7m A. )
Open-circuit impedance should be more than 100kΩ.
・Input wiring
Please wire up to 10m by using a shielded wire or a metal lic electric wire tube indiv idually.
If it is long, it may not work correct ly due to floating capacitance of wire.
(Note)
Operating power supply input part and measured voltage input are not insulated to pulse input parts.
So the input equipment must have the power supply transformer in which the secondary side is not
grounded with the primary and secondary sides insulated, in order to prevent interference of the
power supply circuit when connecting the external input circuit. Be sure not to use an
auto-transformer.
Operating power sup pl y
transformer
METER
(-)
transformer
METER
(sensor etc.)
(-)
Input equipment
Eco-POWER
METER
(-)
(sensor etc.)
9
KW1M-H Eco-POWER METER
Power supply for Load
+
Plus common
Eco-POWER METER
Pulse (+)
Minus common
11
+
Eco-POWER METER
Power supply for Load
12
Pulse (+)
11
12
Load
Load
Correct wiring
○
×
Terminal Terminal
3.5 For Output connection
・Since the transistor output is insulated from the internal circuit by a photo-coupler, it can be used both
as a plus common and minus common.
Pulse (-)
Pulse (-)
-
-
・Wire up to 100m for output connection.
If it is long, it may not work correct ly due to floating capacitance of wire.
3.6 RS485 Communication
・When using shielded ca ble for the RS485 transmiss io n li ne, gr ound one end.
Use a class D dedicated earth for grounding. Do not share a ground with other ear t h lin es. ( Fi g. 1)
・Be sure to connect with daisy chain the RS485 transmission l ine between each unit.
Do not use a splitter. (Fig.2)
・With a terminal station, R S485 (E) (No.10) and RS485 (-) ( No. 9) should be shorted.
*E terminal is not SG (sig nal ground) terminal. Do not ground shielded cable.
(Fig.1)
(Fig.2)
Incorrect wiring
station station
10
KW1M-H Eco-POWER METER
Conductor
Insulator
Resistance
(at 20℃)
HITACHI
Belden Inc. 9860
HITACHI
Belden Inc. 9207
0.75 mm2
VCTF
(JIS)
Cable
Section
Notes
3) Use twist pair cables under a bad noise
Conductor Insulator
Jacket
Shield
Recommended Cable
Use the transmission cables shown below for Eco-POWER METER RS485 com m unication system.
Cable
Twisted-
pair
with shield
VCTF
Twisted-pair
with shield
VCTF
Size
1.25 mm
(AWG16)
2
Max.16.8Ω/km
or more
0.5 mm2
(AWG20)
Max.33.4Ω/km
or more
(AWG18)
Max.25.1Ω/km
or more
Jacket
Conductor Insulator
Material Thickness
Polyethylene
Polyethylene
PVC
Max.
0.5 mm
Max.
0.5 mm
Max.
0.6 mm
1) Use shielded type twist cables.
2) Use only one type of the transmission cables.
2) Do not mix different types of the cables.
environment.
Cable
diameter
Approx.
8.5 mm
Approx.
7.8 mm
Approx.
6.6 mm
Applicable cable
KPEV-S
1.25 mm
2
×1P
KPEV-S
2
0.5 mm
×1P
0.75 mm2×2C
3.7 Low Voltage Directive
When using in the application confirming to EN61010-1/IEC61010-1, make sure to satisfy the following
conditions.
(1) Pulse output part secure only basic insulation. In order to secure reinforced (double) insulation
demanded by EN 61010-1/ IEC61010-1, secure basic insulation or more with load side and
reinforced (double) insulation with communicatio n system side.
(2) Provide the voltage input part with an EN60947-1 or EN60947-3 compliant circuit breaker.
The breaker that connect s to t he voltage input part must arrange at t he pos ition easily reached,
and display shows it is the breaker of the equipment.
(3) Use a wire with basic insulation or mor e f or a w ire cramped (or connected) CT.
【Environmental conditions】
・Overvoltage category Ⅱ, Pollution degree 2
・Indoor use
・An ambient temperatur e of –1 0 to 50℃
・An ambient non-condens ing humidity of 35 to 85%RH (at 20℃)
・Altitude of 2000m or less
【Mount the product in a place with】
・A minimum of dust, and an absence of corrosive gases
・No flammable, explos iv e gas ses
・Few mechanical vibrati ons or shocks
・No exposure to direct su nlight
・No large capacity electromagnetic switches or cabl es t hr ough which large current is flowi ng
11
KW1M-H Eco-POWER METER
Monitor (Display when power on)
Mode 1…Mode for setting each par ameter for power
With SD
Memory card
measurement
without SD memory card
Setting mode
(SD Eject)
(Mode 1)
(Mode 2)
(Mode 3)
(Mode 4)
Phase/Wire system
SYST
CT type
CT-T
<SET>
‘5A’
Remove
memory
When select
<SET>
card
Voltage range
VOLT
<SET>
VT ratio
VT
Current for time
HM-A
CUTA
PL-P
<SET>
<SET>
<SET>
<SET>
<SET>
<SET>
Stand-by alarm 2
AL-S 2
<SET>
Demand alarm
DEM1/DEM2/DEM3
<SET>
Electricity rate
RATE
Conversion factor
CO2
Note) Press <MODE> and <SET> at the same time, the setting
will be initialized.
Chapter 4 Settings
4.1 Operation procedure
【Basic setting to measure】
When wiring Eco-POWER METER and CT and setting mode 1 after power on, Eco-POWER Meter can
measur e the e lect ri c po w er. In ord er to u se th e oth er fu nct i ons, set m od e2, 3 and 4 according to your use.
<SET> <SET>
SD
<MODE>
<SET>
other than ‘5A’
<SET>
<SET>
measurement
When select
<SET> <SET> <SET>
Refer to the next page.
Primary side current of CT
CT-1
<SET>
When select
or ‘DEM’
or ‘P-THR’
Cutoff current
<SET>
Unit for pulse output
When select ‘AL-P’
‘Values’
<SET>
Power alarm
<SET>
<SET>
Monitor
AL-P
<SET>
When select ‘AL-C’
Current alarm
AL-C
When select ‘AL-S’
Stand-by alarm 1
AL-S 1
<SET>
Press <MODE> to return Monitor.
When select ‘Cnt’
Preset value
Cnt
12
KW1M-H Eco-POWER METER
Monitor (Display when power on)
Setting mode
(Mode 1)
(Mode 2)
(Mode 3)
(Mode 4)
Max. counting speed
Hz *1
Protocol
PROT
Auto-off
OFF
Prescale setting mode
PSCL
Station number
NO
Power input type
PWER
Transmission speed
SPD
Saved file type
FILE
When select ‘PM’
<SET>
Pulse type
P.SEL
Transmission format
FMT
Log cycle
LOG *2
When select
‘kWh’
When select
<SET>
Pulse rate
PM.kW
Pulse constant value
PM.PL
Response time
RESP
CAL
<SET>
Clock correction
CLK.A
Initialize memory of main unit
S.FMT
Reference frequency
FREQ *3
Mode 2…Mode for setting of each parameter for pulse measurement
Mode 3…Mode for setting of each parameter for serial co m mu nication
Mode 4…Mode for setting of each parameter for optional function
<MODE>
<SET>
Refer to the
previous
page.
‘PULSE’
<SET> <SET> <SET>
<SET> <SET> <SET>
<SET> <SET> <SET>
<SET>
When select
‘CT’
<SET>
<SET>
<SET>
<SET>
Version check
VER
<SET>
<SET>
Calendar timer
<SET>
<SET>
<SET>
Monitor
*1 When you select ’P-THR’ at unit for pulse output setting mode in MODE1, ‘Max. counting speed setting
mode will be invalid. (50Hz fixed)
*2 Log cycle setting mode is only w hen ‘ON’ is selected for type 3 on Save file type selection mode.
*3 Reference frequency setting mode is only when ‘MANUAL’ is selected on clock correction setting
mode.
Press <MODE> to return M onitor .
Note) Press <MODE> and <SET> at the same time, the setting will be initialized.
13
KW1M-H Eco-POWER METER
Max. counting
speed
Pulse constant
value
Transmission
format
◆Initial value list
Mode 1 Mode 2
Item Initial valu e Item Initial value
Phase/Wire system 1P2W
2000
CT type 50
Primary side current of CT 5 Prescale 1.000
Voltage range 400 Power input type CT
VT 1.00 Pulse type kWh
Current for time measure me nt 1.0 Pulse rate 1.000
Cutoff current 1.0
50000
Unit for pulse output 0.001
Power alarm 9999.99 Clock correction AUTO
Current alarm 100.0 Reference frequency 50.0
Stand-by alarm 1 100.0 Mode 3
Stand-by alarm 2 0 Item Initial value
Preset value 0 Protocol MEWTOCOL
Demand alarm 1 0.00 Station number 1
Demand alarm 2 0 Transmission speed 19200
Demand alarm 3 10
8bit-o
Electricity rate 10.00
Conversion value 0.410 Response time 1
Mode 4
Item Initial valu e
Auto-off 0
Calendar timer 2000 Jan. 1 00:00:00:00
Initialize memory of main unit OFF
Saved file type 1 ON
Saved file type 2 ON
Saved file type 3 ON
Log cycle 60
14
KW1M-H Eco-POWER METER
4.2 Setting Mode Explanation
■The value with under line is in itial setting among each setting value. ☆Set before measurement.
Press <MODE> and <SET> at a time, the setting will be initialized.
4.2.1 MODE1 (Mode for setting each parameter for power measurement.)
Phase/Wire system setting mode SYST
Mode defines phase and wire system to measure.
・Select from Single-phase 2-wire / Single-phase 3-wire / Three-phase 3-wire / Three-phase 4-wire.
Select the system of the measured load.
CT type setting mode CT-T
Mode defines input current type of the dedicated CT.
・Select from the type of 5A/ 50A/100A/250A/400A/600A.
・When the secondary current of CT is 5A, select ‘5A’.
Primary side current of CT setting mode CT-1
*Only when ‘5A’ is selected on CT ty pe set ting mode.
Mode defines primary side current when measuring by combination with existing CT, its
secondary current of 5A.
It is possible to use as the second step for combination with existing CT by selecting ‘5A’ in the
CT type setting mode. In this case, it is necessary to set the primary side current.
・Primary side current of th e ex isting CT can be set the range of 1 to 40 00 ( I nit i al 5).
・When connecting 5ACT directly and measure with 5A range, set to ‘5’.
ex) If primary current of measured existing CT is 400A(se condary side is 5A), set to ‘400’.
Voltage range setting mode VOLT
Mode defines v oltage range of Ec o-P ower Meter.
・Select from 400/200.
・When it measures load of 400V system, select ‘400’.
When it measures load of 100/ 200V system, select ‘200’.
*In case measuring the lo ad of 1 00/200V system with selecting ‘400’, the resolution will be down.
Select the correct voltage range.
VT setting mode VT
Mode defines voltage input method to the main unit, input voltage directly or uses a voltag e
transformer (VT) (over 440V system).
・It can be set the range of 1.00 to 99.99.
‘1.00’ should be set when voltage input directly without connecting VT.
‘1.01 to 99.99’ should be set w hen VT is used to input voltage.
Current for time measurement setting mode HM-A
Mode defines for time measured current. It measures ON-time and OFF-time by setting value.
・It can be set the range of 1.0% to 100.0%F.S.
ex) When 10.0 is set, the current exceeds 10.0%F.S is measured as ON-time, the current under
10.0%F.S is measured as O FF-time.
*Measured current is the current of CT 1.
Cutoff current setting mode CUTA
Mode defines load current that do es not measure (Cutoff current).
Use to avoid miss-measurement by wiring or induction noise at no-load.
0.00kW is displayed for instantaneous electric power, 0.0A is displayed for current. Integrated
electric power is not added.
・It can be set the range of 1.0% to 50.0%.
ex) When set to 10.0, current ( = power) under 10.0%F.S is not added.
15
KW1M-H Eco-POWER METER
Unit for pulse output setting mode PL-P
Mode defines unit used for pulse output. It defines the unit of integrated electric power for
1-pulse output.
・Select from 0.001/0.01/0.1/1/10/100kWh /AL-P/AL-C/AL-S/Cnt/DEM/P-THR.
When one of the ‘0.001/0.01/0.1/1/10/100’ [kWh] is set, one pulse is output at reaching the setting
value.
When ‘AL-P’ is set, alarm is output at the time when instantaneous electric power is over the setting
value.
When ‘AL-C’ is set, alarm is output at the time wh en current is over the setting value.
When ‘AL-S’ is set, alarm is output at the time when current is under the setting value and it passes
the setting time.
When ‘Cnt’ is set, it output at the time when count value reaches preset value set by preset value
setting mode.
When ‘DEM’ is set, it output at the time when demand value is satisfied t he setting conditions.
When ‘P-THR’ is set, it output signal that is input to the pulse input terminal.
Power alarm setting mode AL-P
*Only when ‘AL-P’ is selected on unit for pu lse output setting mode.
Mode defines ins t antaneous elec t r ic power used for alarm output.
・It is set the range of 0.00 to 9999.99kW.
Current alarm setting mode AL-C
*Only when ‘AL-C’ is selected on un it for pulse output setting mode.
Mode defines the ratio of current used for alarm output. (Ratio for the rated current)
・It is set the range of 1.0 to 100.0%.
Stand-by alarm setting mode 1 AL-S1
*Only when ‘AL-S’ is selected on un it for pulse output setting mode.
Mode defines the ratio of current used for thresh old value to judge stand-by power.
(Ratio for the rated current)
・It is set the range of 1.0 to 100.0%.
Stand-by alarm setting mode 2 AL-S2
*Only when ‘AL-S’ is selected on unit for pulse output setting mode.
Mode defines the time used for thr eshold value to judge stand-by power.
・It is set the range of 0 to 9999min.
When ‘0’ is set, alarm is always output at the time when judging the stand-by power.
When ‘1 to 9999’ is set, alarm is output at the time when passing the setting time with the stand-by
power.
The alarm can be reset by pressing <SET> with the instantaneous electric power display. After reset
the alarm, start to monitor t he st and-by power again.
Preset value setting mode Cnt
*Only when ‘Cnt’ is selected on unit for pulse output setting mode.
Mode defines co unt value used for output.
・It is set the range of 0(0.000) to 999999(999.999).
*The range differs according to the pre-scale set by pre-sca le setting mo de.
Demand alarm setting mode 2 DEM2
Mode defines the hysteresis to use for decide alarm off timing.
It can avoid frequent al arm output ON/OFF near a demand target value. (Refer to 5.5)
・It is set the range of 0 to 100%.
16
KW1M-H Eco-POWER METER
Demand alarm setting mode3 DEM3
Mode defines the time to start demand monitoring.
・It is set the range of 1 to 30 min. (Initial 10 minutes)
Ex.) When ‘10’ is set, alarm output or alarm indication ‘d’ is not occurred after 10 minutes from the
demand span started. When ‘30’ is set, it doesn’t output alarm and it doesn’t indicate alarm.
*In case of that ‘DEM1’ is set to 0.00kW, it doesn’t output alarm and it doesn’t indicate alarm.
*When ‘DEM’ is set with unit for pulse output setting mode, it outputs if all conditions DEM1, 2 and 3
are satisfied. And it indicates ‘d’ on the bottom line of the display regardless the setting of unit for
pulse output setting mode. (Refer to 5.5)
Electricity charge setting mode RATE
Mode defines electricity charge ratio used as a stand ar d p er 1kWh.
・It can be set the range of 0.00 to 99. 99 / 1kWh. (Initial 10.00)
Conversion factor setting mode CO2
Mode defines conversion factor of carbon dioxi de us ed as a standard per 1kWh.
・It can be set the range of 0.000 to 9.999/1kWh. (Initial 0.410)
17
KW1M-H Eco-POWER METER
Monitor
↓
<MODE> (MODE 1 Lighting)
↓
<SET>
Phase/Wire system setting mode
Three-phase 3-wire ⇔ Three-phase 4-wire.
↓
<SET>
CT type setting mode
50
100
250
400
600
5
↓
<SET>
Primary side current of CT setting mode
*It is only when ‘5A’ is selected on CT type setting mode.
If measured CT is 100A/5A, set to 100. If 5A is measured, set to 5.
↓
<SET>
Voltage range setting mode
↓
<SET>
VT ratio setting mode
↓
<SET>
Mode1 Setting flow chart
Press <ITEM/△><SHIFT/▽> to change Single-phase 2-wire ⇔ Single-phase 3-wire ⇔