Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Technical/Programming Manual
FT1020G3
Rev 2.2.1
For Software V2.2.x
FT1020G3 CIE
This page has deliberately been left blank.
Technical Manual
FT1020G3 Rev 2.2.1
Table of contents
1 Introduction _____________________________________________________________ 9
1.1 General introduction ................................................................................................. 9
1.2 Definitions / Explanations ......................................................................................... 9
2 Overview ______________________________________________________________ 10
2.1 The FT1020G3 system ........................................................................................... 10
2.1.1 Printer .............................................................................................................. 10
2.1.2 Expansion boards............................................................................................. 10
2.1.3 Power supply.................................................................................................... 10
2.2 Software (S/W) versions ......................................................................................... 10
2.3 Documents ............................................................................................................. 12
2.4 Applications............................................................................................................ 12
2.5 PC software (S/W).................................................................................................. 12
2.5.1 EBLWin ............................................................................................................ 12
2.5.2 TLON Manager ................................................................................................ 13
3 TLON Network __________________________________________________________ 14
3.1 FT1020G3 TLON network ...................................................................................... 14
3.2 Redundant TLON Network ..................................................................................... 14
3.3 Routers .................................................................................................................. 14
3.4 Network connections .............................................................................................. 15
3.4.1 Twisted pair TLON network .............................................................................. 15
3.4.2 Fibre optic TLON network ................................................................................. 15
3.4.3 TCP/IP TLON network ...................................................................................... 16
4 Control & Indicating Equipment ___________________________________________ 17
4.1 FT1020G3 Specifications ....................................................................................... 17
4.2 FT1020G3 CIE Layout............................................................................................ 19
4.2.1 Mounting plates ................................................................................................ 21
4.2.2 Mounting plate for 19" mounting rack ................................................................ 21
4.3 COM loops ............................................................................................................. 22
4.4 Programmable voltage outputs (S0-S3) ................................ ................................ .. 22
4.5 Programmable relay outputs (R0-R1) ..................................................................... 22
4.6 Programmable inputs (I0-I3) ................................................................................... 23
4.7 Relay outputs for routing equipment (TX)................................................................ 23
4.7.1 Fire alarm output .............................................................................................. 23
4.7.2 Fault condition output ....................................................................................... 23
5 Expansion boards 458x __________________________________________________ 24
5.1 8 zones expansion board 4580 ............................................................................... 25
5.1.1 Type of zone line input ..................................................................................... 25
5.1.1.1 Zone line input (EOL capacitor) ................................ .................................... 26
5.1.1.2 EX zone line input (EOL resistor) .................................................................. 26
5.1.1.3 Zone line input (EOL resistor) ....................................................................... 26
5.1.2 Input states ...................................................................................................... 27
5.1.2.1 Normal state ................................................................................................. 27
5.1.2.2 High current state ......................................................................................... 27
5.1.2.3 Alarm state ................................................................................................... 27
5.1.2.4 Short-circuit state ......................................................................................... 27
5.1.2.5 Open circuit state ......................................................................................... 27
5.1.2.6 Disconnected state ....................................................................................... 27
5.2 8 relays expansion board 4581 ............................................................................... 27
5.3 Inputs and outputs expansion board 4583 .............................................................. 28
5.4 I/O Matrix board 4582 ............................................................................................. 29
5.4.1 I/O Matrix jumper link setting ............................................................................ 29
6 Optional Modules _______________________________________________________ 31
6.1 AS1668 Fan control ................................................................................................ 31
6.1.1 Mode Control.................................................................................................... 31
6.1.2 Fan Status ........................................................................................................ 31
1
Technical Manual
FT1020G3 Rev 2.2.1
6.1.3 Configuration and Programming ....................................................................... 32
6.1.4 Fan Reset ........................................................................................................ 34
6.1.5 Fan Front Display ............................................................................................. 35
6.1.6 Supply Air Fan .................................................................................................. 35
6.1.7 Smoke Exhaust Fan ................................ ......................................................... 36
6.2 Zone control ................................ ........................................................................... 37
6.2.1 Controls & Indications ....................................................................................... 37
6.2.2 Zone Control Configuration ............................................................................... 38
6.3 Generic Applications .............................................................................................. 39
6.3.1 Overview .......................................................................................................... 39
6.3.2 New mimic options ........................................................................................... 39
6.3.3 Configuration and programming........................................................................ 40
6.4 Occupant Warning System (OWS) ......................................................................... 41
6.4.1 Overview .......................................................................................................... 41
6.4.2 Audio Amplifiers ............................................................................................... 42
6.4.2.1 60/120 Watt Amplifier Module ....................................................................... 42
6.4.2.2 250 Watt Amplifier Module............................................................................ 44
6.4.3 OWS Volume Adjustment ................................................................................. 45
6.4.4 Auxiliary Audio inputs ....................................................................................... 45
6.4.5 OWS Dual Strobe Output ................................................................................. 45
6.5 Gaseous extinguishing system control module ....................................................... 46
6.5.1 Overview .......................................................................................................... 46
6.5.2 Display board (SUB929) & decal ...................................................................... 46
6.5.3 Control board (SUB928) ................................................................................... 48
6.5.4 CIE interface board (SUB943) .......................................................................... 48
6.5.4.1 Inputs from FT1020G3 to CIE interface board (SUB943) .............................. 48
6.5.4.2 Outputs from CIE interface board (SUB943) to FT1020G3 ............................ 48
7 Printer 49 8 TLON connection board 5090 _____________________________________________ 50
8.1 Single TLON Network (not recommended) ............................................................. 50
8.2 Redundant TLON network ...................................................................................... 50
8.3 Network programming ............................................................................................ 50
9 Peripheral devices ______________________________________________________ 51
9.1 COM loop units ...................................................................................................... 51
9.1.1 Input units ........................................................................................................ 53
9.1.1.1 Analogue Sensor Bases (ASB) ..................................................................... 54
9.1.1.2 Addressable Manual Call Points ................................................................... 54
9.1.1.3 Analogue Detectors ...................................................................................... 55
9.1.1.4 Conventional Detector Bases (CDB) ............................................................. 59
9.1.1.5 Conventional Detectors ................................................................................ 59
9.1.1.6 Accessories.................................................................................................. 60
9.1.2 Addressable I/O units ....................................................................................... 61
9.1.3 Alarm devices (addressable sounders) ............................................................. 62
9.1.4 Short circuit isolators (addressable) .................................................................. 64
9.1.5 Built-in Isolators ................................................................................................ 65
9.1.6 Units for Hazardous (Ex) areas ......................................................................... 65
9.1.6.1 Galvanic isolators / IS barrier units ............................................................... 65
9.1.6.2 Intrinsically Safe mounting bases.................................................................. 65
9.1.6.3 Intrinsically Safe photoelectric smoke detectors ............................................ 66
9.1.6.4 Intrinsically Safe heat detectors .................................................................... 66
9.1.7 Intrinsically Safe Manual Call Points ................................................................. 66
9.1.8 Other COM loop units ....................................................................................... 66
9.2 Units connected to the RS485 interface .................................................................. 68
9.2.1 Alert Annunciation Units ................................................................................... 68
9.2.2 External Presentation Units .............................................................................. 69
9.3 Units connected to the RS232 interface J7 ............................................................. 70
9.3.1 Web-servers ..................................................................................................... 70
9.4 Other units ............................................................................................................. 70
9.4.1 External LEDs .................................................................................................. 70
2
Technical Manual
FT1020G3 Rev 2.2.1
9.4.2 Alarm Devices (sounders, etc.) ......................................................................... 71
9.4.3 Magnetic Door Holders ................................ ..................................................... 71
9.4.4 Duct Detector Chambers .................................................................................. 71
10 Programmable inputs ____________________________________________________ 72
10.1 Control Unit Inputs I0-I3 .......................................................................................... 73
10.2 Inputs 0-4 on expansion board 4583 ....................................................................... 73
10.2.1 Not supervised ................................................................................................. 73
10.2.2 Supervised ....................................................................................................... 73
10.3 The 3361 unit Inputs In0 / Z & In1 ........................................................................... 73
10.3.1 Input In0 ........................................................................................................... 74
10.3.2 Input In1 ........................................................................................................... 74
11 Input programming ______________________________________________________ 75
11.1 Trigger conditions ................................................................................................... 75
11.2 Logic ................................................................................................ ...................... 78
11.2.1 Non-Supervised (Default) ................................................................................. 78
11.2.2 Supervised ....................................................................................................... 78
12 Programmable outputs __________________________________________________ 79
12.1 Control Unit outputs S0 – S3 .................................................................................. 80
12.2 Control Unit outputs R0 & R1.................................................................................. 81
12.3 8 relays expansion board 4581 Output 0 – Output 7 ............................................... 81
12.4 Inputs and Outputs expansion board 4583 Output 0 - 1 .......................................... 81
12.5 The 3361 unit's Outputs Re0 & Re1 ........................................................................ 81
12.6 The 3364 unit's VO0 – VO2 .................................................................................... 81
12.7 The 4477 unit's Output (siren) ................................................................................ 82
12.8 The 3379 unit's Output (sounder) ........................................................................... 82
12.9 The 4380 unit's Output (beacon) ............................................................................. 82
12.10 The 4383 unit's Output (light indicator).................................................................... 82
13 Output programming ____________________________________________________ 83
13.1 Type of output ................................................................................................ ........ 83
13.2 Logic ................................................................................................ ...................... 83
13.3 Supervised / Non-supervised .................................................................................. 84
13.4 Output signal period ............................................................................................... 84
13.5 Control expression ................................................................................................. 86
13.5.1 Trigger conditions ............................................................................................. 86
13.5.1.1 Alarm ....................................................................................................... 87
13.5.1.2 Interlocking ............................................................................................... 87
13.5.1.3 Disablement ............................................................................................. 88
13.5.1.4 Other ........................................................................................................ 88
13.5.1.5 Comments to the trigger conditions (functions): ........................................ 88
13.5.2 Logical operators .............................................................................................. 92
13.5.3 Control expression examples ............................................................................ 92
13.5.3.1 AND ......................................................................................................... 92
13.5.3.2 OR ........................................................................................................... 92
13.5.3.3 NOT ......................................................................................................... 92
13.5.3.4 Parentheses ............................................................................................. 93
13.5.3.5 Control expressions .................................................................................. 93
14 Short circuit isolators____________________________________________________ 94 15 Interlocking function ____________________________________________________ 96
15.1 Programming of interlocking function ...................................................................... 96
15.1.1 Interlocking output ............................................................................................ 97
15.1.2 Interlocking input .............................................................................................. 97
15.1.3 Interlocking combination ................................................................................... 97
15.2 Interlocking indications ........................................................................................... 99
15.3 Interlocking outputs and inputs (H9) ....................................................................... 99
15.3.1 Activated interlocking outputs / inputs (H9/C1) .................................................. 99
15.3.2 Activate / deactivate interlocking output (H9/C2) ............................................. 100
15.3.3 Disable / re-enable interlocking output (H9/C3) ............................................... 100
3
Technical Manual
FT1020G3 Rev 2.2.1
15.4 Interlocking control expressions ............................................................................ 100
16 Fire Door Closing (MDH) ________________________________________________ 101 17 Functions / Services / Features ___________________________________________ 102
17.1 Sensor value ........................................................................................................ 102
17.2 Week average sensor value ................................................................................. 102
17.3 Decision value ...................................................................................................... 103
17.4 Alarm algorithms for smoke detectors / Detection levels / Offsets ......................... 103
17.4.1 Alarm algorithm / Alternative alarm algorithm ................................ .................. 103
17.4.2 Filtering algorithm ........................................................................................... 104
17.4.3 Smouldering smoke algorithm ........................................................................ 106
17.4.4 Performance factor ......................................................................................... 107
17.5 Algorithms for Analogue heat detectors ................................................................ 107
17.5.1 Class A1 algorithm ......................................................................................... 108
17.5.2 Class A2 S algorithm ...................................................................................... 108
17.5.3 Class B S algorithm ........................................................................................ 108
17.6 Self verification ..................................................................................................... 109
17.7 Minimum / Maximum sensor values ...................................................................... 109
17.8 2-zone / 2-address dependence (Co-incidence alarm) ................................ .......... 110
17.8.1 2-zone dependence ........................................................................................ 111
17.8.2 2-address (-unit) dependence ......................................................................... 111
17.8.3 Reset of 2-zone / 2-address dependence (co-incidence alarm) ....................... 112
17.9 Delayed alarm ...................................................................................................... 112
17.9.1 General time delay application ........................................................................ 112
17.9.2 Specific time delay application ........................................................................ 113
17.10 Selective Alarm Presentation ................................................................................ 113
17.11 Alarm Verification Facility (AVF) ........................................................................... 113
17.12 Alert Annunciation ................................................................................................ 114
17.13 Alert Annunciation Applications ............................................................................ 115
17.13.1 Alarm Acknowledgement Facility (AAF) .......................................................... 115
17.13.2 Local Alarm Acknowledgement (LAA) ............................................................. 117
17.14 Quiet alarm .......................................................................................................... 118
17.15 Fire alarm type A and Fire alarm type B ................................................................ 118
17.15.1 Fire alarm type B ............................................................................................ 119
17.15.2 Fire alarm type A ............................................................................................ 119
17.16 Disable zones, alarm points, outputs, etc. ............................................................. 119
17.16.1 Disable / Re-enable zone ............................................................................... 120
17.16.2 Disable / Re-enable zone - address ................................................................ 120
17.16.3 Disable / Re-enable output type ...................................................................... 120
17.16.4 Disable / Re-enable alarm devices.................................................................. 120
17.16.5 Disable / Re-enable interlocking output ........................................................... 120
17.16.6 Disable / Re-enable outputs for routing equipment .......................................... 120
17.16.7 Disable / Re-enable alert annunciation function .............................................. 120
17.16.8 Disconnect & Re-connect loop / zone line input .............................................. 120
17.17 External time channels ......................................................................................... 121
17.18 Test mode ............................................................................................................ 121
17.19 Test alarm devices ............................................................................................... 121
17.20 Test of outputs ..................................................................................................... 122
17.21 Test of routing equipment ..................................................................................... 122
17.22 Calibration of supervised outputs .......................................................................... 122
17.23 Service signal ....................................................................................................... 122
17.24 Fault signal (fault condition) .................................................................................. 123
17.25 Alarm texts ........................................................................................................... 123
17.25.1 Creating the alarm texts via EBLWin ............................................................... 123
17.25.2 Downloading alarm texts to the Display Units 1728 / 1736 .............................. 125
17.26 Real time clock (RTC) .......................................................................................... 126
17.26.1 Daylight saving time ....................................................................................... 126
17.27 Loss of main power source ................................................................ ................... 126
17.27.1 Fault: Loss of main power source ................................................................... 126
17.27.2 LCD backlight ................................................................................................. 126
4
Technical Manual
FT1020G3 Rev 2.2.1
17.28 Zone Groups ........................................................................................................ 126
18 Special New Zealand functions ___________________________________________ 127
18.1 Alarm devices ...................................................................................................... 127
18.1.1 Silence Alarms (inside switch) ........................................................................ 127
18.1.2 New Zealand FB Bulgin Silence switch (outside switch) .................................. 127
18.1.2.1 Isolated alarm ......................................................................................... 128
18.2 Battery faults ........................................................................................................ 129
18.2.1 FAULT: Battery .............................................................................................. 129
18.2.2 FAULT: Low battery capacity (Auto battery test) ............................................. 129
18.3 Routing equipment isolate (disable) ...................................................................... 129
18.4 Acknowledged alarm ............................................................................................ 129
19 Advanced mode _______________________________________________________ 131
19.1 Pulse up – down counter ...................................................................................... 132
19.1.1 Pulse up – down counter for smoke ................................................................ 132
19.1.2 Pulse up – down counter for temperature ....................................................... 132
19.1.3 Pulse up – down counter for smoke & temperature ......................................... 133
19.2 Fire judgement ..................................................................................................... 133
19.3 Alarm threshold levels .......................................................................................... 133
19.4 Alarm Delay Time ................................................................................................. 133
19.5 Learning function / Learning conditions ................................................................. 135
19.5.1 Area Alarm algorithms .................................................................................... 135
19.5.1.1 Smoke - Steam area, level 1 ................................................................... 135
19.5.1.2 Heating area, level 2 ............................................................................... 136
19.5.1.3 Cooking – Welding Area, level 3 ............................................................. 136
19.5.1.4 Clean Area, level 1, 2 & 3 ....................................................................... 136
19.5.1.5 Learning function summary ..................................................................... 136
19.6 Analogue data output ........................................................................................... 136
19.7 Sensitivity compensation ...................................................................................... 136
19.8 Self-diagnosis of internal devices.......................................................................... 137
19.9 Address setting check .......................................................................................... 137
19.10 Polling LED ................................ ................................................................ .......... 137
20 Control Unit Properties _________________________________________________ 138
20.1 Control Unit properties dialog box ......................................................................... 138
20.1.1 General Information ........................................................................................ 138
20.1.2 Peripherals ..................................................................................................... 138
20.1.3 Misc. .............................................................................................................. 138
20.2 EBLWin Control Unit pop-up menu ....................................................................... 139
20.2.1 Reset alarm counter ................................ ....................................................... 139
20.2.2 Software version............................................................................................. 139
20.2.3 Upgrade number of alarm points ..................................................................... 139
20.2.4 Show event log ............................................................................................... 140
20.2.5 Restart ................................................................................................ ........... 141
20.2.6 Delete ............................................................................................................ 141
20.2.7 Properties....................................................................................................... 141
20.2.8 Add Web-server ............................................................................................. 141
21 System properties (settings) _____________________________________________ 142
21.1 System properties dialog box................................................................................ 142
21.1.1 Name ............................................................................................................. 142
21.1.2 User definable text ......................................................................................... 142
21.1.3 System properties, Page 1 ............................................................................. 142
21.1.3.1 Alert Annunciation .................................................................................. 142
21.1.3.2 Alarm Acknowledgement Facility ............................................................ 143
21.1.3.3 Disable routing equipment by door switch ............................................... 143
21.1.3.4 Alarm reset method ................................................................................ 143
21.1.3.5 Alarm delay time (seconds) .................................................................... 144
21.1.4 System properties, Page 2 ............................................................................. 144
21.1.4.1 Door closing by time ............................................................................... 145
21.1.4.2 Main power loss fault delay time (minutes) .............................................. 145
5
Technical Manual
FT1020G3 Rev 2.2.1
22 EBLWin menus ________________________________________________________ 146
22.1 The file menu ....................................................................................................... 146
22.1.1 New ............................................................................................................... 146
22.1.2 Open .............................................................................................................. 146
22.1.3 Import from Win512 ........................................................................................ 146
22.1.4 Report ............................................................................................................ 146
22.1.5 Save .............................................................................................................. 147
22.1.6 Save As ......................................................................................................... 147
22.1.7 Print labels ..................................................................................................... 147
22.2 The View menu .................................................................................................... 148
22.2.1 Filter Box ........................................................................................................ 148
22.2.2 Tree view ....................................................................................................... 148
22.2.3 Deviations ...................................................................................................... 148
22.2.4 Selected loop ................................................................................................. 149
22.2.5 Alarm points ................................................................................................... 149
22.2.6 Interlocking combinations ............................................................................... 150
22.2.7 External faults ................................................................................................ 150
22.2.8 Technical warnings ......................................................................................... 150
22.2.9 External time channels ................................................................................... 151
22.3 The System menu ................................................................................................ 151
22.3.1 Properties....................................................................................................... 151
22.3.2 Time channels ................................................................................................ 151
22.3.3 Alarm algorithms ............................................................................................ 153
22.3.3.1 Parameters for smoke algorithms ........................................................... 154
22.3.3.2 Parameters for heat algorithms ............................................................... 155
22.3.3.3 Parameters for combined decision algorithm........................................... 155
22.3.4 Output Signal Periods ..................................................................................... 156
22.3.5 National holidays ............................................................................................ 157
22.3.6 Two zone dependence ................................................................................... 158
22.3.7 Zone groups ................................................................................................... 158
22.3.8 System information ......................................................................................... 159
22.3.9 Edit Alarm texts .............................................................................................. 159
22.3.10 User data ....................................................................................................... 159
22.4 The Tools menu ................................................................................................... 160
22.5 Web-server .......................................................................................................... 161
23 Download SSD ________________________________________________________ 162
23.1 COM loop menu ................................................................................................... 163
23.1.1 Check Loop .................................................................................................... 163
23.1.2 Auto generate loop ......................................................................................... 163
23.2 SSD Download ..................................................................................................... 164
23.2.1 SSD Download to Single Control Unit ............................................................. 164
23.2.2 SSD Download to Control Units in a TLON Network ....................................... 164
23.3 User definable text messages download ............................................................... 164
24 Download software (System Firmware) ____________________________________ 165
24.1 Single Control Unit (CIE.) ..................................................................................... 165
24.1.1 Establish communications between PC and CIE for software download .......... 165
24.1.2 Download the Software .................................................................................. 166
24.2 Control Units in a TLON network .......................................................................... 167
25 Cable types ___________________________________________________________ 168
25.1 TLON Network cables .......................................................................................... 168
25.2 COM loop cables .................................................................................................. 168
25.3 Remote Display Units cables ................................................................................ 168
25.4 Conventional zone line cables .............................................................................. 168
25.5 Alarm device cables ............................................................................................. 168
25.6 Other equipment cables ....................................................................................... 169
26 FT1020G3 cable length calculation ________________________________________ 170
26.1 COM loop Cable length ........................................................................................ 170
26.2 Cable Length Calculations for 1728 and 1736 ....................................................... 172
6
Technical Manual
FT1020G3 Rev 2.2.1
27 Current consumption ___________________________________________________ 174 28 Power supply _________________________________________________________ 177
28.1 Charger functions ................................................................ ................................. 177
28.1.1 Battery charging ............................................................................................. 177
28.1.2 Battery charging functions: ............................................................................. 178
28.1.3 Battery protection functions ............................................................................ 178
28.2 Current consumption calculations ......................................................................... 178
28.3 Main power source (power supply) ....................................................................... 179
28.4 Standby power source (Batteries) ......................................................................... 179
28.5 Fuses ................................................................................................................... 180
28.6 Current consumption measurement ...................................................................... 180
29 S/W versions __________________________________________________________ 181 30 National regulations ____________________________________________________ 182
30.1 Conventions ......................................................................................................... 182
30.2 Language ............................................................................................................. 182
31 Drawings / Connection Diagrams _________________________________________ 183 32 Revision history _______________________________________________________ 187
32.1 Revision History Table.......................................................................................... 187
32.2 Software Revision V2.2.0 Modifications ................................................................ 187
32.2.1 New common features and additions .............................................................. 187
32.2.2 New or modified features in EBLWin only ....................................................... 188
32.2.3 New or modified feature in system software EBL only ..................................... 188
7
Technical Manual
FT1020G3 Rev 2.2.1
Table of Figures
Figure 1 FT1020G3 System Overview ..................................................................................... 11
Figure 2 Redundant fibre optic network for more than 3 control panels .................................... 16
Figure 3 Redundant fibre optic network for up to 3 control panels ............................................ 16
Figure 4 The FT1020G3 Control Unit, with printer .................................................................... 19
Figure 5 FT1020G3 front display ............................................................................................. 20
Figure 6 Expansion boards 4580, 4581 and 4583. ................................................................... 24
Figure 7 I/O Matrix board 4582. ............................................................................................... 24
Figure 8 Expansion board top side differences ........................................................................ 26
Figure 9 I/O Matrix board application overview ........................................................................ 29
Figure 10 I/O Matrix PCB layout .............................................................................................. 29
Figure 11 Supply air time delay setting .................................................................................... 35
Figure 12 Smoke exhaust or spill fan timing ............................................................................ 36
Figure 13 AS1668 Fan Control Example ................................................................................. 37
Figure 14 Zone Control Connection ......................................................................................... 38
Figure 15 Mimic Board Options ............................................................................................... 40
Figure 16 Generic application, NZ Index panel ........................................................................ 41
Figure 17 Occupant Warning Display Module .......................................................................... 41
Figure 18 Class-D 60W / 120W Audio Amplifier Board Layout ................................................. 43
Figure 19 60W / 120W Audio amplifier photos ......................................................................... 43
Figure 20 Class-D 250W Audio Amplifier Board Layout ........................................................... 44
Figure 21 Typical OWS Dual Strobe Control Circuit ................................................................. 45
Figure 22 Gas Extinguishing Display Layout ............................................................................ 47
Figure 23 Assembled Control & Interface Boards .................................................................... 48
Figure 24 EBLWin properties dialog box for 4301 / 4401(Normal Mode) .................................. 54
Figure 25 Decision algorithm ................................................................................................... 57
Figure 26 Connection example of 2A MDH power supply ........................................................ 71
Figure 27 EBLWin "Input" dialog boxes ................................................................................... 72
Figure 28 EBLWin Voltage & Relay Output dialog boxes ......................................................... 79
Figure 29 EBLWin 3379 and 4477 dialog boxes ...................................................................... 80
Figure 30 EBLWin output signal period dialog box. .................................................................. 84
Figure 31 Signal period set up options..................................................................................... 85
Figure 32 EBLWin control expression ...................................................................................... 86
Figure 33 Short circuit isolators example in FT1020G3 ............................................................ 94
Figure 34 Filter function........................................................................................................... 96
Figure 35 EBLWin "Interlocking Combination" dialog box......................................................... 98
Figure 36 Basic working principle for Analogue smoke sensor ............................................... 103
Figure 37 Filtering algorithm example for analogue smoke detector ....................................... 105
Figure 38 Smouldering smoke algorithm example for 4301. ................................................... 106
Figure 39 Sensor log in graphical form .................................................................................. 110
Figure 40 Sensor Log in Tabulated Form............................................................................... 110
Figure 41 Alert Annunciation function flow chart. ................................................................... 114
Figure 42 Alarm Acknowledgement Facility units ................................................................... 115
Figure 43 Alarm Acknowledgement Facility (AAF) flow chart ................................................. 116
Figure 44 Local Alarm Acknowledgement Facility Connection Diagram ................................. 118
Figure 45 The EBLWin "Control Unit properties" dialog box ................................................... 138
Figure 46 EBLWin "System properties" dialog box, Page 1 and 2 .......................................... 142
Figure 47 Time Channel Alarm Points Report ........................................................................ 147
Figure 48 Deviation Tab ........................................................................................................ 149
Figure 49 Selected Loop Tab ................................................................................................ 149
Figure 50 Time channels configuration .................................................................................. 152
8
Technical Manual
FT1020G3 Rev 2.2.1
Figure 51 Time Channel Setting ............................................................................................ 152
Figure 52 Editing Time Channel Intervals .............................................................................. 153
Figure 53 Alarm Algorithms Dialog Box ................................................................................. 154
Figure 54 Smoke / heat algorithms example .......................................................................... 154
Figure 55 Example setting for national holidays ..................................................................... 157
Figure 56 COM Loop Current Consumtion vs. Cable Length.................................................. 171
Figure 57 Access to COM loop units current consumption ..................................................... 176
Figure 58 FT1020G3 power supply block diagram ................................................................. 177
Figure 59 EBLWin Settings Dialog Box .................................................................................. 182
Figure 60 FT1020G3 General arrangement ................................................................ ........... 184
Figure 61 FT1020G3 Block Wiring Overview ................................................................ ......... 185
Figure 62 FT1020G3 Standard Block Wiring Diagram ........................................................... 186
List of Tables
Table 1 Control Panel Specifications ....................................................................................... 17
Table 2 Control Panel Limitation .............................................................................................. 18
Table 3 Expansion boards address (jumpers) setting............................................................... 25
Table 4 4580 Versions with EOL Values to Use ....................................................................... 26
Table 5 I/O Matrix board 4582 type setting .............................................................................. 30
Table 6 OWS 60/120W amplifier specifications ....................................................................... 43
Table 7 OWS 250W amplifier specifications ............................................................................ 44
Table 8 Connection of the Audio Amplifier 60W, 120W and 250W ........................................... 45
Table 9 Gas Front Status LED Indication and flash Pattern...................................................... 47
Table 10 State of the Supervised Inputs 0-4 ............................................................................ 73
Table 11 Output signal period for programmable output........................................................... 85
Table 12 Smoke Detector Alarm Algorithms .......................................................................... 104
Table 13 Alarm acknowledgement function ........................................................................... 117
Table 14 Summary of Recommended Cables........................................................................ 169
Table 15 Maximum display units cable length ........................................................................ 173
Table 16 FT1020G3 and CIE options current consumption .................................................... 174
Table 17 COM loop units current consumption ...................................................................... 175
Table 18 Other units current consumption ............................................................................. 176
Table 19 Valid S/W versions ................................................................................................. 181
Table 20 List of FT1020G3 block wiring diagrams ................................................................. 183
9
1 Introduction
1.1 General introduction
FT1020G3 Technical / Programming Manual is a document with information of special
interest for planning engineers as well as service / commissioning engineers.
This document should be read in conjunction with FT1020G3 Operation Manual since most of the information in one of the documents is not found in the other document and vice versa.
It should also be read in conjunction with the FT1020G3 connection diagrams according to the drawings / connection diagram list on Table 20 page 183.
When planning a fire alarm installation, the Australian standard AS1670.1 requirements must be followed. Detector type, detector coverage area, detector spacing and special applications in the building, etc. are concerns for the planning engineers and are not covered in this document.
Due to continual development and improvement, different S/W versions are to be found. This document is valid for S/W version V2.2.x. On the date / revision date of the document x = 0.
Technical/Programming Manual
FT1020G3 Rev 2.2.1
A product may be one of the following:
FT1020G3 CIE Configured for 510 or 1020 alarm points and with or without printer. FT1020G3 CIE without front configured for 510 or 1020 alarm points. FT1020G3 CIE with 2 x 5010 and one front to increase the number of COM loops
to 8 and optional I/O matrix board applications.
Hardware H/W: A H/W (e.g. a printed circuit board) has:
a part number (e.g. 5010) a product name (e.g. FT1020G3 Main Board 512 alarm points) a PCB number (e.g. 9290-2B) and can also have a configuration (e.g. CFG: 2)
and a revision (e.g. REV: 1)
sometimes a S/W
Software S/W:
A S/W has:
A version number (e.g. V2.2.x) Sometimes additional information, such as Convention (different functions /
facilities), Language, etc. added.
PC S/W: A PC S/W is a program used for programming, commissioning, etc. e.g. EBLWin. It has a
version number e.g. V2.2.0.
1.2 Definitions / Explanations
Definitions / explanations / abbreviations / etc. frequently used, refer to FT1020G3 operation manual.
Refer to FT1020G3 Operation Manual for more details.
9
FT1020G3 Rev 2.2.1
Product type no.
Product name
4580
8 zones expansion board
4581
8 relay outputs expansion board
4583
Inputs and outputs expansion board
1
2 Overview
2.1 The FT1020G3 system
FT1020G3 is a microprocessor controlled intelligent fire alarm system, intended for
Analogue addressable smoke detectors, as well as conventional detectors and manual call points. Programmable control outputs and output units are available. Up to 1020 addresses can be connected to each Control Unit (CIE). Figure 1 presents an overview of the FT1020G3 System.
FT1020G3 is available in several types, versions and configurations. It can be used as stand-alone Control Unit or connected to a TLON network, i.e. in a "system" with up to 30 Control Units. Each Control Unit has access to all information.
FT1020G3 is designed and assessed to the Australian Standard AS7240.2, AS7240.4 and NZS4512:2010. The Fire Brigade Panel controls and indicators are incorporated as part of the faceplate and conform to AS4428.3:2010.
2.1.1 Printer
Technical/Programming Manual
The Control Unit FT1020G3 can be fitted with an optional printer1.
2.1.2 Expansion boards
Up to six expansion boards can be mounted in FT1020G3 CIE. The following expansion board types are available:
For more details, refer to chapter "Expansion boards 458x, page 24 and drawings F728, F729 and F731.
2.1.3 Power supply
The primary power source is a switch mode power supply, 230 VAC / 24 VDC, 6.5 A (150 Watt).
The standby power source is a backup batteries (2 x 12 V). In the standard cabinet, up to 24 Ah batteries can be fitted. Larger batteries (up to 65 Ah) require additional battery box.
The batteries and the switch mode power supply are connected to the Main board (5010). See chapter "Power supply", page 177 for more information.
2.2 Software (S/W) versions
Due to continual development and improvement, S/W versions are being updated from time to time. When a new FT1020G3 Control Unit is required to be installed in a network system with "older" Control Units, the software in the older Control Units must be updated (or download an older version in the new Control Unit). The S/W version must be the same in all Control Units in a TLON network.
Printer 5058 is a spare part for the FT1020G3 with a printer, i.e. it comes without a mounting frame etc.
10
Technical/Programming Manual
4380
Addr.
Becon
3379 Addr.
Sounder Base
with
430x Analog
Detector
3377
Addr. Siren
BARIL
Remote
Indicator RIL
3314
Address
Setting
Tool
1736 Alert
Annunciation
Unit
1728 Ext.
Presentation
Unit
3333NZ
NZ Addr.
MCP
NZ/Remote
Mimic Panel
4582 I/O
Matrix
Board
SUB927
NZ Mimic
Board
3366 Ext. Power Supply
DC
AC
24V DC
230V AC
3364 Addr.
2 Voltage
Outputs
Unit
4301
Analogue
Photoelectric
Smoke
Detector
3308
Analogue Heat
Detector
4300
Analogue
Multi
Detector
M5411D
Magnetic
Door
Holder
3339
Enclosed
MCP
1598
Web-
Server II
6377
Duct
Detector
3340
AAF Alarm
Acknowledgement Facility
Horn - B24VHHorn - B24VH
2 Outputs
2 Programmable
Inputs
COM Loop (4x)
1590 TLON Board (0)
1590 TLON Board (1)
TLON Network
WebG3 Config via USB cable
VISIODOCUMENT Date: 12/19/2011
Drawn by: Edwin Thein
Pre 2003 NZ
Heat Detectors
4352
Photoelectric Smoke
Detector
Pre 2003 Devices
Conventional Devices
Post 2003 Devices
SUB947
3361
Multipurpose I/O
1590 TLON Board (0)
1590 TLON Board (1)
1590 TLON Board (0)
1590 TLON Board (1)
1590 TLON Board (0)
1590 TLON Board (1)
4352
Photoelectric
Smoke
Detector
4318
Combination
Heat
Detector
4375
Heat
Detector
Conventional Detectors & MCPs
EOL 4K7
4580 TLON Board (0)
4580 TLON Board (7)
4350 Multi Detector
6295 IP67 Heat Detector
30 Units
For NZ
ONLY
FT1020G3 Rev 2.2.1
Figure 1 FT1020G3 System Overview
11
2.3 Documents
The following documents are available:
Technical / Programming Manual (this document) Operation Manual Connection diagrams
Information found in one document is normally not to be found in another document, i.e. the documents complement each other. Product Leaflet for FT1020G3 and other units
are available on Brooks web site: http://www.brooks.com.au. Some important information might be exist in the operation manual as well as this
manual e.g. specifications / limitation, SSD and software download, etc.
2.4 Applications
The FT1020G3 system is intended for small, medium and large size installations. The intelligent Control Units offer the system designer and end user a technically sophisticated range of facilities and functions. Programming (PC software EBLWin and TLON Manager) and commissioning of the Control Units / system is very easy.
Technical/Programming Manual
FT1020G3 Rev 2.2.1
Start with one Control Unit and then when it is required, add more units. The TLON network makes it possible to install the Control Units in one building or in many buildings.
Separate documents are available for TLON Manager, Web-server, etc.
2.5 PC software (S/W)
The following PC programs are used together with the FT1020G3 system. For standalone FT1020G3, the TLON Manager is not used.
2.5.1 EBLWin
The PC program EBLWin is used for programming and commissioning of one or more Control Units, i.e. to:
Autogenerate, i.e. to identify the units connected on a COM loop and make default
settings, which can be edited, saved and used as site specific data (SSD).
Create, download and backup (upload) of site specific data (SSD) Download new system software version, settings, conventions, configurations,
Control Unit & system properties, etc.
Create and download the user definable alarm text messages shown in the display
in the Control Units and other Display Units (1728 & 1736).
Display the fire alarms, faults and disablements as well as reset, acknowledge and
re-enable, etc.
Configure the Web-server II (5098); create and download / make a backup (upload)
of the configuration data as well as download of Web-server software.
The EBLWin must have the same version number as the system software EBL512 G3 version number e.g. 2.2.x and 2.2.x respectively. Only x may be different, it indicates a small correction and is not required to be the same.
Old SSD files can be opened in a newer (higher) version of EBLWin, saved, edited and thereafter downloaded to an FT1020G3 units with the corresponding version.
EBLWin key 5094 is a USB dongle that is required on your PC in order to gain access to log on and download SSD files.
12
Notes: The SSD files saved in one version of EBLWin is not backward compatible with any other earlier versions of PC configuration e.g. WinG3.
It is highly recommended to backup (upload) the SSD file before the system software (EBL512 G3) can be downloaded,
2.5.2 TLON Manager
The PC program TLON Manager is used for the TLON Network programming, installation, etc. (TLON Manager 1.2 and TLON Manager 2.0.x can be used).
For more information refer to the TLON Manager technical manual and the next chapter.
Technical/Programming Manual
FT1020G3 Rev 2.2.1
13
FT1020G3 Rev 2.2.1
3 TLON Network
For further details refer to “TLON Technical / Operation Manual” M437, see also chapter TLON connection board 5090” page 50.
3.1 FT1020G3 TLON network
FT1020G3 system can be one Control Unit (CIE) or up to 30 Control Units connected in a TLON Network.
In a TLON Network, each Control Unit operates independently but has nevertheless total access to all information in the system.
In a system with two or more Control Units in a TLON Network, pay attention to the following:
A zone must not be distributed over the system, i.e. all alarm points in a zone
have to be connected to one CIE
When the "Fire door closing" function is used, the alarm points and the outputs
activated by these alarm points must be connected to the same CIE
Technical/Programming Manual
When the interlocking function is used, the input, output and the Interlocking
Combination (area-point) must be connected to one CIE. An input and an output can only be used in one Interlocking combination.
When the AAF function is used, all devices within the same AAFC zone must be
connected to the same CIE.
3.2 Redundant TLON Network
The FT1020G3 system can be build up as a single TLON Network or as a redundant TLON Network.
A single TLON Network is only allowed when more than one main board (5010) are mounted in the same cabinet. In this case, only one TLON connection board (5090) is required to be plugged in the main board. Whereas in a distributed systems, redundant TLON Network must be used, 2 TLON connection boards (5090) have to be used in each Control Unit.
In the single TLON Network, only one network (Network no. 0) connection is used but in a redundant TLON Network, two networks connections (Network no. 0 and Network no. 1) must be used. In normal conditions, Network no. 1 is only supervised / monitored until Network no. 0 fails to establish the communications between the control panels.
The redundant TLON Network supports full functionality. In case of a network fault (i.e. open circuit or short circuit) in one of the TLON networks, a fault for this TLON Network is generated as shown in the following fault message:
Where network x = Network no. 0 or Network no. 1.
3.3 Routers
In a TLON network, it is recommended to use TP/FT routers in order to split the TLON network into separate FTT-10 channels / segments with the following objectives:
Provide galvanic isolation between TLON segments.
FAULT: Control Unit xx has no contact With control unit xx, network x
14
Technical/Programming Manual
FT1020G3 Rev 2.2.1
Increase the maximum cable length between TLON segments. Reduce unnecessary communications traffic on the respective network links. Improve efficiency of the communications channel. Up to 6 control panels can be connected to one channel i.e. one segment.
When the TLON is divided into more than one segment, the short circuit will affect the communication between the Control Units in this segment only, the communication between Control Units in other segments are not affected. The fault messages will be generated in every Control Unit. However In a redundant system, the network will continue to communicate via the second TLON network.
Dividing the TLON network into segments may assist in fault finding, faults on the network e.g. disturbances etc., will be easier to locate and service.
Note: In retrofit network application where the cable integrity is uncertain, routers may also be required to improve the communications between the TLON segments.
The recommended TP/FT10 router is LPR10, Brooks stock number FTG3 ROUTER. It is also recommended to use the DIN rail mounting plate, stock number FTG3 ROUT PLATE.
3.4 Network connections
The communications between control panels in a network system can be established using one of the three following options:
3.4.1 Twisted pair TLON network
The twisted pair cable connection between control panels and cable specifications are shown in drawings F738-01, F738-02 and F738-03.
The recommended cable is twisted pair 1.5 mm², Brooks stock number BCA0898 or equivalent. 1 mm² Twisted pair cable can also be used depending on the distance between the control panels. If a screened cable is used, the shield must be connected to the CIE earth point.
3.4.2 Fibre optic TLON network
Third party TP/FT10 to fibre optic routers have become obsolete e.g. LRW112 series. However LRW102 series repeaters are still available.
It is possible to connect a TP/FT10 channel to a fibre optic channel using a Fibre Optic to TP/FT10 repeater.
A fibre optic network communications can be achieved by using fibre optic repeater e.g. LRW102 in conjunction with a TP/FT10 router e.g. LPR10. This combination replaces the fibre optic routers LRW112 series when more than 10 control panels connected in a TLON network. Great care shall be taken during planning, installation and commissioning.
The fibre optic link offers an easy way to extend the distance between TLON network segments using high speed back bone fibre optic network link. The maximum distance between the fibre optic routers varies between 5 Km to 30 Km depending on the type of fibre.
The fibre optic solution to network FT1020G3 control panels is shown in Figure 2 and Figure 3 below. The LPR10 router must be used when the number of networked control panels is more than 10 panels as shown in Figure 2.
15
Technical/Programming Manual
FT1020G3 Rev 2.2.1
Figure 2 Redundant fibre optic network for more than 10 control panels
When a number of control panels less than 10 is required in a TLON network, the traffic will not be very heavy and the LPR10 router may not be required as shown in Figure 3
Figure 3 Redundant fibre optic network for up to 10 control panels
The type of fibre optic repeater is dependent on the cable type e.g. single or multi-mode, distance between C.U.’s, etc. Care must be taken when selecting the repeater type.
Note: A TLON network of FT1020G3 control panels may consist of fibre optic segments and twisted pair segments.
3.4.3 TCP/IP TLON network
LonWorks Internet server such as iLon 600, can be used as an internet (or any IP-based LAN or WAN) pathway for TLON.
The transition from TP/FT10 to IP network opens the opportunity to use a large range of infrastructure products e.g. fibre optic converters.
Note: a network of fire alarm system is always connected via a dedicated network wiring, great attention must be taken when choosing an IP network as a pathway for TLON should be used for autonomous Control Units only. The efficiency of the IP based communication is dependent on the efficiency of the infrastructure of the IP network.
16
Technical/Programming Manual
Item
Specifications
Mains Voltage
230VAC (176-264), 1.6A
System Voltage
24VDC @ 6.5A
Current Consumption
Quiescent / alarm current is dependent on other equipment fitted in FT1020G3, type and number of expansion boards, connected external equipment, etc.2.
Ambient Temperature (C)
Operating 0 to + 40, Storage -40 to +70
Ambient humidity (%RH)
Maximum 90, non-condensing
Size (mm)
Standard cabinet 920H x 450W x 210D (with metal door closed)3
Enclosure Material
1.5 Zinc anneal steel
Enclosure Colour
Oyster, powder coated, ripple finish
Approvals
AS7240.2, AS7240.4, AS4428.3:2010 and NZS4512:2010
Standard Inputs / Outputs4
Four COM loops (0-3), each loop can connect up to 255 devices
Four non-supervised inputs
Four programmable Supervised voltage outputs, 0.75 Amp each
Two programmable relay outputs, contact rating 2 Amp
Four programmable clean contact (N/O or N/C) inputs (I0-I3)5
Two non-programmable relay outputs for ASE (fire & fault)
Six x 24V outputs for Web server, ASE, remote display units, external applications 2-4 Amp.
Expansion Boards
Max. 6 of 4580, 4581 or 45836
I/O Matrix 4582 board
Max. 24, 6 per COM loop if no expansion boards on Loop 07 fitted. Up to 6 modules can be used as zone or generic + 18 Fan control modules (4 fans per module)8
2 3
4 5 6
7 8
FT1020G3 Rev 2.2.1
4 Control & Indicating Equipment
4.1 FT1020G3 Specifications
The specifications of FT1020G3 Control Panel are shown in Table 1 below and the system limitations are shown in Table 2 next page.
Table 1 Control Panel Specifications
Refer to chapter “Current consumption” page 173 and the current calculation spread sheet. Medium size enclosure 630H x 450W x 210D can be used to fit limited number of options. A combination of large and medium
size enclosures can be used if more options required. In 19” rack cabinets, a series of 19” face plates are also available. Refer to G3 block wiring diagram, drawing no. F765 First input I0 cannot be used in NZ convention, only 3 programmable inputs are available. Expansion boards are internally connected to COM loop 0, ensure total number of expansion boards and I/O matrix boards
connected to COM loop 0 does not exceed 6. Software 2.1.1 allows to use 6 x 4583. Reduce the number of 4582 connected to COM loop 0 by one for every expansion board used.
If no expansion boards fitted, up to 24 fan control modules can be used i.e. 96 individual fans
17
Table 2 Control Panel Limitation
Item
C.I.E.
Network System
General fire alarm via programmable input
100 External fault via programmable input
50
30 x 50
Programmable inputs
512
Programmable outputs (= control expressions)9
512
Technical warnings
100
30 x 100
Addressable 2 voltage outputs unit 3364
40 External display units
16
30 x 16
Interlocking Combinations
400
400010
Presentation numbers / alarm points11 that can be presented in the display(s) in case of fire alarm
512
512 Presentation numbers8 that can be programmed
512
30 x 512 = 15 360
Zones that can be programmed
51212
999 Faults
300
Disabled zones
512
Disabled alarm points (zone/address) + Disabled COM loops
20013
Disabled outputs
20014
Disabled interlocking outputs
20015
Sensors activating SERVICE signal
200
AAF zones (Max. 5 detectors per AAF zone.)16
100
30 x 100
Total number of expansion boards 4580, 4581 and 458317
6
30 x 6
Number of I/O matrix boards 458218
24
30 x 24
Total number of 4582 for zone control and generic applications
6
30 x 6
Number of user definable text message programmed per 1728 and 1736
617
9
10
11
12
13
14
15
16
17 18
Technical/Programming Manual
FT1020G3 Rev 2.2.1
Approx. 4000 trigger conditions can be used in these control expressions, more outputs can be used without control expression
(V2.1.1 and higher). Max. 100 user definable texts can be displayed "at the same time". Presentation number is a ZONE only or ZONE – ADDRESS. Any zone number between 001 and 999 can be used for the 512 zones. Zone/address disabled via time channel not included. Control outputs disabled via menu H2/B3 and Alarm devices disabled via menu H2/B4 are not included. Interlocking outputs disabled via menu H2/B3 are not included. Used in conjunction with the Alarm Acknowledgement Module (AAM). Expansion boards 4580, 4581 and 4583 are physical connected to COM loop 0
Reduce no. of 4582 boards by one for every expansion board used (4580, 4581 or 4583).
18
FT1020G3 Rev 2.2.1
4.2 FT1020G3 CIE Layout
The FT1020G3 available in many configurations depending on the number of options fitted in the CIE.
Technical/Programming Manual
Figure 4 The FT1020G3 Control Unit, with printer
The FT1020G3 control and indicating equipment (CIE) shown in Figure 4 is housed in a powder coated metal cabinet, colour is oyster. The cabinet has an inner and outer door. The outer door is fitted with 003 keys to provide access level 1 and is made of tinted high impact plastic and allows easy viewing of all indicators and controls.
Access to the inner door is gained by opening the outer door which then provides access to the inner door fixing screws. Opening the inner door allows access to the Control Unit hardware for the purpose of maintenance or servicing
The fire brigade panel (FBP) forms integral part of the control panel (CP) as shown in Figure 5 below, it is used by the fire brigade or fire services personnel to see which alarm point(s) / zone(s) having activated fire alarm and to take required operational control of the system. In the graphical display, the information displayed in the upper part is dependent on how many alarm points / zones having activated fire alarm. In the middle part, the fire alarms will be shown, i.e. one alarm point or one zone together with a user definable alarm text (if programmed) plus some other information.
19
Technical/Programming Manual
19 20
FT1020G3 Rev 2.2.1
Figure 5 FT1020G3 front display
The CP is used to "communicate" with the system, i.e. for commissioning, routine tests, maintenance, etc. Access codes for different access levels are required. A keypad is used to get access to the system (a menu tree with main and sub menus) and for operational control of the system. Up to ten User names can be used for three different User level types. A Password (six digits) for each User name is required19.
The CP has several system status LEDs and a keypad.
Note: Regarding LED indicators, keypad / push buttons / soft keys, user level types and for more information, see FT1020G3 Operation Manual.
Each FT1020G3 Control Unit has the following basic configuration:
Oyster metal cabinet with acrylic door MMI board (5011), see drawing F727
FT1020G3 front with display
Main board (5010), see drawing F726
Four COM loops (0-3) to which the loop units are connected, for
connections and more information, see drawing F784-01, F784-02 and F733.
Four programmable supervised voltage outputs (S0-S3), for connections
and more information, see drawing F732-02.
Two programmable relay outputs (R0-R1), for connections and more
information, see drawing. F732-02.
Four programmable inputs (I0-I3)20, for connections and more information,
see drawing F732-02.
The same User names and Passwords (for the different user levels) can be used for logon to the Web-server. In NZ convention, only I1, I2 and I3 are available i.e. Input I0 cannot be used
20
Technical/Programming Manual
FT1020G3 Rev 2.2.1
Six x 24 VDC power supply outputs for Web-server II (1598), routing
equipment and external equipment requiring battery backed supply. Connections and more information, see Drawing F732-01.
Two non-programmable relay outputs for routing equipment (Fire alarm
output for Fire Brigade TX and Fault output for Fault TX). For connections and more information, see drawing F732-02.
Space and connectors for two TLON connection boards 5090, See
drawing F726 and F732-03.
RS485 and 24VDC outputs for Display Units (1728 & 1736), for
connections and more information, see drawing F765.
Connector for expansion boards (4580, 4581 & 4583), for connections and
more information, see drawing F728, F729 and F731.
Connectors for Web-server (1598), for connections and more information,
see drawing F734.
Connectors for Battery charger DC in and battery termination.
Power supply, see chapter "Power supply", page 177. Connections and more
information, see drawing 765.
Switched mode supply, 230VAC / 24VDC (150 Watt). Space and connection cables for two Sealed Lead-Acid backup batteries. Battery temperature sensor.
Space for up to six optional expansion boards (458x) mounted on two expansion
boards mounting kits.
Space for different brigade (ASE) interface brackets e.g. Romtec, Tyco ASE, etc. Depending on the system requirements and the space available, the following
options can be added to FT1020G3:
Occupant Warning System, 60W, 120W or 250W AS1668 Fire Fan Control Card Zone status indications and control card Gaseous Extinguishing System NZ Fire Brigade mimic display MDH control
See following chapters for more and detailed information.
4.2.1 Mounting plates
The FT1020G3 control panels are equipped with different front and rear mounting plates to suit mounting of compatible equipment, optional application boards and the optional printer.
4.2.2 Mounting plate for 19" mounting rack
When FT1020G3 units are required to be mounted in a 19" mounting rack or cabinets, the standard mounting plates can be replaced with 19” rack mounting plates.
21
4.3 COM loops
21
22
Each FT1020G3 has four COM loops (0-3) to which the loop units are connected. Connections according to drawing F733.
On each COM loop, up to 255 COM loop units can be connected (COM loop address 001 – 255). The exact number of loop units and the cable length are dependent on the cable type (cable resistance) and the total COM loop unit current consumption (i.e. the type and number of loop units). Regarding type and number of COM loop units in relation to the cable length / type, see drawing F733 and chapters "FT1020G3 cable length", page 170 and "Current consumption", page 174.
NOTE: In total, up to 1020 (4 x 255) COM loop units can be used.
Each COM loop unit has a COM loop address (e.g. 123) and depending on the loop number (e.g. 0) and the Control Unit number (e.g. 04), each COM loop unit has a technical number (04 0 123). Each alarm point and zone line input has a fire alarm presentation number (Zone-Address), e.g. 001-01. See FT1020G3 Operation Manual for more information.
Normally the communication (and power supply) direction alternates every 22 second. When the communication is in the COM loop A-direction, the COM loop voltage is checked when the COM loop cable returns to the Control Unit. The voltage has to be > 12 V DC. If not, a fault will be generated.
Technical/Programming Manual
FT1020G3 Rev 2.2.1
4.4 Programmable voltage outputs (S0-S3)
The 24VDC outputs S0-S3 are supervised (monitored)21. One to five 33K resistors can be connected, for connection diagram, refer to drawing F732-02. When all connections are completed, a calibration has to be performed, see chapter "Calibration of supervised outputs" (menu H5/A1)", page 122 and the FT1020G3 Operation Manual. The calibration value should be 1K-50K.
Each output has to be programmed via EBLWin for the following:
Type of output (Control, Alarm devices, etc). Output signal period (steady, pulse, delay, etc.). Supervised / non-supervised. Logic, i.e. normally low (default) or normally high (24VDC). Control expression (contains one or more trigger conditions).
See also chapter "Programmable outputs", page 79.
4.5 Programmable relay outputs (R0-R1)
Connections according to drawing F732-02. Each output has to be programmed (via EBLWin) for the following:
Type (Control, Alarm devices, etc.). Output signal period (steady, intermittent, pulse, delay, etc.) Logic, i.e. normally open (NO) or normally closed (NC) contacts22.  Control expression (one or more trigger conditions).
The outputs in EBLWin are set by default as supervised however, it is possible to change the setting of S0-S3 individually to be
not supervised.
A normally high output cannot be supervised. The supervision voltage is 1.5 – 3.6 VDC (depending on the number of supervision
resistors) and the polarity is reversed compared to activated output.
22
Technical/Programming Manual
23
24
25 26
FT1020G3 Rev 2.2.1
See also chapter "Programmable outputs", page 79.
4.6 Programmable inputs (I0-I3)
Connections according to drawing F732-02. Each input has to be programmed (via EBLWin) for the following:
Type (trigger condition). Logic, i.e. normally open (NO) or normally closed (NC) contacts. Additional information when required, depending on the selected trigger condition
(Fault no., Zone, Address, Fault message (Error text), etc.)
Open = R > 20K. Closed = R < 500. An input has to be activated > 0.5 sec.
See also chapter "Programmable inputs", page 72.
4.7 Relay outputs for routing equipment (TX)
Two dedicated non-programmable relay outputs are used for routing equipment. The outputs can be tested via menu H1. For more information refer to the FT1020G3 Operation Manual. Connections according to drawing F732-02.
4.7.1 Fire alarm output
This output is normally used for fire alarm routing equipment (Fire brigade TX). It is a change-over relay contact that is activated when a fire alarm is generated in the system 23. De-activated output is (normally) indicated by the LED "Fire brigade TX 24.
When a specific zones or alarm points required to call the brigade, any programmable relay can be used and type should be “Fire Brigade TX”.
4.7.2 Fault condition output
This output is normally used for fault warning routing equipment (Fault TX). It is a change­over relay contact that is normally activated and will be de-activated in case of a fault 25 in the Control Unit (CIE) 26. De-activated output (i.e. fault condition) is indicated by the LED Routing equipment "Fault TX activated".
The output can be disabled via "door open" (not recommended) or via menu H2/B5. See also chapter "Alert Annunciation",
page 115.
This output and programmable outputs with type of output = Fire brigade TX, will normally turn on the LED but a programmable
input with trigger condition = Activated routing equipment, can turn on the LED instead. Also when the control unit is powered down (i.e. power supply and batteries are disconnected) or Watch-dog fault. The output can be disabled via "door open" or via menu H2/B5.
23
FT1020G3 Rev 2.2.1
5 Expansion boards 458x
FT1020G3 cabinet provides space for expansion boards holder, up to 4 boards can be mounted on one holder. Another holder can be mounted inside the cabinet for the additional 2 expansion boards. The maximum number of the expansion boards of types 4580, 4581 and 4583 used in each FT1020G3 is six. An expansion board connection cable is to be used to connect expansion boards (connector “J12”) to the main board 5010 (connector “J9”). See drawing F728, F729 & F730.
Figure 6 Expansion boards 4580, 4581 and 4583.
Technical/Programming Manual
I/O Matrix board 4582 is a special type of expansion boards that plugs (piggy back) onto an Application board (Fan, Generic or Zone). The Application board is connected to the COM loop and to 24 VDC. On each COM loop 0-3, up to six 4582
boards can be used (i.e. up to 24 boards in total per FT1020G3 control panel). Refer to drawing F730 for more details.
Note: COM loop 0 is however a special loop, since the expansion boards 4580, 4581 and 4583 are internally connected on this loop. On COM loop 0, up to a total of six 4580, 4581, 4583 and 4582 boards can be used. This means that for each expansion board 4580, 4581 or 4583 used, the number of 4582 boards is reduced by one.
Figure 7 I/O Matrix board 4582.
Maximum six of the I/O Matrix boards 4582 can be programmed as type Generic and/or Zone control.
Note: Maximum 512 programmable outputs per CIE can be used. Each expansion board 4580-4583 must have an expansion board address (0-5) set via
jumpers on the expansion board. The jumpers "JP2-JP4" are used on boards type 4580, 4581 and 4583, and jumpers "JP1-JP3" are used on board type 4582, see Table 3 page
25. Refer to drawings F728, F729, F730 and F731. EBLWin is used for all expansion board programming.
The expansion board address is set via jumpers on the expansion board as shown in Table 3 below.
24
FT1020G3 Rev 2.2.1
Board no. (address)
4580, 4581 and 4583
4582
JP2
JP3
JP4
JP1
JP2
JP3
0
1
X X
2 X X
3 X X X X
4
X X 5
X X X
X
6
7
Table 3 Expansion boards address (jumpers) setting
X=Shunted, Blank = Open Address 6 & 7 are not currently used
Technical/Programming Manual
5.1 8 zones expansion board 4580
Each board has to be programmed via EBLWin with an address (Board no.) which is set via the jumpers "JP2-JP4", see Table 3 above.
The 4580 board has eight conventional zone line inputs (0-7) intended for conventional detectors, MCP, flow switch input or any N/O clean contact. The end-of line device must be connected in the last alarm point on each zone, depending on the selected "Type of zone line input", see below.
Connections to "J1:1-16" and "J2" according to drawing F728. Each zone line input has to be programmed via EBLWin for the following:
Type of zone line input (see below), depending on detectors / end-of-line device
(capacitor or resistor), i.e. different threshold levels etc.
Alarm at short circuit i.e. whether a short- circuit on the zone line input generates
a fault or a fire alarm.
Zone number (address optional) AVF (Alarm Verification Facility), if required Text (Alarm / fault text when required) Alert annunciation time channel Disable time channel
5.1.1 Type of zone line input
Two-unit dependency time channel Type of detectors connected to the zone line input (see “Fire alarm type A and Fire
alarm type B” page 118 for an explanation of A and B)
The terminals support a wire size up to 1.13 mm2 (1.2 mm).
Each input must be selected either as Not used” or as one of the following types / modes.
25
FT1020G3 Rev 2.2.1
4580
SW Version
EOL Resistor to Use
Version 1
9287-2B
1.0.x
10K
Version 2
9287-3A
2.0.x
4K7
5.1.1.1 Zone line input (EOL capacitor)
This mode should normally be used. It has the lowest zone line current consumption since the End-Of-Line device is a capacitor, 470 nF (±10 %).
Maximum allowed cable resistance is 50 ohm. Maximum allowed cable capacitance is 50 nF. Maximum allowed zone line current consumption is 1.5 mA.
5.1.1.2 EX zone line input (EOL resistor)
This mode must be used when the zone line input is intended to be connected to intrinsically safe devices e.g. intrinsically safe detectors or manual call points via the Galvanic isolator MTL5061 (2820). The end-of-line device is a resistor, 10K (±5 %) with a body surface area > 230 mm2 (supplied with the Galvanic isolator).
Maximum allowed cable resistance is 40 ohm. Maximum allowed cable capacitance is 70 nF. Total zone line current consumption is < 1.0 mA.
5.1.1.3 Zone line input (EOL resistor)
Technical/Programming Manual
This mode is typically used in New Zealand where only EOL resistors are allowed. It has to be used when any of the other types cannot be used (e.g. for some older type of detectors and not Panasonic detectors). The EOL resistor has the highest zone line current consumption since the end-of-line device is a resistor, 4K7 (±5 %).
Maximum allowed cable resistance is 50 ohm.  Total zone line current consumption is 2.0 mA.
Note: Older version of 4580 boards PCB9287-2B requires 10K end-of-line resistor while the newer version PCB9287-3A requires 4K7. Table 4 and Figure 8 illustrate the two distinctive differences between the two PCB versions in both hardware and software.
Table 4 4580 Versions with EOL Values to Use
Figure 8 Expansion board top side differences
26
5.1.2 Input states
27
27 28 29 30
Each input will be in one of six different states.
5.1.2.1 Normal state
The normal zone line input state, i.e. no alarm, no fault, etc. and the nominal voltage is 24V
. From this state any other state can be reached / activated.
DC
5.1.2.2 High current state
The maximum current consumption limit28 for the zone line input is exceeded, which is indicating that e.g. too many alarm points are connected. This state generates a fault condition in FT1020G3. From this state any other state can be reached / activated except the open circuit state.
5.1.2.3 Alarm state
One alarm point (or more) on the zone line is in alarm state and the alarm limit28 for the zone line is exceeded which activates a fire alarm in FT1020G3. In this state short-circuit, open circuit, high current and low voltage states cannot be reached / activated. After alarm reset, the zone line input will return to the normal state.
Technical/Programming Manual
FT1020G3 Rev 2.2.1
5.1.2.4 Short-circuit state
The short circuit current limit 28 is exceeded, indicating short-circuit on the zone line which normally generates a fault condition in FT1020G3 but instead, a fire alarm can be activated, if this option is selected via EBLWin.
5.1.2.5 Open circuit state
The open circuit current limit 28 is passed, indicating very low zone line current consumption or no current, i.e. the End-Of-Line device is not detected which generates a fault condition in FT1020G3. From this state any other state can be reached / activated.
5.1.2.6 Disconnected state
Via menu H8/S1 (Disconnect loop / zone line input) the zone line input can be disconnected29, i.e. there is no voltage on the zone line. From this state no other state can be reached / activated.
5.2 8 relays expansion board 4581
Each board has to be programmed via EBLWin for Address (Board no.), set via jumpers "JP2-JP4" as shown in Table 3 page 25.
The 4581 board has eight programmable relay outputs (Output 0-7). Connections to "J1:1-16" and "J2" according to drawing F729. Each output has to be programmed via EBLWin for the following:
Type, i.e. output for Control, Alarm devices, etc. Output signal period (steady, pulse, delay, etc.) Logic, i.e. normally open (NO) or normally closed (NC) contacts30  Control expression (contains one or more trigger conditions)
Voltage range 15-28 V DC. This limit is dependent on the selected input mode. This is indicated in FT1020G3 by the LED Fault / Disablements "General disablements". Relay contact ratings: Max. 2A @ 30 V DC.
27
Loading...
+ 162 hidden pages