Panasonic Fire Alarm Systems Heat Detectors 6275, 6276 Specification Sheet

Panasonic Electric Works Fire & Security Technology Europe AB Citadellsvägen 23, SE-211 18 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info@mfstech.com • www.panasonic-fire-security.com
Fire alarm systems
6275 and 6276
Fixed temperature alarm level
Latching
Can be plugged in a conventional or an addressable base
General
The detectors are conventional fixed temperature heat detectors, i.e. they "give an alarm" at a certain fixed temperature.
6275 goes into alarm at 60°C. 6276 goes into alarm at 80°C. The detector's sensing element consists of a
bimetal contact. At the reached alarm temperature the bimetal makes contact and the detector "gives an alarm". An LED, in the base the detector is plugged into, indicates this. The base also has an output for an external LED indicator 2216 / 2217.
Latching
The heat detectors are latching, i.e. the detectors
will not be automatically reset if the temperature falls below the detector's "alarm temperature" (60°C and 80°C respectively). The detector will be latched and the LED in the base and an ext. LED will be lit until reset is performed in the c.i.e.
Miscellaneous
The detectors 6275 and 6276 can be plugged into a conventional base (2324) connected to a conventional zone line input (or an older addressable base (2330) connected to a COM loop).
Product applications
The heat detectors can be used in the systems EBL500 / 512 / 128 / 1000 / 2000.
The detectors are intended for indoor use and in dry premises.
Heat detector applications are small rooms where the temperature can be expected to rise rapidly in case of a fire or places where smoke detectors can not be used.
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00012 2000-05-15 5 / 2006-08-31
Type numbers
6275
Heat detector, fixed temperature 60°C, latching
6276
Heat detector, fixed temperature 80°C, latching
Technical data
Voltage (V DC) rated
allowed normal
24 12-30 24
Current consumption at nom. volt. (mA)
quiescent (detector only) active (detector only)
Depending on the type of base it is plugged into. For more details, see the base respectively.
0 Max. 70 (Current limitation in all EBL equipment)
Ambient temperature (°C) operating
storage
6275 / 6276
-10 to +40 / -10 to +60
-25 to +70 / -25 to +70 Ambient humidity (% RH) max. 95, non condensing Ingress Protection rating (estimated) IP22 Alarm temp. (fixed temp.)
60°C (6275), 80°C (6276) Weight, detector only (g) 70 Colour grey (N8, Munsell colour code) Approvals CE, EN54-5, response grade 1 (6275)
CE, EN54-8, temp. range 1 detector (6276)
Loading...