This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service
or repair the products dealt with in this service information by anyone else could result in serious injury or death.
IMPORTANT SAFETY NOTICE
There are special components used in this equipment which are important for safety. These parts are marked byin the Schematic
Diagrams, Circuit Board Diagrams, Exploded Views and Replacement Parts List. It is essential that these critical parts should be replaced
with manufacturer’s specified parts to prevent shock, fire or other hazards. Do not modify the original design without permission of
manufacturer.
!
PRECAUTION OF LOW TEMPERATURE
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air
temperature.
12.1.1 Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting
processes. These shifting processes are depending on the air conditioner settings and the operation environment.
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the
electrical power is supplied to the unit.
Remote Control Setting Temperature
60.8F~86F(16C~30C)
Auto Operation Mode Shifting
Indoor Air Temperature Shifting
Outdoor Air Temperature Shifting
Powerful Mode Shifting
Setting Temperature Limit Checking
(Min: 60.8F(16C) ~ 91.4F(33C)
Internal Setting Temperature
12.1.2 Cooling Operation
12.1.2.1 Thermostat control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.7°F (-1.5°C) continue for
3 minutes.
When compressor is OFF (Thermostat OFF) and AUTO FAN is set, the fan will stop periodically.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point.
12.1.3 Soft Dry Operation
12.1.3.1 Thermostat control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -3.6°F (-2.0°C) continue for
3 minutes.
When compressor is OFF (Thermostat OFF) and AUTO FAN is set, the fan will stop periodically.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point.
12.1.4 Heating Operation
12.1.4.1 Thermostat control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +3.6°F (+2.0°C) continue for
3 minutes.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature <
Compressor OFF point.
30
12.1.5 Automatic Operation
y
This mode can be set using remote control and the operation is decided by remote control setting temperature,
remote control operation mode and indoor intake air temperature.
During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the
indoor intake air temperature.
Every 10 minutes, the indoor temperature is judged.
For the 1st judgment
o If indoor intake temperature - remote control setting temperature 3.6°F (2°C), COOL mode is decided.
o If -3.6°F (-2°C) indoor intake temperature - remote control setting temperature < 3.6°F(2°C), DRY mode is
decided.
o If indoor intake temperature - remote control setting temperature < -3.6°F (-2°C), HEAT mode is decided.
-10.8
(-6)
HeatDr
-9.0
-7.2
(-4)
-5.4
(-3)
(-5)
-3.6
(-2)
-1.8
(-1)0(0)
1.8
(1)
3.6
(2)
5.4
(3)
7.2
(4)
Cool
9.0
(5)
10.8
(6)
Unit: F(C)
For the 2nd judgment onwards
o If indoor intake temperature - remote control setting temperature 5.4°F (3°C), if previous operate in DRY
mode, then continue in DRY mode. otherwise COOL mode is decided.
o If -3.6°F (-2°C) indoor intake temperature - remote control setting temperature < 5.4°F (3°C), maintain with
previous mode.
o If indoor intake temperature - remote control setting temperature < -3.6°F (-2°C), HEAT mode is decided.
-10.8
(-6)
-9.0
(-5)
Heat
-7.2
(-4)
-5.4
(-3)
-3.6
(-2)
-
current mode
-1.8
(-1)0(0)
Maintain
1.8
(1)
3.6
(2)
5.4
(3)
7.2
(4)
9.0
(5)
Cool
/Dry
10.8
(6)
Unit: F(C)
12.1.6 Fan Operation
Fan Operation is used to circulate air in a room.
During operation, indoor fan run continuously but outdoor fan and compressor stop.
Temperature setting is not applicable.
12.2 Indoor Fan Motor Operation
12.2.1 Basic Rotation Speed (rpm)
A. Basic Rotation Speed (rpm)
i. Manual Fan Speed
[Cooling, Dry]
Fan motor’s number of rotation is determined according to remote control setting.
Remote control ż ż ż ż ż
Tab Hi Me+ Me Me- Lo
[Heating]
Fan motor’s number of rotation is determined according to remote control setting.
Remote control ż ż ż ż ż
Tab SHi Me+ Me Me- Lo
31
ii. Auto Fan Speed
a
n
L
[Cooling, Dry]
According to room temperature and setting temperature, indoor fan speed is determined automatically.
When set temperature is not achieved, the indoor fan will operate according to pattern below.
F
Speed
Higher
Medium
ower
abc def gh
[1 pattern : 10 s]
ab
When set temperature achieved, the indoor fan speed will be fixed. When thermostat off, the fan stop periodically.
[Heating]
According to indoor pipe temperature, automatic heating fan speed is determined as follows.
RPM Increased
o
F(39oC)
102.2
66.2
o
F(19oC)
RPM Maintain
RPM Reduced
OFF
95oF(35oC)
60.8oF(16oC)
Indoor Pipe Temp.
B. Feedback control
Immediately after the fan motor started, feedback control is performed once every second.
During fan motor on, if fan motor feedback 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error
counter increase, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then H19 - fan
motor error is detected. Operation stops and cannot on back.
12.3 Outdoor Fan Motor Operation
It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.
Compressor:
Outdoor Fan:
ON
ON
Fan Speed
30 sec
OFF
OFF
During cooling operation, and outdoor ambient temperature is below 46.4°F (8°C), outdoor fan speed will be
controlled according to outdoor piping temperature as following:
OD Pipe Temp.
Outdoor fan
B
A
speed increased
Outdoor fan
speed maintain
Outdoor fan
speed reduce
B -5.4°F (B -3°C)
A -5.4°F (A -3°C)
ON
ON
32
OD Pipe Temperature
A 78.8°F (26°C)
B 91.4°F (33°C)
During above condition, when indoor heat exchanger temperature is below 41°F (5°C), the outdoor fan will stop
according to outdoor piping temperature as following:
Outdoor
OD Pipe Temp.
fan ON
Outdoor
fan OFF
86°F (30°C)
12.4 Airflow Direction
There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by
vertical vanes).
Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using
remote control).
12.4.1 Vertical Airflow
Operation Mode Airflow Direction
A 25 17
B 55 37
C 25 17
Heating
Cooling
Soft Dry
Auto with Heat
Exchanger
Temperature
Summer House 55 37
Manual 20 45 55 65 70 17 27 37 47 56
Auto 45 ~ 70 2 ~ 39
Manual 20 25 50 55 70 2 7 17 27 39
Auto 45 ~ 70 2 ~ 39
Manual 20 25 50 55 70 2 7 17 27 39
1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the
angles as stated above. For heating mode operation, the angle of the vane depends on the indoor heat
exchanger temperature as Figure 1 below. It does not swing during fan motor stop. When the air conditioner is
stopped using remote control, the vane will shift to close position.
2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and
the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the
vane will shift to close position.
C
136.4°F (58°C)
B
122.0°F (50°C)
Upper Vane Angle (°) Lower Vane Angle (°)
1 2 3 4 5 1 2 3 4 5
Closed Position
Reference point
Step 1
Upper vane: 60°
Lower vane: 58°
96.8°F (36°C)
A
Indoor Heat
Exchanger Temperature
Figure 1
86.0°F (30°C)
33
Step 2
Step 3
Step 4
Figure 2
Step 5
12.4.2 Horizontal Airflow
Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the
angles as stated below. For heating mode operation, the angle of the vane depends on the indoor heat
exchanger temperature as Figure 1 below. It does not swing during fan motor stop.
Operation Mode Vane Angle (°)
Heating, with heat exchanger temperature
Cooling and soft dry 65 ~115
A 65 ~115
B 90
0°Top View
2
3
1
5
4
109.4°F (43°C)
Indoor Heat Exchanger
Temperature
A: swing
B: fix front
Figure 1Figure 2
104°F (40°C)
Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below
and the positions of the vane are as Figure 2 above.
Pattern 1 2 3 4 5
Airflow Direction Patterns at
Remote Control
Vane Angle (°) 90 65 77.5 102.5 115
12.5 Quiet operation (Cooling Mode/Cooling area of Dry Mode)
Purpose
o To provide quiet cooling operation compare to normal operation.
Control condition
o Quiet operation start condition
When “POWERFUL/QUIET” button at remote control is pressed twice.
POWERFUL/QUIET LED illuminates.
o Quiet operation stop condition
When one of the following conditions is satisfied, quiet operation stops:
POWERFUL/QUIET button is pressed again.
Stop by OFF/ON switch.
Timer “off” activates.
AUTO COMFORT button is pressed.
ECONAVI button is pressed.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
During quiet operation, if timer “on” activates, quiet operation maintains.
After off, when on back, quiet operation is not memorised.
Control contents
o Fan speed is changed from normal setting to quiet setting of respective fan speed.
Fan speed for quiet operation is reduced from setting fan speed.
12.6 Quiet Operation (Heating)
Purpose
o To provide quiet heating operation compare to normal operation.
Control condition
o Quiet operation start condition
When “POWERFUL/QUIET” button at remote control is pressed.
POWERFUL/QUIET LED illuminates.
34
o Quiet operation stop condition
r
r
When one of the following conditions is satisfied, quiet operation stops:
POWERFUL/QUIET button is pressed again.
Stop by OFF/ON switch.
Timer “off” activates.
AUTO COMFORT button is pressed.
ECONAVI button is pressed.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except
fan mode only.
During quiet operation, if timer “on” activates, quiet operation maintains.
After off, when on back, quiet operation is not memorised.
Control contents
o Fan speed manual
Fan speed is changed from normal setting to quiet setting of respective fan speed.
Fan speed for quiet operation is reduced from setting fan speed.
o Fan Speed Auto
Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.
12.7 Powerful Mode Operation
When the powerful mode is selected, the internal setting temperature will shift lower up to 3.6°F (2°C) (for
Cooling/Soft Dry) or higher up to 6.3°F (3.5°C) (for Heating) than remote control setting temperature for
20 minutes to achieve the setting temperature quickly.
12.8 Timer Control
There are 2 sets of ON and OFF timer available to turn the unit ON or OFF at different preset time.
If more than one timer had been set, the upcoming timer will be displayed and will activate in sequence.
12.8.1 ON Timer Control
ON timer 1 and ON timer 2 can be set using remote control, the unit with timer set will start operate earlier than
the setting time.
This is to provide a comfortable environment when reaching the set ON time.
60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to
determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting
time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
12.8.2 OFF Timer Control
OFF timer 1 and OFF timer 2 can be set using remote control, the unit with timer set will stop operate at set time.
Indoorintakeai
temperatureoF(oC)
86 (30)
77 (25)
5min
Cooling/Soft Dry
15 min
10 min
86 (30) 95 (35)
Outdoor air
temperature
oF(o
Indoorintakeai
temperatureoF(oC)
59 (15)
41 (5)
35 min
C)
25 min
30 min
32 (0) 41 (5)
Heating
Outdoor air
temperature
oF(o
C)
12.9 Auto Restart Control
When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be
selected randomly) after power supply resumes.
This type of control is not applicable during ON/OFF Timer setting.
This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.
35