Fire alarm systems
Heat detectors
6275 and 6276
• Fixed temperature alarm level
• Latching
• Can be plugged in a conventional or an addressable base
General
The detectors are conventional fixed
temperature heat detectors, i.e. they "give an
alarm" at a certain fixed temperature.
6275 goes into alarm at 60°C.
6276 goes into alarm at 80°C.
The detector's sensing element consists of a
bimetal contact. At the reached alarm
temperature the bimetal makes contact and
the detector "gives an alarm". An LED, in
the base the detector is plugged into,
indicates this. The base also has an output
for an external LED indicator 2216 / 2217.
Latching
The heat detectors are latching, i.e. the
detectors
the temperature falls below the detector's
"alarm temperature" (60°C and 80°C
respectively). The detector will be latched
and the LED in the base and an ext. LED
will be lit until reset is performed in the
c.i.e.
will not be automatically reset if
Miscellaneous
The detectors 6275 and 6276 can be plugged
into a conventional base (2324) connected to
a conventional zone line input (or an older
addressable base (2330) connected to a
COM loop).
Product applications
The heat detectors can be used in the
systems EBL500 / 512 / 128 / 1000 / 2000.
The detectors are intended for indoor use
and in dry premises.
Heat detector applications are small rooms
where the temperature can be expected to
rise rapidly in case of a fire or places where
smoke detectors can not be used.
Panasonic Electric Works Fire & Security Technology Europe AB
Citadellsvägen 23, SE-211 18 Malmö, Sweden
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99
info@mfstech.com • www.panasonic-fire-security.com
Type numbers
6275
6276
Heat detector, fixed temperature 60°C, latching
Heat detector, fixed temperature 80°C, latching
Technical data
Voltage (V DC)
rated
allowed
normal
Current consumption at nom. volt.
(mA)
quiescent (detector only)
active (detector only)
Ambient temperature (°C)
operating
storage
Ambient humidity (% RH) max. 95, non condensing
Ingress Protection rating (estimated) IP22
Alarm temp. (fixed temp.)
Weight, detector only (g) 70
Colour grey (N8, Munsell colour code)
Approvals CE, EN54-5, response grade 1 (6275)
24
12-30
24
Depending on the type of base it is plugged into. For more details, see
the base respectively.
0
Max. 70 (Current limitation in all EBL equipment)
6275 / 6276
-10 to +40 / -10 to +60
-25 to +70 / -25 to +70
60°C (6275), 80°C (6276)
CE, EN54-8, temp. range 1 detector (6276)
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00012 2000-05-15 5 / 2006-08-31