Panasonic Industrial Company 5RS072FAA21
Air Conditioning Department 208/230V, 60Hz R-410a
5RS072FAA21
Application Cooling (C) / Heating (H)
Ref. Charge Limit (C/H) 16.4 oz. 465 g
(C) 19.4 oz. 550 g
Evaporating Temp Range (C/H)
(C)
5°F to 53.6 °F -15°C to 12°C
14°F to 53.6 °F -10°C to 12°C
Rated Performance at 230 V
Capacity 6,892 BTU/h
Motor Input 740 Watts
Current 3.35 Amperes
Compressor Data
Pump Type Rotary
Displacement 7.26 cm3/rev.
Oil FV50S (PVE)
or equivalent
Oil Charge (Precharged) 10.14 fl. oz. 300 cm
Net Weight 20.1 lb. 9.10 kg
3
Motor Data
Motor Type Permanent Split Capacitor
Locked Rotor Amperes 19 A at 240 V
Winding Resistance
Max. Continuous Current
2
Main: ____Ω, Aux: ____Ω
2
_________
Maximum Operating Conditions
Condensing Temp. 149°F 65°C
Return Gas Temp. 95°F 35°C
Discharge Gas Temp. 239°F 115°C
Motor Wire Temp. 266°F 130°C
Electrical Components
Overload Protector 7100681
Texas Instrument part# MRA 99212-9201
Run Capacitor 15 µF / 370 V
Rated at ASHRAE/T Conditions
Evaporating Temp. 45°F 7.2°C
Condensing Temp. 130°F 54.4°C
Return Gas Temp. 95°F 35.0°C
Liquid Temp. 115°F 46.1°C
Ambient Temp. 95°F 35.0°C
Performance Data
Based on Voltage 230 V, Frequency 60 Hz
Return Gas 65
°F 18.3°C
Liquid Sub Cooling 15°F -9.4°C
Ambient, Air Over 1m/s 95
°F 35.0°C
EVAP. TEMP.
35°F
1.7°C
45°F
7.2°C
55°F
12.8°C
Btu/h 6494 6144 5754 5342 4928
Watts 536 603 668 728 780
Amperes 2.5 2.8 3.1 3.3 3.5
Btu/h 7936 7524 7094 6642 6164
Watts 528 608 677 742 802
Amperes 2.5 2.8 3.2 3.4 3.6
Btu/h 9607 9116 8597 8122 7565
Watts 526 605 677 749 812
Amperes 2.4 2.8 3.2 3.4 3.7
100°F 110°F 120°F 130°F 140°F
37.8°C 43.3°C 48.9°C 54.4°C 60°C
COND. TEMP.
UL file no.: To Be Confirmed 2Contact Panasonic for value