Panasonic Industrial Company 5PS132UAB21
Air Conditioning Department 115V, 60Hz R-410a
5PS132UAB21
Application Cooling (C) / Heating (H)
Ref. Charge Limit (C/H) 24.0 oz. 680 g
(C)
Evaporating Temp Range (C/H)
(C)
28.2 oz. 800 g
5°F to 53.6 °F -15°C to 12°C
14°F to 53.6 °F -10°C to 12°C
Rated Performance at 115 V
Capacity 12,890 BTU/h
Motor Input 1360 Watts
Current 12.15 Amperes
Compressor Data
Pump Type Rotary
Displacement 13.2 cm3/rev.
Oil FV50S (PVE)
Or equivalent
Oil Charge (Precharged) 11.8 fl. Oz. 350 cm
Net Weight 25.8 lb. 11.7 kg
3
Motor Data
Motor Type Permanent Split Capacitor
Locked Rotor Amperes 62 A at 120 V
Winding Resistance
Max. Continuous Current
2
Main: ____Ω, Aux: ____Ω
2
_________
Maximum Operating Conditions
Condensing Temp. 149°F 65°C
Return Gas Temp. 95°F 35°C
Discharge Gas Temp. 239°F 115°C
Motor Wire Temp. 266°F 130°C
Electrical Components
Overload Protector 7100795 / 7100522
Texas Instrument part# MRA 98896-9091 / 98896-
9200
Run Capacitor 45 µF / 260 V
Rated at ASHRAE/T Conditions
Evaporating Temp. 45°F 7.2°C
Condensing Temp. 130°F 54.4°C
Return Gas Temp. 95°F 35.0°C
Liquid Temp. 115°F 46.1°C
Ambient Temp. 95°F 35.0°C
Performance Data
Based on Voltage 115 V, Frequency 60 Hz
Return Gas 65
°F 18.3°C
Liquid Sub Cooling 15°F -9.4°C
Ambient, Air Over 1m/s 95°F 35.0°C
EVAP. TEMP.
35°F
1.7°C
45°F
7.2°C
55°F
12.8°C
Btu/h 12190 11530 10800 10025 9250
Watts 965 1090 1205 1315 1410
Amperes 8.8 9.9 11.0 11.7 12.6
Btu/h 14895 14120 13315 12465 11570
Watts 955 1095 1225 1340 1450
Amperes 8.8 9.9 11.5 12.0 12.9
Btu/h 18030 17110 16135 15245 14200
Watts 950 1095 1225 1355 1465
Amperes 8.6 9.9 11.5 12.0 13.1
100°F 110°F 120°F 130°F 140°F
37.8°C 43.3°C 48.9°C 54.4°C 60°C
COND. TEMP.
UL file no.: To Be Confirmed 2Contact Panasonic for value