Panasonic 5PS132FAA21 User Manual

Panasonic Industrial Company 5PS132FAA21
Air Conditioning Department 208/230V, 60Hz R-410a
5PS132FAA21
Application Cooling (C) / Heating (H) Ref. Charge Limit (C/H) 24.0 oz. 680 g
(C)
Evaporating Temp Range (C/H) (C)
28.2 oz. 800 g 5°F to 53.6 °F -15°C to 12°C 14°F to 53.6 °F -10°C to 12°C
Rated Performance at 230 V
Capacity 13,010 BTU/h Motor Input 1335 Watts Current 5.90 Amperes
Pump Type Rotary Displacement 13.2 cm3/rev. Oil FV50S (PVE)
Or equivalent Oil Charge (Precharged) 11.80 fl. Oz. 350 cm Net Weight 25.8 lb. 11.7 kg
3
Motor Data
Motor Type Permanent Split Capacitor Locked Rotor Amperes 34 A at 240 V Winding Resistance Max. Continuous Current
2
Main: ____Ω, Aux: ____Ω
2
_________
Maximum Operating Conditions
Condensing Temp. 149°F 65°C Return Gas Temp. 95°F 35°C Discharge Gas Temp. 239°F 115°C Motor Wire Temp. 266°F 130°C
Electrical Components
Overload Protector 7100792 / 7100078 Texas Instrument part# MRA 98768-9090 / 98768 Run Capacitor 30 µF / 370 V
Rated at ASHRAE/T Conditions
Evaporating Temp. 45°F 7.2°C Condensing Temp. 130°F 54.4°C Return Gas Temp. 95°F 35.0°C Liquid Temp. 115°F 46.1°C Ambient Temp. 95°F 35.0°C
Performance Data
Based on Voltage 230 V, Frequency 60 Hz Return Gas 65
°F 18.3°C
Liquid Sub Cooling 15°F -9.4°C Ambient, Air Over 1m/s 95°F 35.0°C
EVAP. TEMP.
35°F
1.7°C
45°F
7.2°C
55°F
12.8°C
Btu/h 12520 11845 11095 10300 9500
Watts 950 1070 1185 1290 1385
Amperes 4.3 4.8 5.3 5.7 6.1
Btu/h 15300 14510 13680 12805 11885
Watts 935 1075 1200 1315 1420
Amperes 4.3 4.8 5.6 5.8 6.3
Btu/h 18525 17575 16575 15660 14585
Watts 930 1070 1200 1330 1440
Amperes 4.2 4.8 5.3 5.8 6.4
100°F 110°F 120°F 130°F 140°F
37.8°C 43.3°C 48.9°C 54.4°C 60°C
COND. TEMP.
UL file no.: To Be Confirmed 2Contact Panasonic for value