Panasonic 5PS102FAD21 User Manual

Panasonic Industrial Company 5PS102FAD21
Air Conditioning Department 208/230V, 60Hz R-410a
5PS102FAD21
Application Cooling (C) / Heating (H) Ref. Charge Limit (C/H) 24.0 oz. 680 g
(C) 28.2 oz. 800 g
Evaporating Temp Range (C/H) (C)
5°F to 53.6 °F -15°C to 12°C 14°F to 53.6 °F -10°C to 12°C
Rated Performance at 230 V
Capacity 9,710 BTU/h Motor Input 1040 Watts Current 4.55 Amperes
Pump Type Rotary Displacement 10.2 cm3/rev. Oil FV50S (PVE)
or equivalent Oil Charge (Precharged) 11.83 fl. Oz. 350 cm Net Weight 26.2 lb. 11.9 kg
3
Motor Data
Motor Type Permanent Split Capacitor Locked Rotor Amperes 26 A at 240 V Winding Resistance Max. Continuous Current
2
Main: ____Ω, Aux: ____Ω
2
_________
Maximum Operating Conditions
Condensing Temp. 149°F 65°C Return Gas Temp. 95°F 35°C Discharge Gas Temp. 239°F 115°C Motor Wire Temp. 266°F 130°C
Electrical Components
Overload Protector 7100553 Texas Instrument part# MRA 99027-9201 Run Capacitor 30 µF / 330 V
Rated at ASHRAE/T Conditions
Evaporating Temp. 45°F 7.2°C Condensing Temp. 130°F 54.4°C Return Gas Temp. 95°F 35.0°C Liquid Temp. 115°F 46.1°C Ambient Temp. 95°F 35.0°C
Performance Data
Based on Voltage 230 V, Frequency 60 Hz Return Gas 65
°F 18.3°C
Liquid Sub Cooling 15°F -9.4°C Ambient, Air Over 1m/s 95
°F 35.0°C
EVAP. TEMP.
35°F
1.7°C
45°F
7.2°C
55°F
12.8°C
Btu/h 9177 8682 8131 7549 6964
Watts 747 841 931 1015 1089
Amperes 3.3 3.7 4.2 4.4 4.7
Btu/h 11215 10633 10025 9385 8710
Watts 737 847 945 1035 1119
Amperes 3.3 3.8 4.3 4.5 4.8
Btu/h 13576 12882 12149 11477 10691
Watts 734 844 945 1045 1132
Amperes 3.2 3.7 4.3 4.6 4.9
100°F 110°F 120°F 130°F 140°F
37.8°C 43.3°C 48.9°C 54.4°C 60°C
COND. TEMP.
UL file no.: To Be Confirmed 2Contact Panasonic for value