Fixed temperature (static) alarm level
Fire alarm systems
Heat detectors
4375 and 4376
Fixed temperature alarm level
The conventional fixed temperature (static) heat detectors will give an alarm within a static response temperature range, within a specified response time, in accordance with EN54-5:2000 + A1:2002.
The heat sensitive element is a thermistor. The detector is plugged in a conventional
detector base 2324, connected to a conventional zone line input. An LED on the base will light up when the detector goes into alarm. The base also has an output for an external LED, e.g. 2218.
4375 and 4376
The following types are available (type number, temperature and class):
4375, 60°C, class A2 S. 4376, 80°C, class B S.
Latching
The detectors are latching, i.e. they will not be automatically reset if the temperature, after the alarm, falls below the detector's static response temperature. The LED in the base and a connected external LED will be lit until the detector is reset via the c.i.e.
Environment friendly
The detectors have unleaded soldering.
The latest IC technology reduces the number of semiconductors and other electronic components to a minimum. The detectors fulfils the RoHS Directive.
Product applications
The detectors can be used in the systems EBL500 / 512 / 128 / 1000 / 2000 provided with some zone line inputs for the system respectively (e.g. an 8 zones expansion board 1580 / 4580 zone line input, an addressable multi purpose I/O unit 3361 zone line input, etc.).
Heat detectors are normally used in rooms where the temperature can be expected to rise rapidly in case of a fire or places where smoke detectors can not be used.
The detectors are intended for indoor use and in dry premises premises.
Panasonic Electric Works Fire & Security Technology Europe AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
Type numbers
4375 4376
Heat detector, 60°C, class A2 S. Heat detector, 80°C, class B S.
The zone line is connected to the base 2324 (A+ & B-) Ext. LED is connected to the base 2324 (A+ & L).
A
B
In the detector: See also "Engineering Instructions for detectors Type 435x".
A Contact for base 2324 B Contact for base 2324
The detector is plugged in a base 2324. End-of-line device depending on the zone line input.
Technical data
Voltage (V DC) rated allowed normal
Current consumption at nom. voltage, quiescent (mA)
Current limitation required, when active (mA)
(EBL equipment has current limitation.)
Ambient temperature (°C)
operating (Min. / Typical / Max.) storage
Static response temperature (°C) Ingress Protection rating (estimated) IP51 Size x h (mm) Weight (g) 54 Construction / Colour Modified Polycarbonate / Grey (N8, Munsell colour code) Approvals 07 EC Certificate no. 0786-CPD-20334 (4375); EN54-5 + A1
24 10-30 24 (zone line voltage)
Max. 0.015
Must be min. 6 and max. 100
4375 (A2 S): 4376 (B S):
-10 /+25 /+40 -10 /+40 /+60
-25 to +70 -25 to +70 55 (4375) and 72 (4376)
102 x 39
07 EC Certificate no. 0786-CPD-20335 (4376); EN54-5 + A1
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision