Panasonic 4318 User Manual

Rate-of-rise and fixed temperature alarm levels
Fire alarm systems
Combination heat
detector 4318
General
Heat detector 4318 is a conventional com­bination heat detector, class A1R. It "gives an alarm" at a certain fixed temperature (59°C) and/or at a certain temperature rise, "rate-of-rise" function.
The sensing element is a thermistor. The detector is plugged in a conventional
base 2324 connected to a conventional zone line input.
The base has an LED that will light when the detector goes into alarm. In the base there are terminals to connect an external LED, e.g. 2218.
Environment friendly
The detector has unleaded soldering. The
latest IC technology reduces the number of semiconductors and other electronic components to a minimum.
Product applications
This conventional heat detector can be used in the systems EBL500 / 512 / 128 / 1000 /
2000. The detector is intended for indoor use and
in dry premises. Heat detectors are normally used in small
rooms where the temperature can be expected to rise rapidly in case of a fire or places where smoke detectors can not be used.
Panasonic Electric Works Fire & Security Technology Europe AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
Type number
4318 Combination heat detector
The zone line is connected to the base 2324 (A+ & B-) Ext. LED is connected to the base 2324 (A+ & L).
A
Mark Mark
B
A+
C.i.e. EBL512 / EBL128 / EBL500
+
-
Zone line input
A+ A+
B-
B- L
Zone line
+
Ext. LED
A+
B-
End-of-line
B- L
device
In the detector: See also "Engineering Instructions for detectors Type 435x".
A Contact for base 2324 B Contact for base 2324
The detector is plugged in a base 2324. End-of-line device depending on the zone line input.
Technical data
Voltage (V DC) rated
allowed normal
Current consumption at nom. volt. (mA)
quiescent (detector only) active (detector only)
Ambient temperature (°C) operating
storage Application temperature class A1 (°C)
typical / max. Ambient humidity (% RH) max. 95, non condensing Ingress Protection rating (estimated) IP51
Alarm temp. (T=°C; deltaT=°C/168s) Size x h (mm)
Weight (g) 54 Construction / Colour Modified polycarbonate / Grey (N8, Muncell colour code) Approvals 07 EC Certificate no. 0845-CPD-232.1566; EN54-5, class A1R.
24 10-30 24
Depending on the type of base it is plugged into. For more details see the Product Leaflet respectively, e.g. MEW00008 (Base 2324).
0.015 min. 3
-10 to +50
-25 to +70
+25 / +50
59; 18 (T=static response temp. Class A1 T
min.
=54; T
max.
=65.)
102 x 39
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00852 2007-01-11 3 / 2008-09-18