Panasonic 4313 User Manual

Fire alarm systems
Common base for the different analog detectors
Built-in short circuit isolator
Easy connections incl. output for external LED
Analog base
4313
Common base
The analog base 4313 is connected to a COM loop. Any analog heat, smoke and multi detector types 33xx / 430x can be plugged in the base. (For required type of base, see Product Leaflet for the detector type respectively.)
Short circuit isolator
The analog base 4313 has a built-in short circuit isolator with the same functions as the Addressable short circuit isolator 4370.
The short circuit isolator will divide the COM loop into segments. A segment is the part of a loop between two isolators or between one isolator and the c.i.e. In case of a short circuit on a COM loop, only the affected segment will be disabled, i.e. the number of disabled loop units is minimised. All other loop units will continue to work normally. Up to eight isolators (4313 and/or
4370) can be connected on each COM loop.
Easy connection
The base has screw terminals for the COM loop (in/out) and an external indicator (LED), e.g. 2218.
COM loop address
The COM loop address for the isolator is set with an Address setting tool 3314, which is also used to set the mode:
NORMAL mode 4313 in system EBL128.
2330 mode (2370/4370 in Win512) in system EBL512.
2312 mode
: Short circuit isolator
: Short circuit isolator 4313
: Not used for 4313.
Miscellaneous
The base has an address label (Al) where the detector's and isolator's COM loop addresses can be written.
Individual fault signal is obtained if wrong type of detector (compared with the programming) is plugged in the base or if the detector is unplugged. A short circuit or a single break (cut-off) on the loop will generate a fault and a fault message, e.g. short circuit or break, COM loop number and between which isolators.
For more information regarding detector types, connections, etc. see Planning Instructions and connection diagrams for the system respectively.
Label holder
An optional label holder could be mounted in the base (in the label holder recess) and is intended for a label showing "zone-address" etc. Can be read also when the detector is plugged in the base and is ceiling mounted.
Panasonic Electric Works Fire & Security Technology Europe AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
Product applications
Used in the systems EBL512 / 128 to increase the COM loop safety.
The base is intended for indoor use and in dry premises.
E
)
Type number
4313 Analog base with isolator 3390 Label holder (100 holders per packet, excl. labels) 3391 Labels for 3390 (10 sheets à 132 labels)
xt.
LED
E
+
E
OUT IN
Lss (430x)
LED
o
A
S
B
S
i
A
S
50 mm 73 mm
-
Al
The detector plugged in the base is connected on the SAo side.
Lss (33xx
SAi Terminal for COM loop (in) SAo Terminal for COM loop (out) SB Common terminal for COM loop
in/out)
Al Address Label Lss Locking screw stopper (for detector
type 33xx and 430x respectively)
15
6.2
102 mm
E- Terminal for external LED E+ Terminal for external LED LED Isolator LED (yellow)
Isolator LED: Normal state = one blink 250ms / 3s. Isolated state = two blinks 250ms / 3s. NOTE! The LED is not visible when the detector is plugged in the base.
The base is prepared (Lss) for mechanical locking of detector with locking screw. Terminal wire diameter 0.6 – 1.6 mm (approx. 0.3 – 2 mm
2
). Analog detector types 33xx and 430x can be plugged in the base 4313. The position of the detector's built-in LED is marked in the base for correct mounting position of the base.
Technical data
Voltage (V DC) allowed
normal Current consumption at nom. volt.
from COM loop (mA) quiescent (excl. detector)
active (excl. detector) Ext. LED terminals
voltage (V) max. current output (mA)
Ambient temperature (°C) Operating
storage Ambient humidity (% RH) max. 95, non condensing Ingress Protection rating (estimated) IP54
Size x H (mm) Weight (g) 80 Construction / Colour ABS / Grey (N8, Munsell colour code) Approvals 07 EC Certificate no. 0845-CPD-232.1567; EN54-17
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
12-30 24 (COM loop voltage)
Depending on the type of detector that is plugged into the base.
1.3
<
1.3
< Depending on the detector plugged in the base. Normally:
5 2
-10 to +50
-20 to +60
102 x 15
Product Leaflet Date of issue Revision / Date of revision
MEW00853 2007-01-11 1 / 2008-09-24